201160 - 12,000W ELEcTRic START GENERATOR

MAiNTENANcE

25

Operation at High Altitude

The density of air at high altitudes is lower than at sea level. 
Engine power is reduced as the air mass and air-fuel ratio 
decrease. Engine power and generator output will be reduced 
approximately 3½% for every 1000 ft. of elevation above sea level. 
At high altitudes increased exhaust emissions can also result due 
to the increased enrichment of the air fuel ratio. Other high altitude 
issues can include hard starting, increased fuel consumption and 
spark plug fouling.

To alleviate high altitude issues other than the natural power 
loss, CPE can provide a high altitude carburetor main jet. The 
alternative main jet and installation instructions can be obtained 
by contacting our Technical Support Team. Installation instructions 
are also available in the Technical Bulletin area of the CPE website.

 

WARNiNG

Operation using the alternative main jet at elevations lower 
than the recommended minimum altitude can damage the 
engine. For operation at lower elevations, the originally 
supplied standard main jet must be used. Operating the 
engine with the wrong engine configuration at a given altitude 
may increase its emissions and decrease fuel efficiency and 
performance.

MAiNTENANcE

Make certain that the generator is kept clean and stored properly. 
Only operate the unit on a flat, level surface in a clean, dry 
operating environment. DO NOT expose the unit to extreme 
conditions, excessive dust, dirt, moisture or corrosive vapors.

 

WARNiNG

Never operate a damaged or defective generator.

 

WARNiNG

Improper maintenance will void your warranty.

 

NOTicE

For Emission control devices and systems, read and 
understand your responsibilities for service as stated in the 
Emission Control Warranty Statement of this manual.

The owner/operator is responsible for all periodic maintenance.

Complete all scheduled maintenance in a timely manner.

Correct any issue before operating the generator. 

For service or parts assistance, contact our 
Technical Support Team at 1-877-338-0999.

cleaning the Generator

 

cAUTiON

DO NOT spray generator directly with water.

Water can enter the generator through the cooling slots and 
damage the generator windings. It can also contaminate the 
fuel system.

1.  Use a damp cloth to clean exterior surfaces of the generator.

2.  Use a soft bristle brush to remove dirt and oil.

3.  Use an air compressor (25 PSI) to clear dirt and debris from 

the generator. 

4.  Inspect all air vents and cooling slots to ensure that they are 

clean and unobstructed.

To prevent accidental starting, remove and ground the spark plug 
wire before performing any service.

changing Engine Oil and filter

Change oil when the engine is warm. Refer to the oil specification 
to select the proper grade for your operating environment.

1.  Remove the oil drain bolt.

2.  Allow the oil to drain completely into an appropriate container.

3.  Replace the oil drain bolt.

4.  Remove oil filter by turning counterclockwise.

Summary of Contents for 201160

Page 1: ...should remain with the product Specifications descriptions and illustrations in this manual are as accurate as known at the time of publication but are subject to change without notice This product m...

Page 2: ...monoxide risks you ll be better prepared to protect your family from this colorless oderless threat CARBON MONOXIDE SAFETY THE BIG PICTURE KNOW THE SYMPTOMS Headache Nausea Shortness of breath Dizzin...

Page 3: ...ection 21 Starting the Engine 21 Battery 22 Connecting Electrical Loads 22 Do Not Overload Generator 23 GFCI 23 Stopping the Engine 24 Moving the Generator 24 Operation at High Altitude 25 Maintenance...

Page 4: ...effort has been made to ensure the accuracy and completeness of the information in this manual at the time of publication and we reserve the right to change alter and or improve the product and this...

Page 5: ...guards in place Rotating parts can entangle hands feet hair clothing and or accessories Traumatic amputation or severe laceration can result Keep hands and feet away from rotating parts Tie up long ha...

Page 6: ...sistance is felt and then pull rapidly to avoid kickback DO NOT start or stop the engine with electrical devices plugged in and turned on WARNING Although the generator contains a spark arrester maint...

Page 7: ...ine outdoors in a well ventilated area DO NOT pump gasoline directly into the generator at the gas station Always use an approved container to transfer the fuel to the generator DO NOT overfill the ga...

Page 8: ...ctanos como m nimo M ximo de etanol de 10 ESSENCE SANS PLOMB SEULEMENT Indice d octane minimal de 87 Maximum 10 d thanol K 109 Colors LPN 1110 L OP Rev B Size 46 x 46 mm Artwork Notes 3mm corner radiu...

Page 9: ...before operation Electric Shock Failure to use in dry conditions and to observe safe practices can result in electric shock Improper connections to a building can allow current to backfeed into utili...

Page 10: ...Off Run Push choke knob to RUN position Choke Pull choke knob to CHOKE position Circuit Breaker On Circuit Breaker Off Circuit Breaker Reset Flip Circuit Breaker Reset Push Locking Receptacle SYMBOL...

Page 11: ...be disclosed to or used by or for outside parties without the explicit consent of Champion Power Equipment K CYAN 376 186 152 CG1 Starting the Engine DANGER Move generator outside and far away from w...

Page 12: ...Cap Used to fill oil 3 Spark Plug Arrester and Muffler 4 Support Leg 5 Dipstick Used to check oil level 6 Never Flat Wheels 12 in 30 5 cm 7 Ground Terminal Consult an electrician for local grounding r...

Page 13: ...120 240V AC 50A NEMA 14 50R May be used to supply electrical power for operation of 120 240 Volt AC 50 Amp single phase 60 Hz electrical loads B Y 120 240V AC 30A Locking NEMA L14 30R May be used to s...

Page 14: ...ust when the generator is running If CO Shield detects elevated levels of CO gas it automatically shuts off the engine See CO Shield section for more information MODE DESCRIPTION 1 Voltage V Output vo...

Page 15: ...s subject to the following two conditions 1 This device may not cause interference and 2 This device must accept any interference including interference that may cause undesired operation of the devic...

Page 16: ...n roll through the wheel from the outside 4 Slide the wheel pin roll through the mount point on the frame 5 Secure with the R Pin 6 Install wheel hub cap onto wheel 7 Repeat steps 2 6 to attach the se...

Page 17: ...000 ml Volume after oil and oil filter change 44 fl oz 1300 ml 5 Pull out dipstick and check engine oil level Add as needed DO NOT OVERFILL 6 Replace dipstick 7 Close engine access cover NOTICE Check...

Page 18: ...e can expand after filling A minimum of in 6 4 mm of space left in the tank is required for gasoline expansion although more than in 6 4 mm is recommended Gasoline can be forced out of the tank as a r...

Page 19: ...cifications section for specified type of grounding OPERATION CO Shield Carbon Monoxide CO Detection and Auto shutoff System CO Shield technology monitors the accumulation of carbon monoxide CO a pois...

Page 20: ...minute after it was manually shut off This does not occur if generator shut off from a high CO event If CO Shield system experiences a fault and no longer provides protection the generator is shutoff...

Page 21: ...properly cool before transport or for storage purposes Failure to follow proper safety precautions may result in personal injury damage to the generator and void the manufacturer s warranty WARNING Du...

Page 22: ...nnect 3 phase loads to the generator DO NOT overload the generator Use only a high quality insulated compatible 3 wire or 4 wire grounded cord set rated equal to or greater volts and amps than the rec...

Page 23: ...nt of a ground fault a GFCI trips automatically to stop the flow of electricity and prevent serious injury The green indicator light A on the receptacle will also turn off Press the RESET B button loc...

Page 24: ...Generator CAUTION NEVER lift or carry the generator using the folding handle NEVER tilt sideways while moving the generator ALWAYS place the generator on its wheels in the upright position ALWAYS turn...

Page 25: ...n a clean dry operating environment DO NOT expose the unit to extreme conditions excessive dust dirt moisture or corrosive vapors WARNING Never operate a damaged or defective generator WARNING Imprope...

Page 26: ...plug types in Specifications when replacing the plug 6 Firmly re install the plug 7 Attach the spark plug cable to the spark plug 8 Repeat Steps 1 7 for spark plug on other side of engine Cleaning th...

Page 27: ...ct our Technical Support Team at 1 877 338 0999 for all other service and or adjustment needs Generator Battery Your generator is equipped with an automatic battery charging circuit that charges the b...

Page 28: ...er Check adjust valve clearance EVERY 3 YEARS Replace fuel line To be performed by knowledgeable experienced owners or CPE certified service centers STORAGE WARNING To avoid accidental or unintended i...

Page 29: ...OTICE If the generator has been improperly stored for a period longer than 30 days with ethanol blended gasoline in the gasoline tank all fuel must be drained If the gasoline tank was properly emptied...

Page 30: ...gine Oil Type 80 100 120 28 9 F C 17 8 6 7 4 4 15 6 26 7 37 8 48 9 10W 30 5W 30 Full Synthetic 10W 40 5W 30 NOTICE Temperature will affect engine oil and engine performance Change the type of engine o...

Page 31: ...when CO Shield shutoffs occur due to accumulating carbon monoxide CO and if the red LED light blinks on the panel Move generator to an open outdoor area Point exhaust away from people and buildings Mo...

Page 32: ...CO Shield continues to sense the fault and shuts off contact technical support Both CO Shield LEDs not blinking 10 times upon start up Starting the generator within 1 minute after being manually shuto...

Page 33: ...beyond the product s limits modified installed improperly or connected incorrectly to any electrical component Normal maintenance is not covered by this warranty and is not required to be performed a...

Page 34: ...gnosis parts and labor MANUFACTURER S EMISSION CONTROL SYSTEM WARRANTY COVERAGE This emission control system is warranted for two years subject to provisions set forth below If during the warranty per...

Page 35: ...placement point for that part If the part fails prior to the first scheduled replacement the part shall be repaired or replaced by CPE according to Subsection d below Any such emissions related part r...

Page 36: ...ister Mounting Brackets Carburetor Purge Port Connector TO OBTAIN WARRANTY SERVICE You must take your CPE engine or the product on which it is installed along with your warranty registration card or o...

Reviews: