Chandler Systems UV-10DH Operation & Installation Instructions Download Page 10

1 0 |

P a g e

Step 6:  Once the system has been plumbed in, gently remove the 

quartz sleeve from its packaging being careful not to touch the length 

with your hands. The use of cotton gloves is recommended for this 

procedure as oils from the hands can leave residue on the sleeve and 

lamp which can ultimately block the UV light from getting to the wa-

ter.

Carefully slide the sleeve into the reactor until you can feel it hit the 

opposite end of the reactor. Align the sleeve so it centered along the 

length of the reactor, then gently push it in to lock it into the inter-

nal centering springs in the far side of the reactor. CAUTION: Pushing 

too hard when the sleeve is not aligned can damage the centering 

springs. Slide the o-ring onto the sleeve until it is butted up against 

the reactor. 

 

Figure 4.  Quartz 

Sleeve Installation

Step 7:  Hand tighten the provided gland nut over the quartz sleeve onto the threaded end of 

the reactor. It has a positive stop to prevent over-tightening. A firm force may be required to fully 

tighten the gland nut, but DO NOT USE TOOLS for this step. Insert the provided stainless steel 

compression spring into the quartz sleeve. The spring works with the lamp and lamp connector 

to create the proper lamp alignment. PLEASE NOTE: DO NOT install a UV lamp inside the quartz 

sleeve without the sleeve spring in place.

Step 8:  Install the UV sensor (UVDM systems only). Align the flat portion so it faces the gland 

nut end and matches up with the half metal lip on the sensor port (see Figure 5). Insert the sen-

sor so it is fully seated and hand tighten the sensor nut. 

Figure 5.  UV Sensor Installation

Figure 6. IEP Connection

Step 9:  The reactor is now ready for water flow. When all plumbing connections have been 

completed, slowly turn on the water supply and check for leaks. Make sure the by-pass valves are 

functioning properly and that the water is flowing through the reactor. The most common leak 

is from the o-ring not making a proper seal on the reactor. For new installations, review steps 6 

and 7. For older systems drain the reactor, remove the o-ring, dry it and reapply silicon grease. 

Reinstall the o-ring ensuring that it is properly sealed against the reactor and check again for 

leaks.

Step 10:  Mount the controller to the wall so it is above or beside the reactor to ensure that no 

moisture can deposit on any of the connections (see Figure 1). Always mount the controller verti-

cally. For monitored systems, insert the sensor connector into the IEP port located on the right 

side of the controller (Figure 6). For the sensor to be recognized by the controller, the controller 

power must be plugged in last. Do not plug the controller power cord in before the last step. 

Summary of Contents for UV-10DH

Page 1: ...V 5H UV 5DH UV 5DHM 5 gpm UV 3 UV3D UV3DM 3 gpm UV 10H UV 10DH UV 10DHM 10 gpm UV 6 UV6D UV6DM 6 gpm UV 15H UV 15DH UV 15DHM 15 gpm UV 11 UV11D UV11DM 11 gpm UV 25H UV 25DH UV 25DHM 25 gpm UV 15 UV15D...

Page 2: ...pply with a UV system gives you reassurance that your family will have access to safe drinking water throughout your entire home with no chance of microbiological contamination This is chemical free p...

Page 3: ...llers 14 Power up Sequence not UV systems 14 UV D UV DH Operational Screens 15 UV DM UV DHM Operational Screens 16 Lamp Countdown Sequence 16 Lamp Replacement UV UVH systems 17 Lamp Replacement UV DM...

Page 4: ...vice instructions if required 7 Do not use this system for any purpose other than what it was intended for Misuse of this system could potentially cause harm to the user or others 8 Your system is int...

Page 5: ...required will depend on parameters being treated Hardness 7 gpg 120 mg L if hardness level is 7 gpg or slightly below the quartz sleeve must be cleaned periodically in order to ensure effi cient UV p...

Page 6: ...an UV D UV DM SYSTEMS UVC 5 North American 300016 Complete Assembly 310026 Teflon Plug 310040 O Ring 390007 Brass Nut UVS 2 5 UVDM 2 3 6 11 15 series UVS 3 5 UVDM 20 series GLAND NUT O RING SLEEVE SPR...

Page 7: ...nits UV DH UV DHM SYS TEMS UVC 4H fits all units POWER CORD 300016 Complete Assembly 310026 Teflon Plug 310040 O Ring 390007 Brass Nut UVS 3 5H Standard series 260004 North American 320006 310038 UVLM...

