* Approximate value corresponding to the automatic change of scale (when red light lit:
multiply the reading by 10 to get the result)
Use of the guarded terminal:
To avoid disruption of the insulation
resistance measurement by superficial
earth leakages, connect a safety circuit
using safety terminal “G”.
Insulation resistance measurements (IMEG 1000N)
SWITCH POSITION
250 V
500 V
1kV
MEASUREMENT EXTENT
1...11 *...500 MW
1...11 *...500 MW
1...11 *...500 MW
TEST VOLTAGE
250 V DC
250 V DC
1000 V DC
constant (± 5%)
constant (± 5%)
constant (± 5%)
ACCURACY
± 2.5% of the end of scale value
MAXIMUM VALUE OF
MEASUREMENT CURRENT
5 mA
MEASUREMENT TIME
FOR CAPACITATIVE LOAD
0.2 s/ µF
0.5 s/ µF
0.5 s/ µF
DISCHARGE TIME
8 s/ µF
8 s/ µF
8 s/ µF
PERMITTED OVERLOAD
600 V AC and DC
TYPE OF PROTECTION
Over capacity components