9.0 COMPRESSOR ROOM
9.1 FLOOR
The floor must be even and of industrial type; the total weight of the machine is shown in the Chap. 13.0
Remember the total weight of the machine when positioning it.
9.2 VENTILATION
When the machine is operating, the room temperature must not be higher than
46 °C
or lower than
5 °C.
The volume of the room must be about
30 m
3
The room must be provided with 2 openings for ventilation with a surface area of about
0,5 m
2
each.
The first opening must be in a high position to evacuate the hot air, the second opening must be low to allow the intake of
external air for ventilation.
If the environment is dusty it is advisable to fit a filtering panel on this opening.
9.3 EXAMPLES OF VENTILATION OF THE COMPRESSOR ROOM (FIG.11)
FAN AIR OUTPUT
FIG. 11
2
1