www.charltonandjenrick.co.uk
19
LT5049 (ISS 2)
CLEARANCE TO SHELF
Minimum clearance from hearth to underside of combustible shelf should be 700mm provided shelf depth 150mm
or less. This height may be reduced to 640mm for a shelf depth of 100mm or less. ( Low Lintel 650mm for shelf of
150mm).
When the shelf depth is increased by increments of 12.5 mm greater than 150mm, add 25mm to the 700mm minimum
clearance.
CLEARANCE TO SIDES OF FIRE
Minimum width between vertical sides of combustible surround should not be less than 700mm provided fire is central
to surround and sides do not project more than 150 mm. When vertical side forward projection is increased by 12.5
mm add 50 mm to inside width of surround.
N.B. When fire is fitted this provides a minimum side clearance of 100mm.
Care should be taken to prevent any damage being caused to surrounding soft furnishings or decoration, e.g. many
embossed vinyl wall coverings may become discoloured if placed too close to the appliance.
VENTILATION
In the United Kingdom no special ventilation bricks or vents are required into the room containing the appliance,
provided normal adventitious room ventilation exists. The installer must satisfy this point by carrying out a mandatory
spillage test.
In the Republic of Ireland permanent ventilation must comply with the rules in force
SECTION NINE To Install the Appliance (installation instructions)
EXAMINE FLUE / CHIMNEY
Check that the flue/chimney conforms to the required specifications as previously stated. Examine the condition
and carry out any remedial work. If the flue/chimney has been used for solid fuel or oil, it should be swept prior to
appliance installation. A smoke test must be carried out to check that satisfactory smoke clearance has been
established. If all the smoke is not drawn into the flue, pre-heat the flue with a blowtorch or similar and re-check. If
there is any uncertainty examine for the cause and, if necessary, seek expert advice.
CONNECTING THE GAS SUPPLY
Determine where the gas supply is to be connected to the appliance. This may be done from the front of the unit
from either the left or right side, or a concealed fitting from the rear.