Channel Safety Systems Zerio Plus Manual Download Page 6

6  |   revision 013-1   

 

 

www.channelsafety.co.uk   



0845 884 7000     @ [email protected]

Input/Output Unit

PRODUCT CODE

DESCRIPTION

F/EDA-T6080 

Zerio Plus radio clean contact input / output unit

In normal operation the EDA-T6080 Zerio Plus Wireless Output unit  
continuously listens via its built in radio receiver to any instruction  
emanating from its controlling panel. Once operated it provides a clean 
contact output switch to operate external equipment.
 
To ensure that the integrity of the communication link is maintained, 
frequent transmissions are made by the EDA-T6080 Zerio Plus Wireless 
Output unit to the control panel so that in the unlikely event of the radio 
signal failing to reach the panel a fault is reported.

Product Dimensions

• Height 

90mm

• Width 

80mm

• Depth 

60mm

SPECIFICATIONS 

Temperature Range

0°C to +60°C

Humidity

0 to 95% (no condensation)

Transmitter Frequency

868 MHz

Transmission Type

Narrow band FM

Channels

13 available

Audible Warning

Sounds in alarm and test mode

Indications

Alarm - high intensity clear LED
Fault - red solid, red fl ashing

Battery

x1 EDA-Q690

Weight

240g

SPECIFICATIONS 

Temperature Range

0°C to +60°C

Humidity

0 to 95% (no condensation)

Transmitter Frequency

868 MHz

Transmission Type

Narrow band FM

Channels

13 available

Audible Warning

Sounds in alarm and test mode

Indications

Alarm - red solid
Fault - red fl ashing
Log-on mode - green solid

Battery

x1 EDA-Q690

Weight

240g

Call Point

PRODUCT CODE

DESCRIPTION

F/EDA-C5000

Zerio Plus call point

The Call point incorporates the radio communication equipment within 
the device.  Powered entirely by a lithium battery assembly,housed within 
the call point;  ensures that no external cables are required to power the 
unit and that the unit can be installed by simply using two screws.

The EDA-C5000 Zerio Call Point is supplied complete with a backbox and 
battery assembly.

Product Dimensions

• Height 

90mm

• Width 

90mm

• Depth 

53mm

Summary of Contents for Zerio Plus

Page 1: ...Wireless system from Channel Safety Systems Zerio Plus...

Page 2: ...acement battery for all devices SPECIFICATIONS Maximum Number of Zones EDA Z5008 8 EDA Z5020 20 Maximum Number of Devices 240 for larger premises upto four systems can be linked together Max no of rad...

Page 3: ...le wireless smoke detector and combined sounder The smoke chamber and internal workings of the EDA R6000 are housed in an attractive low profile exterior The unit is completely self contained and requ...

Page 4: ...detector element and internal workings are housed in an attractive low profile exterior The unit is completely self contained and requires no external cabling and is powered by a lithium battery assem...

Page 5: ...Battery x3 EDA Q690 Weight 440g Visual Indicators The EDA A6000 Zerio Plus Wireless Wall Sounder is a wall mounted and designed specifically to be used with the Zerio Plus range of wireless fire alar...

Page 6: ...on Transmitter Frequency 868 MHz Transmission Type Narrow band FM Channels 13 available Audible Warning Sounds in alarm and test mode Indications Alarm high intensity clear LED Fault red solid red fla...

Page 7: ...vailable Audible Warning Sounds in alarm and test mode Battery 1 x 12V 7AH for booster only Booster Panel and Antennas PRODUCT CODE DESCRIPTION F EDA Z6000 Zerio Plus booster panel requires 240V suppl...

Page 8: ...oning service for this equipment For more details contact our Technical Services department on 0845 884 7000 or email service channelsafety co uk Case Contents 1 x Survey Detector SSD 1 x Survey Trans...

Reviews: