 Voltage Indicator Tester Operating Instructions

Operating Instructions for PSC4032915 (ARVI)

1.    Power-up the ARVI to be tested and verify that the automatic self-test has been successfully 

completed per its operating instructions.

2.    Insert the plug of the Voltage Indicator Tester into the jack located on the back of the meter 

housing of the ARVI.

3.    Connect the alligator clip onto the Shepherd Hook of the ARVI.

4.    One of the Range LED's in the four (4) to twenty-five (25) kV range of the ARVI should begin 

blinking and the audible alarm should emit a beeping sound.

5.   Leave the Voltage Indicator Tester connected to the ARVI for 15-20 seconds. The ARVI should go 

into the AUTO-HOLD mode. The Range LED should light continuously and the audible beeping 
should convert to a continuous signal for 1-2 seconds followed by 5-6 very rapid beeps, followed 
by 1-2 seconds of silence, and finally return to the normal audible mode until the ARVI is reset.

6.   If the ARVI operates as described, it is operating properly. If not, replace the battery in the Voltage 

Indicator Tester and repeat the above procedure. If the ARVI still does not operate as described, 
either the ARVI or Voltage Indicator Tester may not be operating properly. Both units should be 
returned to the manufacturer for repair.

Summary of Contents for PSC4033582

Page 1: ...ll Incorporated hpsliterature hubbell com hubbellpowersystems com For use with NOTICE Before operating a Chance Voltage Indicator Tester thoroughly read understand and follow these instructions Keep t...

Page 2: ...rocedures techniques etc that if not followed carefully could RESULT IN DEATH A WARNING refers to operating procedures techniques etc that if not followed carefully could RESULT IN INJURIES OR DEATH A...

Page 3: ...cator Tester model PSC4033582 is a portable device for safely testing specific models of voltage indicators and the MAIN unit of the Wireless Phasing Set Only use this device on the indicators listed...

Page 4: ...audible alarm should emit a beeping sound 5 Leave the Voltage Indicator Tester connected to the ARVI for 15 20 seconds The ARVI should go into the AUTO HOLD mode The Range LED should light continuousl...

Page 5: ...r 15 20 seconds The WPS should go into the AUTO HOLD mode The Range LED should light continuously and the audible beeping should convert to a continuous signal for 1 2 seconds followed by 5 6 very rap...

Page 6: ...3 Connect the alligator clip onto the Shepherd Hook of the MRVI 4 The Sense LED will change from flashing to continuously illuminated the pointer will rotate and indicate a voltage level between four...

Page 7: ...t which is located at the opposite end of the round universal coupling holder Make sure that nothing but the insulated boot is touching the metal alligator clip during the test 4 One or more of the LE...

Page 8: ...ections to the circuit board while not short circuiting the battery Gently pull the battery from the housing To install the replacement battery insert the unconnected battery into the housing While ob...

Page 9: ...Weight with battery 388 g 13 7 oz Dimensions w o leads 1 5 X 12 L Battery requirements One 1 Alkaline 9 Volt battery Operating voltage range s Not to be used near energized voltage sources Operating t...

Page 10: ...____________________________________________________________ ___________________________________________________________________________________ _______________________________________________________...

Page 11: ...____________________________________________________________ ___________________________________________________________________________________ _______________________________________________________...

Page 12: ...hubbellpowersystems com PSP4033598 TD_09_104_E Rev B Hubbell has a policy of continuous product improvement Please visit hubbellpowersystems com to confirm current design specifications 2017 Hubbell...

Reviews: