background image

PPE-5095.E

 Page 1 of 2

© 2012 CHARLESWATER LTD.

Unit 17. Millbrook Business Park, Sybron Way • Crowborough, East Sussex TN6 3JZ United Kingdom

Phone: 00 44 (0) 1892-665313, Fax: 00 44 (0) 1892-668838 • Internet: 

Charleswater.co.uk

AC Outlet Analyser and Wrist Strap Tester
Installation, Operation and Maintenance

Description

The Charleswater AC Outlet Analyser and Wrist Strap 

Tester is an easy-to-use, low cost, plug-in tester.  It is 

designed to confirm the proper orientation of hot, neutral 

and protective earth ground.  The product can also be 

used as a wrist strap tester per IEC 61340-5-1 clause 

A.1.

“Wrist straps should be tested periodically.  The 

frequency of testing, however, is driven by the amount 

of usage, wear and ESD risk exposure that can occur 

between tests.  For example, what is the quantity of 

product handled between test periods?
Typical test programs recommend that wrist straps that 

are used daily should be tested daily.  However, if the 

products that are being produced are of such value that 

a guarantee of a continuous, reliable ground is needed 

then continuous monitoring should be considered or 

even required.” (CLC/TR 61340-5-2 user guide wrist 

strap clause 4.7.2.4.4 test frequency)

The AC Outlet Analyser and Wrist Strap Tester is 

available in the following models:

November 2012

Packaging

AC Outlet Analyser and Wrist Strap Tester

1  Certificate of Calibration

Installation

Plug the tester into an AC outlet.  The Outlet Pass LED 

will illuminate green if the outlet’s wiring is correct and 

the path to earth ground via the equipment grounding 

conductor (green wire) is intact.  The tester will alarm 

and Outlet Fail LED will illuminate red if either condition 

is not met.

Operation

1.  Fit the wristband snugly onto your wrist and attach the 

 

wrist cord to it.

2.  Connect your wrist cord to the wrist strap jack 

  located on the face of the tester.
3.  Touch and hold the metal test plate on the tester 

  to perform the test.  The green Test Pass LED will 

  illuminate if the wrist strap contains adequate current 

  limiting resistance and continuity form their skin to 

  earth ground.  Failure is indicated by a 

  non-illuminated Test LED.
  The tester may also be used to check the 

  sleeve-to-sleeve conductive path integrity of ESD 

  protective garments. 

Made in the

United States of America

  TECHNICAL BULLETIN PPE-5095.E

Item

Input Voltage

Plug

99142

220VAC

UK

99143

220VAC

Europe

Figure 1.  Charleswater AC Outlet Analyser and Wrist 
Strap Testers

99142

99143

Reviews: