NOTICE

All DIP switches are set to ON by default from the factory.

2.  Verify the DIP switches are set for your installation. Adjust as 

needed.

DIP Switch Settings

Switch 1. Load Module 1 Lockout

 

On

= Load Module 1 is being managed. Load Module 1 is the 

lowest priority of the 4 load modules. This load will be turned 
off first as the ATS manages the home’s load.

 

Off

= Load module 1 will stay off during HSB power.

Switch 2. Load Module 2 Lockout

 

On

= Load Module 2 is being managed.

 

Off

= Load module 2 will stay off during HSB power.

Switch 3. Load Module 3 Lockout

 

On

= Load Module 3 is being managed.

 

Off

= Load module 3 will stay off during HSB power.

Switch 4. Load Module 4 Lockout

 

On

= Load Module 4 is being managed. Load Module 4 is the 

highest priority of the 4 load modules. This load will be turned 
off last as the ATS manages the homes load.

 

Off

= Load module 4 will stay off during HSB power.

Switch 5. Frequency Protection.

 

On

= All managed loads will be turned off when if the HSB 

frequency drops below 58 Hz.

 

Off

= All managed loads will be turned off when if the HSB 

frequency drops below 57 Hz.

Switch 6. Spare. Not used at this time. Switch position does not 
matter.

Switch 7. Power Management

 

On

= ATS is managing the homes load.

 

Off

= ATS has disabled power management.

Switch 8. PLC vs. Two Wire Communication

 

On

= ATS will control HSB startup and shutdown through PLC.  

This is the preferred method of communication however it 
requires the HSB to be an aXis controlled HSB.

 

Off

= ATS will control the start of the HSB using the AC2 Relay.   

In this setting the AC2 can not be used to manage a load. Pins 
1 and 3 of the AC2 connector will be used for the HSB startup 
signal.

Switch 9. Test HSB with Load

 

On

= Test occurs with load.

 

Off

= Test occurs without load.

Switch 10. Master/Slave

 

On

= This ATS is the primary or only ATS. <- most common.

 

Off

= This ATS is being controlled by a different aXis 

controller™ ATS.  Used for installations that require two ATS 
boxes (i.e. 400A installations).

Switch 11. Exercise Test

 

On

= Exercise tests will occur per the schedule that is 

programmed into the aXis controller.

 

Off

= Exercise tests are disabled.

Switch 12. Time delay for HSB to accept load.

 

On

= 45 seconds.

 

Off

= 7 seconds.

3.  Have authorized utility personnel reconnect the utility meter 

to the meter socket.

4.  Verify voltage at utility circuit breaker.

5.  Turn on utility circuit breaker.

6.  ATS aXis Controller

TM

 module will begin boot up process.  

Allow ATS aXis Controller

TM

 module to fully boot up 

(approximately 6 minutes).

7.  Home should be fully powered at this point.

WIFI Setup Method

1.  Use a WiFi enabled device (laptop, smart phone, tablet, etc.) 

in near proximity to the ATS.

2.  Search and Connect to network name (SSID) “Champion 

HSB”. The password for the network is located on a decal on 
the deadfront of the ATS.

3.  After connecting, open your device’s web browser.  Many 

times the Champion aXis Controller

TM

 Home Standby 

Generator Settings Page will autoload however if that is not 
the case, refresh the browser or change the web address to 
anything.com. As your device attempts to reach the internet 
the WiFi module in the ATS will redirect your browser to the 
Champion aXis Controller

TM

 Home Standby Generator Settings 

Page.

Summary of Contents for 102006

Page 1: ...his manual contains important safety precautions which should be read and understood before operating the product Failure to do so could result in serious injury This manual should remain with the pro...

Page 2: ...atic Transfer Switch with aXis ControllerTM Module 6 Panel Board Safety Information 7 Unpacking 8 Location and Mounting 8 Electrical Grommet s 8 Installation Wiring for ATS Utility Socket 9 Wiring the...

Page 3: ...e Please always exercise common sense and always err on the side of caution when operating the product to ensure no accident property damage or injury occurs We want you to continue to use and be sati...

Page 4: ...operating technique the manufacturer does not specifically recommend follow all codes to ensure safety for personnel Many accidents are caused by failing to follow simple and fundamental rules codes...

Page 5: ...ntial and privileged and shall not be disclosed to or used by or for outside parties without the explicit consent of Champion Power Equipment 152 Alternate Power Source 2 This switch will not transfer...

Page 6: ...ls and features Save this manual for future reference Champion Automatic Transfer Switch with aXis ControllerTM Module 1 aXis Controller 2 Antenna 3 Generator L1 and L2 Terminals 4 Battery Charger Fus...

Page 7: ...5 Wire land 5 B B BLACK 6 Wire land 6 B R RED A 120VAC circuit must be installed for battery charging From ATS fuse block or distribution panel install L1 and N to Wire land 2 and 3 respectively Autom...

Page 8: ...or future reference TOOLS REQUIRED NOT INCLUDED 5 16 in Hex Wrench Mounting Hardware Line Voltage Wire 1 4 in Flat Screwdriver Conduit Fittings Location and Mounting Install the ATS as close as possib...

Page 9: ...a wire brush All power cables must enter the enclosure through the enclosure knockouts 1 Determine where the flexible liquid tight conduit will pass through the building from the inside to outside Whe...

Page 10: ...voltage controls route your low voltage wiring into the ATS using code appropriate conduit and fittings Connect the wiring to pin 1 and pin 2 of either AC1 or AC2 as shown in the diagram above Please...

Page 11: ...lled HSB Off ATS will control the start of the HSB using the AC2 Relay In this setting the AC2 can not be used to manage a load Pins 1 and 3 of the AC2 connector will be used for the HSB startup signa...

Page 12: ...here are three tabs located at the top of the page ATS GEN and LMM Each tab will display the status for the Transfer Switch Home Standby Generator or Load Management Module s respectively 4 When finis...

Page 13: ...ICATIONS aXis ControllerTM Module Automatic Transfer Switch Model Number 102006 Enclosure Style NEMA 3R outdoor Maximum Amps 200 Nominal Volts 120 240 Load Management Circuits 4 Weight 43 lbs 19 6 kg...

Page 14: ...he life of a part or the equipment as a whole Installation Use and Maintenance This warranty will not apply to parts and or labor if the product is deemed to have been misused neglected involved in an...

Reviews: