33
3.3. ELECTRICAL CHARACTERISTICS, SENSITIVITY 10MV/A (PAC 26)
Output impedance: 215
W
Specified
measurement range
0.
5 to 40A
ac/dc
40 to 100A
ac/dc
100 to 150A
dc
Intrinsic uncertainty
≤ ± (3%L + 5 mV)
≤ ± 1.5%L
≤ ± 1.5%L
Phase error (45 to 65Hz)
Specified measurement range
1 to 100A
ac
Phase shift
≤ ‑2°
Typical amplitude error versus frequency curve at 60Hz
Error (%)
Current (A)
-15
-10
-5
0
0,1
1
10
100
Typical amplitude error versus frequency curve at DC
Error (%)
Current (A)
-15
-10
-5
0
0,1
1
10
100
1000