Page 8: ...or tap near est the pressure system and measure the amount of water drawn off until the pump starts again Depending on the size of the container used it is acceptable to turn the faucet on and off to...

Page 9: ...s it will allow you to isolate the UV reactor This will allow for easier access in case maintenance is required See Figure 3 Step 3 Use the supplied fasteners to mount the UV reac tor to wood or drywa...

Page 10: ...SE NOTE DO NOT install a UV lamp inside the quartz sleeve without the sleeve spring in place Step 8 Install the UV sensor UVDM systems only Align the flat portion so it faces the gland nut end and mat...

Page 11: ...ou The key will plug into the lamp key port on the right side of the controller Figure 8 Step 13 Plug the lamp connector into the lamp Note the keying for proper alignment see Fig ure 7a 7b Insert the...

Page 12: ...eaning At a minimum the quartz sleeve should be cleaned on an annual basis The following steps outline a basic clean ing procedure Step 1 If a by pass assembly is installed shut the inlet valve off to...

Page 13: ...of the sensor port Step 6 Holding the sensor in your hand wipe the flat portion sensor face of the sensor with isopropyl alcohol using a clean lint free cloth Step 7 Replace sensor following step 9 fr...

Page 14: ...description of the system s performance in addition to pro viding any applicable fault messages and system diagnos tics The controllers used in both the UVD and UVDM are identical The difference is t...

Page 15: ...ts screens by pressing the button located on the front of the controller UV DM UV DHM Operational Screens On systems with the UV monitor the system will display the same screens as on the UVD except t...

Page 16: ...ible chirp Past the zero day threshold the LED or display screen changes to solid red with a continuous buzzer UV D DM UV DH DHM UV UVH At any point during this sequence the audible chirp or alarm can...

Page 17: ...pired it must be replaced with the same part number as indicated on the Maintenance Parts screen or on the label on the reactor With the system powered down re move and discard the lamp key from the c...

Page 18: ...on the reactor or on the Maintenance parts screen Low UV Intensity Remove and clean the quartz sleeve and sensor Check water quality meets requirements on page 5 and add filtration as required Replac...

Page 19: ...to the system Replace any module that is not detected when plugged directly into the controller COMING SOON Warning After any hard alarm the home or facility should be disinfected Follow the steps un...

Page 20: ...to allow fresh cooler water to enter the system The TRV works with out power and comes complete with 10 of drain line Order PN UV TRV 0 5 for 1 2 ports PN UV TRV 0 75 for 3 4 ports PN UV TRV 1 for 1 p...

Page 21: ...L1 4 20 mA MODULE Outputs a 4 20mA signal of the UV output to a remote device such as a data logger or computer Order PN UVMOD 420 The WiFi module and accompanying IoT application allows you to connec...

Page 22: ...9 62 51 Replacement Lamp UVLMP 2 UVLMP 3 UVLMP 6 UVLMP 11 UVLMP 15 UVLMP 20 Replacement Sleeve UVQTZ 2 UVQTZ 3 UVQTZ 6 UVQTZ 11 UVQTZ 15 UVQTZ 20 Reactor Dimensions 6 4 x 26 2 cm 2 5 x 10 3 6 4 x 36 4...

Page 23: ...0 2 m3 hr 0 5 m3 hr 0 6 m3 hr 1 1 m3 hr 1 8 m3 hr Port Size MNPT MNPT 1 MNPT 1 MNPT 1 MNPT Electrical 90 265V 50 60Hz 1 5A Max Lamp Power Watts 18 34 45 67 101 Power Watts 20 36 48 72 108 Replacement...

Page 24: ...CHANDLER s closest Distribution Facility or authorized service depot CHANDLER will not be liable for any costs of removal installation transportation or any other charges which may arise in connectio...

Page 25: ...PRODUCT AND IS GIVEN IN LIEU OF ANY OTHER WARRANTY TO THE EXTENT ALLOWED BY APPLICABLE LAW ANY AND ALL EXPRESS OR IMPLIED WARRANTIES NOT SET FORTH HEREIN ARE WAIVED AND DISCLAIMED INCLUDING ANY IMPLI...

Page 26: ...2 6 P a g e...

Page 27: ...2 7 P a g e...

Page 28: ...Chandler Systems 710 Orange Street Ashland OH 44805 Phone 888 363 9434 www chandlersystemsinc com PN 910181 Version Date 03 2020...

Reviews: