120 VAC POWER

(Wiring and hookup only by a qualified electrician/installer!)

NOTES:

Maximum ambient temperature for installation, 104 F.

For automotive use only, no motorcycles, bicycles or pedestrians.

Be sure your main power (120 VAC) is OFF before attempting
hookup. The 120 volts AC supply should be terminated to the
wires below the duplex receptacle. Connect the 120 VAC to
BLACK wire, Neutral to the WHITE wire and Ground the GREEN
wire. 

Warning: Do not connect any 120 VAC wires directly to the

terminal strips on the electronic control board.

Only U.L.

approved 14 AWG (or larger) 600 volt insulated wire should be
used. A separate UL approved 10 amp circuit breaker should be
used for each MEGA SLIDE UL operator. 

Batteries must be

installed after 120 VAC Power is turned on.

See BATTERY at

page 10 and 120 VAC wiring diagram.

(UL-325, main power must be off before attempting to connect
any accessories devices).

INPUT COMMANDS

(Use common and normally open contacts from devices
connected to these inputs)

JP2 INPUT

This input will stop the gate and activate the siren.

This input is for connection to wired contact edge sensors at
pinch points and photo beams that run along either side the gate
panel when in open position (if dead panel is present one beam
should run along it)

INPUT COMMANDS - J5 CONNECTOR BLOCK AT TOP OF
CONTROL BOARD.

Control wire connections at low voltage terminal strip will be at
the top of the electronic control board. Make connections to the
appropriate points for the desired operation. Wires should be U.L.
approved 600 volt rated and at least 18 awg. All external control
devices must have normally open dry contacts. 

DO NOT

CONNECT ANY DEVICE WHICH WOULD DELIVER ANY VOLTAGE
OF ANY KIND TO THESE TERMINALS.

Terminals 9, 10, 11, 12 are the commons (0 VDC) used to
activate the following inputs.

1, 2, 3 OPEN:

These inputs will trigger gate open when pulsed

or hold gate open with maintained contact. When released gate
will close if closing timer is on or if close input is given.

4, AUXILIARY OPEN:

This is the wired line of sight, intended

manual reset input. Use this input to reset the unit after a 2nd
sequential obstruction is sensed and gate is locked with siren
running. This input normally functions as listed below.
Acts same as 1, 2, 3 above with S2-6 off. With S2-6 ON this
will operate as a pulse-open, pulse-close. 

NOTE:

Pulse to close will only work when gate is at full open

position.

Version 6.34 or higher only, SIREN will run for 5 minutes after

2nd sequential obstruction

, then turns itself off, however

operator will require a reset signal to J5 #4 to re-activate gate.
In addition, cycling the AC power switch will also reset unit.

W I R I N G   A N D   H O O K U P

5, SAFETY:

Safety edge(s) and safety loop input. This function

will make the gate reverse and go back to the open position if it
was closing. Input is for all NORMALLY OPEN contact safety
devices. This input is disabled when gate is in the full closed
position.

6, CLOSE:

ANTI-TAIL GATE close input. When using a vehicle

detector, you must use the presence contacts (N.O. and C.)
This input will QUICK close gate after input is applied and then
removed. It will stop the open cycle and reverse gate to close.
(Example: Car crosses over close loop before gate reaches full
open position – gate will reverse and close). 

NOTE:

The close

input also acts as a safety-stop in that if gate is closing and a
tail-gater is sensed at the close input, the gate WILL STOP its
closing motion and not continue to close until the close input is
removed (car backs up) or gate is re-opened.

7, BACK-AWAY (FOR BARRIER ARM GATE ONLY):

This input is

recommended for use with our Mega Arm barrier gates. For
your Mega Slide UL, please use terminals 1, 2 or 3 for your
free exit loop input.

8, SHADOW LOOP:

This input operates as a hold open only

when gate is a full open position.

9, 10, 11, 12 COMMON:

These inputs used for common 

(0 VDC) to above listed functions.

Note:

J5 inputs 1-8 are tied to LED indicators to assist in trouble

shooting.

3-BUTTON CONTROL STATION (VERSION 6.41 OR HIGHER
ONLY):

Not already in place. See diagram below.

Open

Close

Stop

J5 Commons #9-12

J5 Input #1

J5 Input #6

JP2 Connector

(Note: Siren Will
Sound When Stop
Button Is Depressed)

120 Vac (Black)

Neutral (White)

Ground (Green)

Duplex
Outlet Box

120 VAC POWER CONNECTION 

Connect 120 VAC to the 3 wires
that come out from the bottom
of the duplex outlet box.

Summary of Contents for LIFTMASTER PROFESSIONAL MSLDCBB

Page 1: ...unit must only be installed by an experienced technician Disconnect AC power and batteries before servicing IMPORTANT Read and understand Warranty Page first Batteries not included MUST be connected f...

Page 2: ...t Locations 16 MEGA SLIDE UL PARTS LIST Part Numbers and Descriptions 17 Parts Shipped 17 OPERATOR NOTES 18 WARRANTY 19 REPAIR PARTS AND SERVICE 20 TA B L E O F C O N T E N T S IMPORTANT SAFETY INSTRU...

Page 3: ...is class operator is approved for the application of the operator 1 2 3 or 4 required ______ A sphere with a 2 1 4 diameter cannot be pushed through the gate or fixed panel ______ A safety screen mesh...

Page 4: ...erator must be in the line of sight and must be an intended reset Access control devices of any kind that required intended on purpose activation may be used for this reset Devices that will cause an...

Page 5: ...e secondary stop photo beam should be installed along the gate s path that is covered when open Photo beams are to be installed according to their manufacturer s instructions and are to be placed in a...

Page 6: ...ds installed covering all cantilever wheels required All controls located far out of reach of gate fixed panel and operator required This class operator is approved for the application of the operator...

Page 7: ...y to persons use photo electric eyes on both sides of gate and pressure sensing edges at all pinch points and at the front leading edge of the gate Safety loops vehicle detectors should be installed i...

Page 8: ...helf maybe installed after all conduits are cut to proper height and all wiring has been properly routed NOTE Do not attempt to hook up the 120VAC mains if wires are LIVE or HOT Be sure power is off C...

Page 9: ...is input to reset the unit after a 2nd sequential obstruction is sensed and gate is locked with siren running This input normally functions as listed below Acts same as 1 2 3 above with S2 6 off With...

Page 10: ...R any input at J5 with control detectors receivers keypads timers etc wires to it must also be run to the same terminals of the second Along with these control wires both operators MUST share a common...

Page 11: ...delay if activated MODE SELECTIONS SWITCH PACK S2 6 8 SWITCH 6 Sets auxiliary open input terminal 4 at J5 to be pulse open pulse close example residential applications SWITCH 7 AUTO CLOSE TIMER Defaul...

Page 12: ...vel as possible but still ensuring that it will slow down just before reaching the closed position INSTANT REVERSE DEVICE IRD The instant reverse device is an internal circuit that continuously monito...

Page 13: ...can be used with up to 15 rolling code remotes or passwords in HIGH security mode Alternately it can be used with up to 31 of any type remote in NORMAL security mode including any combination of roll...

Page 14: ...the right side of the gate operator frame Once turned off motor will not run and gate can be pushed by hand T R O U B L E S H O O T I N G Flip switch up for normal operation Flip switch down to diseng...

Page 15: ...DEVICE Gate will open when activated by an access control device When timer expires if used gate will close Figure 2 Terminal 5 is safety input Terminals 1 2 and 3 are open inputs DUAL DIRECTION AS E...

Page 16: ...AC XFMR MOTOR RED YEL YEL BLU ORG 24VDC REQULATED F4 F3 1 AMP DC F1 H BEAT BATTERY LOW AC POWER C O N T R O L B O A R D L AY O U T COMPONENT LOCATIONS Accessory power is 24VDC regulated rated at 500...

Page 17: ...BER DESCRIPTION 12 MS014 Siren 100 db 13 MS015 Transformer 110 220 VAC 24VAC 14 MS016 Duplex Outlet MS017 Bolt and Nut 4 Reducer 15 MS018 Idler Pulley Bolt Washer and Nut 16 MS019 120 VAC On Off Switc...

Page 18: ...18 OPERATOR NOTES...

Page 19: ...erating freely or not on level ground The warranty set forth above is entirely exclusive and no other warranty whether written or oral is expressed or implied LiftMaster inc specifically disclaims any...

Page 20: ...andard Time 6 00 A M TO 7 00 P M Monday through Friday 8 00 A M TO 4 30 P M Saturday www liftmaster com WHEN ORDERING REPAIR PARTS ALWAYS GIVE THE FOLLOWING INFORMATION PART NUMBER PART NAME MODEL NUM...

Reviews: