Channel Safety Systems Zerio Plus Manual Download Page 2

2  |   revision 013-1   

 

 

www.channelsafety.co.uk   



0845 884 7000     @ [email protected]

Zerio Plus

The Zerio Plus Radio Fire Alarm System has been 
designed to meet the requirements of EN54 Part 
25. 

With the wireless system up to 240 devices across a maximum of 100 
zones is achievable; meaning the system off ers the perfect solution 
for small domestic buildings up to large commercial premises. The 
panel, although simple to use, off ers sophisticated features more 
commonly seen in larger hard wired equivalents. 

Setting the system up could not be simpler. Each device is 
programmed onto the system using a clearly laid out user-friendly 
menu structure. There is no need to connect the device with a 
programming lead, as the confi guration is achieved by radio. 

Location descriptions can be added by using a PC or simply 
programmed using a standard PC keyboard plugged into the panel 
or, for a single device, the in-built keypad.

With analogue detector functionality and complex multi-path 
fault tolerant signalling, the system minimizes false alarms whilst 
providing maximum protection for the occupants of a building. In 
order to increase the radio range of the system, either wired or radio 
booster panels can be installed at appropriate positions. During the 
automatic set-up the system will confi gure this equipment to ensure 
the most eff ective operation is achieved. 

Typical Application

The Zerio Plus wireless system is suitable for all sizes of building such 
as;
• Large 

offi

  ce blocks

• Hotels
• Small 

shops

• Restaurants

Wireless system

PRODUCT CODE

DESCRIPTION

F/EDA-Z5008

8 zone Zerio Plus control panel (requires 12/7 battery)

F/EDA-Z5020 

20 zone Zerio Plus control panel (requires 12/7 battery)

N/CH12/7

12V 7AH battery

S/BATT/EDA-Q690

Spare/replacement battery for all devices

SPECIFICATIONS 

Maximum Number of Zones

EDA-Z5008 8 EDA-Z5020 20

Maximum Number of Devices

240 (for larger premises upto four 
systems can be linked together)

Max no of radio control / booster 
units

15 (per system)

Alarm Indicators

Twin fl ashing red LEDs
Red individual zone indication
Fire message on LCD with 60 scroll-
ing characters of location text

Fault Indicators

Amber LEDs and LCD providing 
details and location of fault with 60
scrolling characters of location text

Event Log Storage

255 events maximum

Mains Supply

230V 50Hz 0.3A max

No of Relays

(Programmable) 2
Fire -1A Changeover Contacts
Fault -1A Changeover Fail Safe 
Contacts
12V Sounder Circuit (500mA)

Operating Frequency

868MHz

Modulation

NBFM

Output Power (ERP)

10mW

Operational Temperature

0°C to +60°C

Monitored Inputs

2 x wired monitored circuit (4k7Ω 
end of line resistor monitored for 
open and short circuit, 470 Ω alarm 
load)

Battery

1x12V 7.0 Ah sealed lead acid

Weight

4Kg (not including battery)

Product Dimensions

• Height 

220mm

• Width 

275mm

• Depth 

85mm

Tracey Park Golf Club were under pressure to install a fi re alarm 
and detection system; being a listed building that was constantly 
in use, running cables would not have been an acceptable option. 
A wireless radio system was proposed due to the constraints and 
within only a few days the Zerio Plus wireless system was installed 
and commissioned. The EN54 Zerio Plus system met all the clients 
needs for a simple to use cost eff ective system; without the hassle of 
wiring and cable management detracting from the aesthetics of the 
building.

Features

• EN54 

Compliant

• 

240 Fully Addressable Devices

• 

Sophisticated Cause and Eff ects

• 

In-built HMO options

• 

Plugable Memory Module for Back-up

• 

USB Keyboard to program

• Confi guration Reporting via USB Memory Stick
• 

Intuitive Menu Structure

• 

5 Access Levels

• 

Compatible with full range of Zerio Plus Devices

• 

Simple to Set-up

Tracey Park Golf Club in Bath

Summary of Contents for Zerio Plus

Page 1: ...Wireless system from Channel Safety Systems Zerio Plus...

Page 2: ...acement battery for all devices SPECIFICATIONS Maximum Number of Zones EDA Z5008 8 EDA Z5020 20 Maximum Number of Devices 240 for larger premises upto four systems can be linked together Max no of rad...

Page 3: ...le wireless smoke detector and combined sounder The smoke chamber and internal workings of the EDA R6000 are housed in an attractive low profile exterior The unit is completely self contained and requ...

Page 4: ...detector element and internal workings are housed in an attractive low profile exterior The unit is completely self contained and requires no external cabling and is powered by a lithium battery assem...

Page 5: ...Battery x3 EDA Q690 Weight 440g Visual Indicators The EDA A6000 Zerio Plus Wireless Wall Sounder is a wall mounted and designed specifically to be used with the Zerio Plus range of wireless fire alar...

Page 6: ...on Transmitter Frequency 868 MHz Transmission Type Narrow band FM Channels 13 available Audible Warning Sounds in alarm and test mode Indications Alarm high intensity clear LED Fault red solid red fla...

Page 7: ...vailable Audible Warning Sounds in alarm and test mode Battery 1 x 12V 7AH for booster only Booster Panel and Antennas PRODUCT CODE DESCRIPTION F EDA Z6000 Zerio Plus booster panel requires 240V suppl...

Page 8: ...oning service for this equipment For more details contact our Technical Services department on 0845 884 7000 or email service channelsafety co uk Case Contents 1 x Survey Detector SSD 1 x Survey Trans...

Reviews: