background image

 11

75 100

PARTS 115/1/60 208-230/1/60 220-240/1/50 115/1/60 208-230/1/60 220-240/1/50
DESCRIPTION 100/1/50 100/1/50

Condensing Unit (Air-cooled) C413012212 C413012213 C413012214 C413012312 C413012313 C413012314

Compressor (Only) C413010844 C413010845 C413010846 C413010847 C413010848 C413010849

Overload C59255787 C59255788 C59255789 C592557810 C592557811 C592557812

Start Relay C59456837 C59456838 C59456839 C594568310 C594568311 C594568312

Start Capacitor N/A C591010326 C591010327 C591010328 C591010329 C591010329

Fan Motor C610523831 C610523832 C610523832 C610523833 C610523834 C610523834

Fan Blade C414022719 C414022725 C414022725 C414022720 C414022720 C414022720

Hot Gas By-Pass Valve C98021 C98021 C98021 C98021 C98021 C98021

Condenser (Air Cooled) C413011120 C413011120 C413011120 C413011121 C413011121 C413011121

Dryer C413016514 C413016514 C413016514 C413016514 C413016514 C413016514

Fan Pressure Switch N/A N/A N/A N/A N/A N/A

Contactor N/A N/A N/A N/A N/A N/A

By-Pass Valve Strainer C41307018 C41307018 C41307018 C41307018 C41307018 C41307018

On-Off Switch C611070613 C611070613 C611070613 C611070613 C611070613 C611070613

High Temperature Sensor C61503332 C61503332 C61503332 C61503332 C61503332 C61503332

Digital PC Board (IC 1-0)

w/ high temp-sensor C59455767 C59455767 C59455767 C59455767 C59455767 C59455767

25

 

                                                     35 50

PARTS 115/1/60 208-230/1/60 220-240/1/50 115/1/60 208-230/1/60 220-240/1/50 115/1/60 208-230/1/60 220-240/1/50
DESCRIPTION 100/1/50

100/1/50 100/1/50

Condensing Unit (Air-cooled) C41301205 C41301208 C41301209 C413012111 C41301219 C41301219 C413012210 C413012211 C413012215

Compressor (Only) C413010834 C413010861 C413010835 C413010838 C413010839 C413010840 C413010841 C413010842 C413010843

Overload C59255702 C592557824 C59255703 C59255781 C59255782 C59255783 C59255784 C59255785 C59255785

Start Relay C59456555 C594568324 C59456556 C59456831 C59456832 C59456833 C59456834 C59456835 C59456835

Start Capacitor N/A N/A N/A N/A N/A N/A N/A C5910-103-23 N/A

Fan Motor C61052391 C61052374 C61052374 C610523827 C610523828 C610523828 C610523829 C610523830 C610523830

Fan Blade C41402282 C41402282 C41402282 C414022717 C414022717 C414022717 C414022718 C414022718 C414022718

Hot Gas By-Pass Valve C98021 C98021 C98021 C98021 C98021 C98021 C98021 C98021 G98021

Condenser (Air Cooled) C413011026 C413011026 C413011026 C413011118 C413011118 C413011118 C413011119 C413011119 C413011119

Dryer C413016514 C413016514 C413016514 C413016514 C413016514 C413016514 C413016514 C413016514 C413016514

By-Pass Valve Strainer C41307018 C41307018 C41307018 C41307018 C41307018 C41307018 C41307018 C41307018 C41307018

On-Off Switch C611070613 C611070613 C611070613 C611070613 C611070613 C611070613 C611070613 C611070613 C611070613

High Temperature Sensor C61503332 C61503332 C61503332 C61503332 C61503332 C61503332 C61503332 C61503332 C61503332

Digital PC Board (IC 1-0)

w/ high temp-sensor C59455767 C59455767 C59455767 C59455767 C59455767 C59455767 C59455767 C59455767 C59455767

PARTS LIST

Flow (scfm) 25 35 50 75 100

Standard CRNMK2 CRNMK2 CRNMK3 CRNMK4 CRNMK4
With Optional Cold Coaleser CRNMK12 CRNMK12 CRNMK13 CRNMK14 CRNMK14

Maintenance Kits

Summary of Contents for CRN100

Page 1: ...645 1st Ed 7610 478 39 040103 INTERNAL USE ONLY CONTENTS GENERAL SAFETY INFORMATION 2 RECEIVING MOVING UNPACKING 2 1 0 INSTALLATION 3 2 0 OPERATION 4 3 0 MAINTENANCE 6 SIZING 6 ENGINEERING DATA 7 ELECTRICAL SCHEMATICS 8 DIMENSIONS WEIGHTS 9 TROUBLESHOOTING 10 PARTS LIST 11 WARRANTY 12 Models CRN25 CRN35 CRN50 CRN75 CRN100 ...

Page 2: ...s evidence of loss or damage at time of delivery to you insist that a notation of this loss or damage be made on the delivery receipt by the carrier s agent B UNPACKING Check for Concealed Loss or Damage When a ship ment has been delivered to you in apparent good order but concealed damage is found upon unpack ing notify the carrier immediately and insist on his agent inspecting the shipment Conce...

Page 3: ...r installation Standard units are designed for indoor installation Contact manufacturer if installing outdoors 1 2 Mounting Mount the dryer on a level solid surface Holes are provided in the dryer base to permanently mount the dryer to the floor 1 3 Piping connections A Air Inlet Connect compressed air line from air source to air inlet See callout drawing on page 3 for air in outlet connection loc...

Page 4: ... and void the warranty 1 5 Moisture separator A Separator and Oil Removal Filter where applicable has an internal drain which automatically discharges collected condensate It may be desirable to pipe the condensate from the Automatic Drain outlet to a suitable drain NOTE Discharge is at system pressure Drain line should be anchored NOTE Condensate may contain oil Comply with applicable laws concer...

Page 5: ...ed in Table 1 2 Where the dryer is consistently operating at less than maximum capacity it may be possible to increase the LED set point to minimize air loss Discretionary adjustments to the dryer should only be made on a hot humid day when the maximum expected air load is flowing through the dryer Failure to do so may prevent the condensate from draining completely when operating under peak load ...

Page 6: ...d drain mechanism annually To facilitate service maintenance kits are available Please refer to page 11 3 0 Maintenance Sizing Determining dryer capacity at actual operating conditions To determine the maximum inlet flow capacity of a dryer at various operating conditions multiply the rated capacity from Table 1 by the multipliers shown in Table 2 Example How many scfm can an air cooled 100 scfm m...

Page 7: ... 275 229 220 183 350 292 Electrical Nominal Voltages 115 1 60 Max Min Voltage 127 104 127 104 127 104 127 104 127 104 Rated Load Amps 3 4 3 9 5 9 7 4 10 3 Locked Rotor Amps 18 0 22 0 28 0 35 0 48 0 Minimum Circuit Ampacity 4 0 4 7 7 3 9 1 12 4 Branch Circuit Fuse Size amps 15 15 15 15 20 Watts 35 F Evaporator 100 F Ambient 280 290 465 600 815 Overload Thermal Current Auto reset Nominal Voltages 20...

Page 8: ...rload TB Terminal Block CAP Start Capacitor SR Start Relay DRN1 Drain Solenoid STD IC2 MTR Compressor DRN2 Drain Solenoid IC2 Oil Coalescing Option FM Fan Motor TC1 Temperature Sensor Optional Notes 1 IC1 Includes IC1 Instrument Panel and Pneumatic Pilot operated Drains 2 IC2 Includes IC2 Instrument Panel and Timed Solenoid Drains 3 DRN2 Optional Cold Coalescing Drain ...

Page 9: ... 18 3 16 18 3 16 18 3 16 20 11 16 20 11 16 H 21 3 16 21 3 16 21 3 16 24 3 16 24 3 16 I 18 1 2 18 1 2 18 1 2 24 24 J 16 1 2 16 1 2 16 1 2 21 13 16 21 13 16 Inlet Outlet Connections 1 2 MPT 1 2 MPT 1 2 MPT 3 4 MPT 3 4 MPT Weights lbs 142 146 152 209 228 Weights lbs w Oil Removal Filter 147 151 157 216 235 A F B I J C E D H G TOP VIEW FRONT VIEW LEFT SIDE VIEW TOP VIEW FRONT VIEW LEFT SIDE VIEW 25 th...

Page 10: ...igh air outlet temperature 2 Refrigeration system not func tioning properly resulting in high air outlet temperature 3 Dryer is running with no load a Power failure b Line disconnect switch open c Blown fuses open breaker d Faulty wiring loose terminals a High or low ambient conditions b Air cooled models Dirty clogged condenser fins obstructed air flow across condenser or non functioning fan moto...

Page 11: ...00 1 50 Condensing Unit Air cooled C41301205 C41301208 C41301209 C413012111 C41301219 C41301219 C413012210 C413012211 C413012215 Compressor Only C413010834 C413010861 C413010835 C413010838 C413010839 C413010840 C413010841 C413010842 C413010843 Overload C59255702 C592557824 C59255703 C59255781 C59255782 C59255783 C59255784 C59255785 C59255785 Start Relay C59456555 C594568324 C59456556 C59456831 C59...

Page 12: ...GE BY REASON OF STRICT LIABILITY IN TORT OR ITS NEGLIGENCE IN WHATEVER MANNER INCLUDING DESIGN MANUFACTURE OR INSPECTION OF THE EQUIPMENT OR ITS FAILURE TO DISCOVER REPORT REPAIR OR MODIFY LATENT DEFECTS INHERENT THEREIN THE MANUFACTURER HIS REPRESENTATIVE OR DISTRIBUTOR SHALL NOT BE LIABLE FOR LOSS OF USE OF THE PRODUCT OR OTHER INCIDENTAL OR CONSEQUENTIAL COSTS EXPENSES OR DAMAGES INCURRED BY TH...