40
To perform a prior check of voltage U
F
, choose a test current: 0.2, 0.3, 0.4, or 0.5 I
D
N
.
To make a faster measurement by eliminating the prior check of voltage U
F
, choose: --x--.
To restore the factory adjustment parameters: I
D
N
= 30 mA, STD and
types.
0.3 I
∆
N
TEST
Press the
TEST
button to start the measurement. The measurement stops automatically.
In the case of type S or G circuit-breakers, the device counts 30 seconds between the prior test of UF and the test of
the RCD itself, in order to allow its demagnetization. This wait can be cut short by pressing the
TEST
button again.
This symbol invites you to wait while the measurement is in progress.
To activate or deactivate the audible voltage alarm (the threshold being equal to U
L
).
This function makes it possible to locate, on the distribution panel, using the audible signal, the RCD
protecting a remote current socket outlet (typical case of a panel at a distance from the socket outlet)
without being in the immediate vicinity of the device.
30 mA
Choice of the nominal current of the residual current device I
D
N
: VAR. (variable: the user programs a value be-
tween 6 and 999 mA), 10 mA, 30 mA, 100 mA, 300 mA, 500 mA, 650 mA, or 1000 mA.
Choice of type of residual current device: STD (standard),
S
or
G
(the S type is tested with a current of 2 I
D
N
as default).
Choice of the form of the test signal:
3.10.3. CONFIGURING THE MEASUREMENT
Before starting the measurement, you can configure it by modifying the parameters displayed:
signal that starts with a positive alternation,
signal that starts with a negative alternation,
signal containing only positive alternations,
signal containing only negative alternations.