background image

030-300377 Rev. A

Section CMPH-75CC-801

 CMPH

t

 CROSS-CONNECT SERIES INSTALLATION GUIDE 

3

0905I1P1

 8.  

h

Set base in place.

 Lift the base over the existing cabling and

equipment, and route the wrapped splice and all equipment up

through the base bottom while lowering the base to the bottom of the

hole. If the existing stakes were used, verify they are 

inside 

the

base. If new stakes were attached to the base, insure the hole

accommodates them

Perform Steps 14-15 of Table 1 for the proper

base depth and level

.

 9.  

h

Attach base to re-used stakes.

 Remove the nuts and washers

from the 4 bolts located inside the CMPH base that secure the frame

channels in place (2 bolts on each side, 4” apart). Manipulate the

base and/or stake tops so the re-used stakes fit into the preformed

stake grooves in the base walls. Align the base bolts with the stake

holes, and re-attach the washers and nuts onto the bolts. Firmly

tighten nuts.

 10.  

h

Attach cables to bars and brackets. 

If the splice bars or brackets

were removed, re-install them now in the best positions to support

(and ground) the equipment. Per company practice, attach or mount

all cables and equipment to the internal framework (bars, brackets)

of the CMPH. Re-attach any grounding, bonding, and cable

connections previously unattached to remove the old enclosure.

 11.  

h

Close the CMPH, clean the site. 

Perform Steps 19-24 in Table 1 to

close the CMPH and restore the site to its previous condition.

Table 4.   Making Ground, Cable, and Jumper Connections

Step #

Instructions

 1.  

h

Route cables into CMPH enclosure.

 Per company practice and

local codes

bring the feed and distribution cables into the CMPH

enclosure through the open base bottom. Secure and stabilize the

cables per company practice.

 2.  

h

Open cables.

 Per company practice

perform

 

all cable opening

procedures.

 3.  

h

Bond and strain-relief the

cables. 

Ground or bond the

cable(s) to the ground posts

provided on the ground plate.

Perform cable strain relief and

bonding per company practice.

Attach earth ground to ground lug

Attach cable bond

straps to posts

Ground Plate

Posts to attach plate to ground bracket

 4.  

h

Splice cables to terminal block stubs. 

Per company practice

,

perform

 

cable 

 

splicing and connection procedures to connect the

feeder and distribution cables to the appropriate terminal block

wire-bundle stubs inside the CMPH enclosure.  Perform cable

management techniques per company practice.

 5.  

h

Perform labelling. 

Fill out and complete the label provided on the

top of the internal CMPH framework to facilitate pair identification.

Each toggle port of each terminal block is labelled by the terminal

block manufacturer.

 6.  

h

Mount jumper wire spool.

 Mount the field-provided jumper wire

spool on the provided jumper wire spool holder located inside the

enclosure.

 7.  

h

Locate proper toggles for

first wire pair.

 Locate or

identify the correct toggle in

the correct 

feeder 

terminal

block for the first wire pair

to be placed in service.

Also locate the correct

toggle in the correct

distribution 

block.

 8.  

h

Pull jumper wire from spool. 

Pull the jumper wire from the spool

toward the identified first toggle in the 

feeder 

terminal block.

 9.  

h

Prepare wires of first wire pair.

 Straighten the last 1

2’’ of the

conductor pair wires to be installed and placed in service. Trim the

conductor wire ends evenly, but do not strip the insulation.

 10.  

h

Open feeder terminal block toggle and insert

wires into toggle ports.

 Pinch and pull back the

toggle. Insert the pair into the ports, one wire per

port (two port holes per toggle). Note that ports are

labeled “T” for tip and “R” for ring. Wires should be

inserted about 3/8’’ before bottoming out.

 11.  

h

Close toggle.

 While holding the conductor wires in the toggle ports

with one hand, with the other hand push the toggle closed until it locks

shut. Tug gently on each individual wire to verify a good connection

was made. If a good connection was not made (wire is loose),

disconnect and remove the pair by pinching and pulling back the

toggle, remove the wire pair, then repeat Steps 9 and 10 until a good

connection is made. 

Note: Trim away the scored insulation area of

wire prior to reconnection.)

 12.  

h

Route and dress jumper wire toward distribution block. 

Unwind

enough jumper wire from the spool to reach the identified toggle in

the distribution terminal block. Dress the jumper wire down toward

the bottom of the toggle, then route it sideways along the bottom of

the row of toggles toward the side of the block. Route the jumper

down the block, then over to the side, toward the hinge side of the

door panel, then on towards the panel on the opposite side. Slip the

jumper wire through any installed cable management rings and

behind the race-ways and run guides provided in the CMPH. 

Do not

run wires across the front face of the terminal blocks.

 13.  

h

Cut jumper wire to proper length.

 Per company practice, extend

the wire toward the targeted distribution block’s correct toggle, allow

ample wire slack, and then cut the jumper wire to the proper length.

 14.  

h

Connect wire pair to correct toggle of distribution terminal

block.

 Repeat Steps 9-11 for the proper toggle of the targeted

distribution 

terminal block.

 15.  

h

Test connection.

 To test the wire pair connections, insert the

provided Dat@Term terminal block test clip into the toggle locations.

Make sure the test clip alignment guide is on the hinge side of the

toggle. Attach test set to test clip and test per company practice.

 16.  

h

Complete the label.

 Per company practice, fill out the provided label

to identify the line placed in service.

 17.  

h

Repeat for all lines.

 Repeat above steps for all lines to be placed in

service.

 18.  

h

Replacing toggles.

 In the unlikely event a toggle is damaged,

toggle removal and replacement is accomplished as described

herein. Tyco Dat@ Terminals have rotating wire terminating toggles

that can be removed and replaced if needed. To replace a damaged

toggle:  1. Open damaged toggle to normal open position. 2. Push

toggle out of it’s block cell by rotating it past it’s normal open

position. This will cause it to break free of the holding mechanism in

the block without damaging the block. 3. Once free, remove toggle

from block and discard. 4. Insert new toggle. 5. Rotate toggle into

cell, using care to make sure the toggle axle is mated with the

bearing surface in the block. 6. Rotate toggle until it closes and the

toggle latch locks. Toggle is now replaced. 7. Close any

corresponding opened toggles.

 19.  

h

Perform cable management.

 Verify all equipment and cabling is

organized and will not contact the interior walls of the dome when

installed (keep items at least 1” from the vertical plane of the base

collar). This assures safe and smooth dome placement.

Table 5.   Physical Specifications

Feature

U.S.

Metric

Height, overall

47 in.

119.4 cm

Height, base only, incl. collar

17 in.

43.2 cm

Height, dome only

33 in.

83.8 cm

Height, internal framework

30 in.

76.2 cm

Height, base bottom to ground line

9 in.

22.9

Depth, base (at wider footprint)

17 in.

43.2 cm

Depth, dome

14.5 in.

36.8 cm

Width, base (at wider footprint)

29.5 in.

75 cm

Width, dome

27 in.

68.6 cm

Weight, dome

21 lbs.

9.5 Kg

Weight, base

22 lbs.

10 Kg

Weight, base w/brackets and

terminal blocks

100 lbs.

45 Kg

Weight, two 30” stakes

5 lbs.

2.2 Kg

Weight, two 36” stakes

6 lbs.

2.7 Kg

Weight, two 42” stakes

7 lbs.

3.2 Kg

NOTE:  All dimensions and weights are approximate.

Table 6.   Model Number Ordering Information and Options

Model #

Description

CMPH-7512CC-EMT 1200 Pair Cross Connect CMPH With Tyco Blocks
CMPH-7509CC-EMT 900 Pair Cross Connect CMPH With Tyco Blocks
CMPH-7506CC-EMT 600 Pair Cross Connect CMPH With Tyco Blocks
CMPH-7503CC-EMT 300 Pair Cross Connect CMPH With Tyco Blocks

Optional Equipment for Use with CMPH Cross Connect

CMPH-BOND10

Package of 10 ground plates, each plate

contains a ground lug and 6 bond posts.

Attaches to internal, horizontal, ground

bracket.

19-300545-0

100 pair Tyco Data Term

Terminal Block, 5 ft. cable,

3M MS2 connectors

UMS30-STD

Universal Mounting Stake - 30 inches

UMS36-STD

Universal Mounting Stake - 36 inches

UMS42-STD

Universal Mounting Stake - 42 inches

Various replacement and optional parts are available, including bracket kits for vault-mounting. Contact Charles Industries for
more information.

3.

CUSTOMER TECHNICAL SERVICE

If technical assistance or customer service is required, contact Charles Indus-

tries by calling or using one of the following options:

847-806-8500 (Technical Service local)
847-806-6300 (Customer Service)
800-607-8500 (Technical Service toll-free)
847-806-6653 (Customer Service FAX)
847-806-8556 (Technical Service FAX)

[email protected] (email)
[email protected] (email) 
www.charlesindustries.com

 

(website)

Reviews: