OPERATION

Connecting Electrical Loads

1.  Let the engine stabilize and warm up for a few 

minutes after starting

2.  Plug in and turn on the desired 120/240 Volt AC 

single phase, 60 Hz electrical loads.

 

– DO NOT connect 3-phase loads to the generator.

 

– DO NOT connect 50 Hz loads to the generator.

 

– DO NOT overload the generator.

Connecting a generator to your electric utility company’s 
power lines or to another power source may be against 
the law. In addition this action, if done incorrectly, could 
damage your generator and appliances and could cause 
serious injury or even death to you or a utility worker who 
may be working on nearby power lines. If you plan to run a 
portable electric generator during an outage, please notify 
your electric utility company immediately and remember 
to plug your appliances directly into the generator. Do not 
plug the generator into any electric outlet in your home. 
Doing so could create a connection to the utility company 
power lines. You are responsible for ensuring that your 
generator’s electricity does not feed back into the electric 
utility power lines.
If the generator will be connected to a building electrical 
system, consult your local utility company or a qualified 
electrician. Connections must isolate generator power from 
utility power and must comply with all applicable laws and 
codes.

NOTE

Stopping the Engine

1.  Turn off and unplug all electrical loads. Never start 

or stop the generator with electrical devices plugged 
in or turned on.

2.  Let the generator run at no-load for several minutes 

to stabilize internal temperatures of the engine and 
generator.

3.  Turn the Fuel Valve to the “OFF” position.
4.  Let the engine run until fuel starvation has stopped 

the engine. This usually takes a few minutes.

5.  Press the engine switch to the “OFF” position.
6.  Turn Battery Switch to the “Off” Position.
Important: Always ensure that the Fuel Valve and the 
Engine Switch are in the “OFF” position when the 
engine is not in use.

When turning off the generator after LPG operation, turn 
the fuel knob on LPG cylinder off too. Make sure it is in 
the fully closed position.

NOTE

If the engine will not be used for a period of two (2) weeks 
or longer, please see the Storage section for proper engine 
and fuel storage.

NOTE

Do Not Overload Generator

Capacity

Follow these simple steps to calculate the running and 
starting watts necessary for your purposes. 
1.  Select the electrical devices you plan on running at 

the same time.

2.  Total the running watts of these items. This is 

the amount of power you need to keep your items 
running.

3.  Identify the highest starting wattage of all devices 

identified in step 1. Add this number to the number 
calculated in step 2. Surge wattage is the extra 
burst of power needed to start some electric driven 
equipment. Following the steps listed under “Power 
Management” will guarantee that only one device will 
be starting at a time.

If the engine starts but does not run make certain that 
the generator is on a flat, level surface. The engine 
is equipped with a low oil sensor that will prevent the 
engine from running when the oil level falls below a 
critical threshold.

NOTE

When the battery switch is in the “ON” position, the 
switch will light up if the battery is sending out a 
charge. If the switch does not light up while in the “ON” 
position, check that the battery connection is still good.

NOTE

The supplied 12V 15AH battery does re-charge while the 
engine is running, but it is also recommended that the 
battery be fully charged at least once per month.

NOTE

Starting the Engine Cont’d.

If the ignition switch is held down in the “Start” position 
longer than 5 seconds it could damage the starter.

CAUTION

Summary of Contents for 71531

Page 1: ...338 0999 www championpowerequipment com 8400 Starting Watts 6750 Rated Watts LPG 9375 Starting Watts 7500 Rated Watts Gas DUAL FUEL GENERATOR SAVE THESE INSTRUCTIONS Important Safety Instructions are...

Page 2: ...r Champion Power Equipment product is designed and rated for continuous operation at ambient temperatures up to 40 C 104 F When your product is needed your product may be operated at temperatures rang...

Page 3: ...ad Generator 15 Capacity 15 Power Management 16 Operation at High Altitude 16 Maintenance and Storage 17 Engine Maintenance 17 Oil 17 Spark Plugs 17 Air Filter 17 Spark Arrester 18 Cleaning 18 Adjustm...

Page 4: ...this information available when ordering parts and when making technical or warranty inquiries Accessories Champion Power Equipment manufactures and sells accessories designed to help you get the most...

Page 5: ...hazardous situation which if not avoided may result in minor or moderate injury CAUTION CAUTION used without the safety alert symbol indicates a potentially hazardous situation which if not avoided m...

Page 6: ...amaged or frayed DO NOT operate generator in wet weather DO NOT allow children or unqualified persons to operate or service the generator Use a ground fault circuit interrupter GFCI in damp areas and...

Page 7: ...generator s running capacity can damage the generator and or electrical devices connected to it DO NOT overload the generator Start the generator and allow the engine to stabilize before connecting el...

Page 8: ...FLAMMABLE AND EXPLOSIVE Fire or explosion can cause severe burns or death Unintentional startup can result in entanglement traumatic amputation or laceration DANGER When adding or removing Gas Turn th...

Page 9: ...l Tank 6 1 gallon 23 L capacity fuel tank 2 Choke Used to start the engine 3 Air Cleaner Protects the engine by filtering dust and debris from the intake air 4 Recoil Starter Used to manually start th...

Page 10: ...al Consult an electrician for local grounding regulations 7 120 Volt AC 30 Amp Twist Lock Receptacle NEMA L5 30R May be used to supply electrical power for the operation of 120 Volt AC 30 Amp single p...

Page 11: ...nge Bolt M10x120 for Wheel 2 Bushing 2 Flat Washer 10 2 Lock Nut M10 2 Support Leg w Vibration Mounts 1 Flange Bolt M8x16 for Support Leg 2 Flange Lock Nut M8 2 Other Oil 1 2 qt 1 1 L LPG Hose With Re...

Page 12: ...lowing tools to install the wheels 17 mm wrench OR adjustable wrench not included Socket wrench with a 16 mm socket not included Pliers not included 1 Before adding fuel and oil tip the generator on i...

Page 13: ...evel in the crankcase falls below the threshold level CAUTION Add Engine Oil DO NOT attempt to crank or start the engine before it has been properly filled with the recommended type and amount of oil...

Page 14: ...an ethanol content of less than 10 by volume 2 DO NOT mix oil with fuel 3 Clean the area around the fuel cap 4 Remove the fuel cap 5 Slowly add fuel to the tank DO NOT OVERFILL Fuel can expand after...

Page 15: ...hat have not been plugged or kept closed must also be purged The purging process should be done by a LPG supplier Cylinders from an exchange supplier should have been purged and filled properly alread...

Page 16: ...when positioning generator Failure to follow proper safety precautions may void manufacturer s warranty Do not operate or store the generator in rain snow or wet weather Using a generator or electrica...

Page 17: ...attery switch to the ON position 7 ELECTRIC START Press and hold the ignition switch to the START position Release as the engine begins to roll over If the engine fails to start within five seconds re...

Page 18: ...ne This usually takes a few minutes 5 Press the engine switch to the OFF position 6 Turn Battery Switch to the Off Position Important Always ensure that the Fuel Valve and the Engine Switch are in the...

Page 19: ...end of the generator near the handle where engine fan air flows out from the generator This air is slightly heated by flowing over the engine The container should not be placed in the path of the muf...

Page 20: ...lug 6 Carefully thread the plug into the engine 7 Use the spark plug tool to firmly install the plug 8 Attach the spark plug wire to the plug For service or parts assistance contact our help line at 1...

Page 21: ...tenance and Storage Federal and local laws and administrative requirements indicate when and where spark arresters are required When ordered spark arresters are required for operation of this generato...

Page 22: ...ulling the engine recoil cord If the battery voltage is extremely low the charging circuit may not be able to re charge the battery In this case the battery must be connected to a standard automotive...

Page 23: ...F6RTC Replacement spark plug NGK BPR6ES or equivalent Make certain the spark plug gap is 0 7 0 8 mm or 0 028 0 031 in An Important Message About Temperature Your Champion Power Equipment product is de...

Page 24: ...56 57 66 23 82 83 84 85 86 87 88 44 65 1 2 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 5 5 16 59 62 63 64 60 61 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 76 89 90 91 92 93 95 97 98 99 94 100 10...

Page 25: ...00800 09 2 Decorative Plate 1 68 152 070031 00 Jacket LPG Hose 3 69 6 5 233 420 2 Frame 1 70 1 6177 1 10 Flange Lock Nut M10 4 Part Number Description Qty 71 152 201200 03 Motor Mount I 2 72 1 6182 10...

Page 26: ...108 85 10 1 2 3 4 5 6 7 8 9 11 12 13 14 15 16 17 18 19 20 16 24 25 26 27 28 29 30 31 33 34 35 12 36 30 37 38 23 39 41 42 43 44 46 47 48 49 50 51 52 53 12 54 55 57 58 59 60 61 62 65 66 68 69 70 71 72 7...

Page 27: ...1 56 2 01 010 Stud Bolt M8 35 2 57 2 15 002 F6RTC Spark Plug F6RTC 1 Part Number Description Qty 58 2 08 014 Flange Bolt M10 80 4 59 46 020002 00 Gasket Cylinder Head Cover 1 60 47 021000 00 Cylinder...

Page 28: ...DCW multi purpose meter FUEL CUT SOLENOIL B G B G W G W G G OFF G Y G Y G Y 3 4 5 2 1 6 G Y Charger Br G Y SWITCH lb l la G Y EARTH TERMINAL G Y G Y L14 30R L5 30R 5 20R B W W R R R G Y B B W G Y W W...

Page 29: ...position Generator shuts down during operation Out of fuel Fill the gasoline tank or fill LPG cylinder Low oil level Fill crankcase to the proper level Place generator on a flat level surface Generato...

Page 30: ...nd or labor if this generator is deemed to have been misused neglected involved in an accident abused loaded beyond the generator s limits modified installed improperly or connected incorrectly to any...

Page 31: ...parts and labor For engines less than or equal to 80cc only the fuel tank and fuel line is subject to the evaporative emission control warranty requirements of this section MANUFACTURER S EMISSION CON...

Page 32: ...be warranted for the period of time prior to the first scheduled replacement point for that part If the part fails prior to the first scheduled replacement the part shall be repaired or replaced by CP...

Page 33: ...ets Carburetor Purge Port Connector TO OBTAIN WARRANTY SERVICE You must take your CPE engine or the product on which it is installed along with your warranty registration card or other proof of origin...

Reviews: