Make sure the extension cord is properly wired and in good electrical condition.
Always replace a damaged extension cord or have it repaired by a qualified
electrician before using it.
Protect the extension cords from sharp objects, excessive heat, and damp or wet
areas.
recoMMended MiniMuM wire gauge For eXtension cords*
(120/240 Volt)
naMeplate
aMperes
(at full load)
eXtension cord lengtH
25 Feet
50 Feet
75 Feet
100 Feet
150 Feet
0 – 2.0
18
18
18
18
16
2.1 – 3.4
18
18
18
16
14
3. – .0
18
18
16
14
12
.1 – 7.0
18
16
14
12
12
7.1 – 12.0
18
14
12
10
-
12.1 – 16.0
14
12
10
-
-
16.1 – 20.0
12
10
-
-
-
taBle a
* Based on limiting the line voltage drop to five volts at 150% of the rated amperes.