Voltage Indicator Tester Operating Instructions
Operating Instructions for PSC4032915 (ARVI)
1. Power-up the ARVI to be tested and verify that the automatic self-test has been successfully
completed per its operating instructions.
2. Insert the plug of the Voltage Indicator Tester into the jack located on the back of the meter
housing of the ARVI.
3. Connect the alligator clip onto the Shepherd Hook of the ARVI.
4. One of the Range LED's in the four (4) to twenty-five (25) kV range of the ARVI should begin
blinking and the audible alarm should emit a beeping sound.
5. Leave the Voltage Indicator Tester connected to the ARVI for 15-20 seconds. The ARVI should go
into the AUTO-HOLD mode. The Range LED should light continuously and the audible beeping
should convert to a continuous signal for 1-2 seconds followed by 5-6 very rapid beeps, followed
by 1-2 seconds of silence, and finally return to the normal audible mode until the ARVI is reset.
6. If the ARVI operates as described, it is operating properly. If not, replace the battery in the Voltage
Indicator Tester and repeat the above procedure. If the ARVI still does not operate as described,
either the ARVI or Voltage Indicator Tester may not be operating properly. Both units should be
returned to the manufacturer for repair.