Model

 80° F Ambient

 90° F Ambient

 9° F Ambient

 100° F Ambient

110° F Ambient

box Temperature

0° F  -10° F -0° F 0° F  -10° F -0° F 0° F  -10° F -0° F 0° F  -10° F -0° F 0° F  -10° F -0° F

PTN019L6

2,960 N/A

N/A 2,640 N/A

N/A 2,470 N/A

N/A 2,270 N/A

N/A 1,910 N/A

N/A

PT*021L6

3,220 2,590 1,610 2,860 2,300 1,430 2,680 2,160 1,340 2,470 1,990 1,230 2,080 1,670 1,030

PT*031L6

5,060 3,830 2,470 4,500 3,400 2,200 4,220 3,190 2,060 3,880 2,940 1,900 3,260 2,470 1,600

PT*044L6

7,040 5,440 4,080 6,260 4,830 3,630 5,870 4,530 3,400 5,400 4,170 3,130 4,540 3,500 2,630

PT*052L6

8,400 6,430 4,690 7,470 5,720 4,170 7,000 5,360 3,910 6,440 4,930 3,600 5,410 4,140 3,020

PT*069L6

10,870 8,520 6,300 9,670 7,850 5,600 9,060 7,100 5,250 8,340 6,530 4,830 7,010 5,490 4,060

*T For Outdoor, N for Indoor.     

Model

voltage

McA MOPd Unit 

Amps

Evaporator 

cFM

Plug 

supplied

Matching 

NEMA 

receptacle

dimensions 

Figure¹

Approximate Net 

Weight

lbs.

kg

PTN024H2A

115/1/60

10.2

15

10.2

340

Yes

5-20R

A

88

40

PTN029H2A

115/1/60

10.6

15

10.6

340

Yes

5-20R

A

90

41

PTN040H2A

115/1/60

11.7

15

11.7

340

Yes

5-20R

A

92

42

PT*047H2A

115/1/60

16.9

20

14.2

350

Yes

5-20R

B

192

87

PT*047H2B

208-230/1/60

8.6

15

7.3

350

Yes 

2

6-15R

B

192

87

PT*063H2B

208-230/1/60

11.6

15

9.9

550

Yes 

2

6-15R

B

207

94

PT*072H2B

208-230/1/60

10.9

15

9.3

500

Yes 

2

6-15R

B

211

95

PT*099H2B

208-230/1/60

17.1

20

14.7

875

Yes 

2

6-20R

C

270

122

PT*099H2C

208-230/3/60

15.4

20

13.3

875

No

C

265

120

PT*128H2B

208-230/1/60

20.3

30

17.2

825

No

C

290

132

PT*128H2C

208-230/3/60

14.8

20

12.8

825

No

C

285

129

PTN019L6A

115/1/60

13.0

20

13.0

340

Yes

5-20R

A

101

46

PT*021L6A

115/1/60

14.5

20

12.3

350

Yes

5-20R

B

213

97

PT*021L6B

208-230/1/60

7.6

15

6.5

350

Yes 

2

6-15R

B

213

97

PT*031L6B

208-230/1/60

13.8

15

11.6

550

Yes 

2

6-15R

B

221

100

PT*044L6B

208-230/1/60

15.9

20

13.3

520

Yes 

2

6-20R

B

225

102

PT*052L6B

208-230/1/60

18.1

20

15.3

900

Yes 

2

6-20R

C

275

125

PT*052L6C

208-230/3/60

12.2

15

13.0

900

No

C

270

122

PT*069L6B

208-230/1/60

23.8

30

20.0

875

No

C

280

127

PT*069L6C

208-230/3/60

15.9

20

14.2

875

No

C

275

125

*T For Outdoor, N for Indoor.     

2

 Plug supplied on Indoor models only.  

1

 see dimensions page 6.

Model

 80° F Ambient 

 90° F Ambient 

 9° F Ambient   100° F Ambient   110° F Ambient 

box Temperature

° F

8° F

° F

8° F

° F

8° F

° F

8° F

° F

8° F

PTN024H2

2,800

2,920

2,630

2,740

2,540

2,650

2,460

2,570

N/A

N/A

PTN029H2

3,380

3,500

3,170

3,290

3,070

3,180

2,980

3,090

N/A

N/A

PTN040H2

4,660

4,790

4,380

4,500

4,240

4,350

4,110

4,220

N/A

N/A

PT*047H2

5,480

5,830

5,150

5,480

4,980

5,300

4,830

5,140

4,250

4,520

PT*063H2

7,350

7,800

6,910

7,340

6,680

7,100

6,480

6,890

5,700

6,060

PT*072H2

8,400

8,870

7,890

8,330

7,630

8,060

7,400

7,820

6,510

6,880

PT*099H2

11,540

12,470

10,850

11,730

10,490

11,340

10,180

11,000

8,960

9,680

PT*128H2

14,930

15,970

14,030

15,010

13,570

14,520

13,160

14,080

11,580

12,390

Model PTN/PTT

 

High/Medium Temperature | Air Defrost | Cooler Application

Model PTN/PTT

 

Low Temperature | Electric Defrost | Freezer Application

Model PTN/PTT

 

Electrical Data | Specifications | All Models

*T For Outdoor, N for Indoor.     

PeRfoRManCe, CaPaCiTies and sPeCifiCaTions

Summary of Contents for PRO3 Top Mount PTN

Page 1: ...CH PTMTB January 2008 Replaces CH PROTB 08 07 PRO3 TOP MOUNT Packaged Refrigeration System Technical Guide Model PTN and PTT For Indoor and Outdoor Applications...

Page 2: ...2 B H PRODUCT LINE DESIGN ORIENTATION APPLICATION LOCATION NOMINAL CAPACITY TEMPERATURE RANGE REFRIGERANT TYPE VOLTAGE MOTOR PRO3 Packaged Refrigeration System T Top Mount N T Indoor Outdoor BTUH x 1...

Page 3: ...rol Maximizes storage area in a cooler or freezer evaporator grill mounts flush on a standard 4 or a recessed 5 1 2 ceiling panel Ease of Use System is factory assembled evacuated charged run tested a...

Page 4: ...C motors you save money both directly from a decrease in motor watts and also from a reduction of heat gain into the refrigerated space Permanent Split Capacitor PSC motors can significantly lower you...

Page 5: ...30 17 2 825 No C 290 132 PT 128H2C 208 230 3 60 14 8 20 12 8 825 No C 285 129 PTN019L6A 115 1 60 13 0 20 13 0 340 Yes 5 20R A 101 46 PT 021L6A 115 1 60 14 5 20 12 3 350 Yes 5 20R B 213 97 PT 021L6B 20...

Page 6: ...sions Figure A Small Cabinet Design indoor only Figure B Medium Cabinet Design Figure C Large Cabinet Design 23 5 59 69 cm on outdoor models with weatherhood 21 5 54 61 cm on outdoor models with weath...

Page 7: ...p Control Cooler 115V 28916301 1 1 1 1 Freezer Sensor 28912101 2 2 2 2 2 2 2 2 Cooler Sensor Coil 28916202 1 1 1 1 1 1 1 1 1 1 1 Cooler Sensor Room 28916203 1 1 1 1 1 1 1 1 1 1 1 Heater Limit Thermost...

Page 8: ...1881 FAX 770 465 5990 www chandlerref com Since product improvement is a continuing effort we reserve the right to make changes in specifications without notice CH PTMTB 0108 version 000 For more info...