ChargePoint® Charging Stations
1-2
Specifications
Electrical Input
Input Power
7.2 kW (x 2)
Input Voltage
208/240 VAC
Input Current
30 A (x 2)
Input Power Connections
Two independent 40 A branch circuits, each providing Line 1 and Line 2. A single protective Earth conductor.
Required Service Panel Breaker
40A double pole breaker (non-GFCI type) on each dedicated circuit
Service Panel GFCI
Do not provide external GFCI as it may conflict with internal GFCI (CCID)
Standby Power
7 W typical
Electrical Output
Output Charging Power
7.2 kW (x 2)
Output Voltage
208/240 VAC
Output Current
30 A (x 2)
Output Charging Connector
SAE J1772
TM
EV connector on 18’ (5.48 m) cable (x 2)
Functional Interfaces
Card Reader
ISO 15693, 14443
Ground Fault Detection
20 mA CCID with auto retry (15 minute delay, 3 retries)
Plug-Out Detection
Power terminated per SAE J1772
TM
specification
Power Measurement
2% @ 15 minute intervals
Local Area Network
2.4 GHz 802.15.4 dynamic mesh network
Wide Area Network
Commercial GPRS or CDMA cellular data network
Safety and Operational Ratings
Safety Compliance
UL listed for USA and cUL certified for Canada; Complies with UL 2594, UL 2231-1, UL 2231-2, UL 1998,
UL 991, and NEC Article 625
Surge Protection
6 kV @ 3000 A. In geographic areas subject to frequent thunder storms, supplemental surge protection at
the service panel is recommended.
EMC Compliance
FCC Part 15 Class A
Operating Temperature
-22°F to 122°F (-30°C to +50°C)
Operating Humidity
95% non-condensing
Enclosure
Type 3R
Terminal Block Temperature
Rating
212°F (100°C)
Maximum Charging Stations per
802.15.4 Radio Group
24 (each station must be within 150 feet “line of sight” of at least one other station)
Approximate Shipping Weight
98 lbs (44.5 kg)