18
V AC
and
V AC/DC
400 mV
4 V
40 V
400 V 1000 V
Impedance
> 100 M
Ω
10 M
Ω
Digital
Max reading 399.9 mV 3.999 V
39.99 V
399.9 V
1000 V
Accuracy
1.5% rdg ± 5 counts
on AC
(3)
Accuracy
4% rdg ± 5 counts
on AC/DC
(3)
Max reading
500 mV
5 V
50 V
500 V
1000 V
Scale
50
10
Analogue
Reading
coefficient
x 10
x 0.1
x 1
x 10
x 100
Accuracy
(4)
2.5%
Permitted overload
1000 V
1200 V
4 - DC AND AC VOLTAGES
■
Connect the leads to the multimeter and connect in parallel to the
circuit to be tested.
■
When the order of magnitude is not known, place the switch on the
highest range then progressively lower to the appropriate range.
■
Analogue reading: to get the voltage in V, multiply the value read
on the appropriate scale by the reading coefficient shown in the
table.
■
■
■
■
■
Digital reading: if necessary, press the following keys:
-
for the rms value (See in Ch.3)
-
MAX
for the maximum value
-
HOLD
to hold the value in memory
-
for display backlighting
(1) As % of the reading (rdg) from 5 to 100% of the range
(2) As % of the end of scale
V DC
400 mV
4 V
40 V
400 V 1000 V
Impedance
> 100 M
Ω
10 M
Ω
Digital
Max reading 399.9 mV 3.999 V
39.99 V
399.9 V
1000 V
Accuracy
(1)
1% rdg ± 2 counts
Max reading
500 mV
5 V
50 V
500 V
1000 V
Scale
50
10
Analogue
Reading
coefficient
x 10
x 0.1
x 1
x 10
x 100
Accuracy
(2)
2.5%
Permitted overload
1000 V
1200 V
NB: Accuracies given in the frequency reference range 35 to 500 Hz.
(1) Use possible from 20 Hz to 10 kHz with digital accuracy: 5% rdg ± 5 counts and analogue
accuracy: 5%. Additional error of 1% for a crest factor FC
≤≤≤≤≤
3 and 3% for FC
≤≤≤≤≤
5.
(2) Use possible from 20 Hz to 10 kHz with digital accuracy: 7.5% rdg ± 5 counts and analogue
accuracy: 5%.
(3) As % of the reading (rdg) from 5 to 100% of the range (4) As % of end of scale
(1)
(2)
~
906129433-GB-Ed.4-NF CA 5011.p65
05/03/02, 16:12
18