200967 - 3500W DUAL FUEL PORTABLE GENERATOR
ASSEMBLY
19
NOTICE
–
The LPG hose included with this unit works with standard
20, 30, and 40 pound LPG tanks.
–
Verify the requalification date on the cylinder has not
expired.
–
Always position the cylinder so the connection between the
cylinder valve and generator inlet won’t cause sharp bends
or kinks in the LPG hose.
CAUTION
Do not allow children to tamper or play with the LPG cylinder
or hose connections.
CAUTION
Use approved LPG cylinders equipped with an OPD (overfilling
prevention device) valve. Always keep the cylinder in a vertical
position with the valve on top and installed at ground level
on a flat surface. Cylinders must not be installed near any
heat source and should not be exposed to sun, rain, and dust.
When transporting and storing, turn off the cylinder valve and
generator LPG valve, and disconnect the cylinder. Plug the
outlet, usually by a plastic protective cap, if one is available.
Keep cylinders away from heat and ventilated when in a
vehicle.
WARNING
If there is a strong smell of LPG: Close valve on the cylinder.
Check all connections for leaks by wetting the fittings with a
solution of soap and water. Bubbles which appear or bubbles
which grow indicate that a leak exists. Do not smoke or light a
cigarette, or check for leaks using a match, open flame source
or lighter. Contact a qualified technician to inspect and repair
an LPG system if a leak is found, before using the generator.
Grounding
Your generator must be properly connected to an appropriate
ground to help prevent electric shock.
WARNING
Failure to properly ground the generator can result in electric
shock.
A ground terminal connected to the frame of the generator has
been provided (see Controls and Features for terminal location).
For remote grounding, connect a length of heavy gauge
(12 AWG minimum) copper wire between the generator ground
terminal and a copper rod driven into the ground. We strongly
recommend that you consult with a qualified electrician to ensure
compliance with local electrical codes.
Neutral Floating*
–
Neutral circuit
IS NOT
electrically connected to the frame/
ground of the generator.
–
The generator (stator winding) is isolated from the frame and
from the AC receptacle ground pin.
–
Electrical devices that require a grounded receptacle pin
connection will not function if the receptacle ground pin is not
functional.
Neutral Bonded to Frame*
–
Neutral circuit
IS
electrically connected to the frame/ground of
the generator.
–
The generator system ground connects lower frame cross-
member below the alternator. The system ground is connected
to the AC neutral wire.
* See your Specifications section for specified type of grounding.