Chamberlain LiftMaster K001A6039 Installation Instructions Manual Download Page 6

GATE RUNS TOO SLOW

GATE DOES NOT CLOSE
AUTOMATICALLY

GATE WON’T STAY OPEN
WHEN USING FIRE INPUT

Fire Input switch should
be a constant contact
key switch connected to
Open Loop input 
(Open only).

INTERRUPT LOOP DOES
NOT ACT PROPERLY

EXIT LOOP (FREE EXIT)
DOES NOT OPEN GATE

MAGLOCK DOES NOT
WORK

Maglock does not hold
gates locked

1) Open and Close Limits are set too

If the Open and Close Limits are set within the ramp down distance of 

close together.

each other, the gate will run at slow speed all the time.

2) The gate is starting within the ramp

Gate will run slow to limits if motion is started within the ramp-down 

down distance from the Open or 

distance from the limit.

Close Limit.

1) Verify that the TTC is turned OFF.

Verify that the TTC is ON and set.

2) Gate opened by an obstruction reversal.

Check gate area to ensure path is unobstructed.

3) The Interrupt Loop is obstructed.
4) Obstructed close photoelectric eye or edge.
5) The Open input is "stuck".

Check the Open Loop area to ensure all obstructions are removed. If an
external opening device or entry or entry system is attached, check for
proper operation of that system.

1) Fire Input switch is a momentary 

Make sure the Fire Input switch is constant contact. If it is not, replace

contact.

with a constant contact switch.

1) Bad loop sensor or loop detector.

Replace loop sensor or loop detector.

2) Bad connection between loop sensor, 

Check connections to make sure they are secure.

loop detector, and the control board.

1) Bad loop sensor or detector.

Replace loop sensor or loop detector.

2) Bad connection between the loop

Check connections to make sure they are secure.

sensor, loop detector, and the 
control board.

3) The Shadow Loop is obstructed.

Check the gate area to make sure all obstructions are removed.

4) An Open photoelectric eye or safety 

Check the gate area to make sure all obstructions are removed.

edge is obstructed.

1) Bad connection between the Maglock, 

Check connections between the Maglock, its power supply, and 

its power supply, and the control board.

the control board to make sure they are secure.

2) Bad Maglock or Maglock power supply.

Replace Maglock or Maglock power supply.

3) Large gap between gates.

Reduce the gap between the gates.

4) Bad control board.

Replace the control board.

FAULT

POSSIBLE CAUSE

FIX

DIAGNOSTIC CODES

# OF BLINKS

MEANING

1

No Stop Switch Connected

2

Gate 1 Arm Disengaged

3

Gate 2 Arm Disengaged

4

Both Gate Arms Disengaged

5

RPM Reversal

6

Force Reversal

7

Processor Reset

8

ROM Check Failed

9

RAM Check Failed

10

EEPROM Check Failed

T R O U B L E S H O O T I N G

©2005, The Chamberlain Group, Inc.

01-32324

All Rights Reserved

Printed in Mexico

Summary of Contents for LiftMaster K001A6039

Page 1: ... going to the antenna at the board F connector Figure 2 4 Remove all quick connect terminals in use to the logic board Figure 2 Wiring terminals Motor connectors Alarms Reset terminals NOTE Remember location of all wire connections for reinstallation 5 Disconnect the earth ground wire from the board connector J4 6 Remove the screws 4 that fasten the control board to the mounting bracket and remove...

Page 2: ...onnect the earth ground wire to the board connector J4 5 Reconnect the coaxial cable to the board F connector B 6 Reconnect all quick connect terminals A to the logic board Wiring terminals Motor connectors Alarms Reset terminals NOTE The quick connect terminals blue connectors that have wires attached from the previous board can be reused 7 Clear electrical box of all debris and tools COMPLETE TH...

Page 3: ...1 Turn Bi Part switch to desired setting Set to Off for single gate applications 2 Press the LEARN LIMITS button 3 The SET OPEN LIMIT LED will blink 4 Use the Gate 1 buttons to move Gate 1 to the desired open position Repeat if Gate 2 is present using Gate 2 buttons 5 Press the LEARN LIMITS button to set the Open Limit for gate s 6 The SET OPEN LIMIT LED will turn off The SET CLOSE LIMIT LED will ...

Page 4: ...products COMPATIBLE REMOTES 315MHz Passport Remote Security Remotes CPT13 370LM CPT23 371LM CPT33 372LM Security Keypad 373LM 376LM 374LM R1 LEARN XMITTER 2 LiftMaster L1 R1 R2 Z1 K5 Ø14GPØ89ØE Ø14LGØ89ØE Ø14SKØ89ØE K6 K2 F3 10A 32V D1Ø P1 P2 J1 J19 S1 Q9 K1 Z12 MAGLOCK ALARM GATE 1 C C NC NO NO GRN WHT YEL BLU RED BRN SET OPEN LIMIT SET CLOSE LIMIT LEARN LIMITS DIAGNOSTIC GATE 1 SAVE MAGLOCK MODE...

Page 5: ...tton connection loose Check SBC and COM connections to ensure they are secure 3 STOP button connection loose Check STOP button connections STOP and COM to make sure they STOP LED is OFF are secure 4 Obstruction is blocking the photoelectric Check gate area to ensure photoelectric eyes are not blocked eyes in the direction of movement 5 The safety edge is damaged Check gate area to ensure safety ed...

Page 6: ...t If it is not replace contact with a constant contact switch 1 Bad loop sensor or loop detector Replace loop sensor or loop detector 2 Bad connection between loop sensor Check connections to make sure they are secure loop detector and the control board 1 Bad loop sensor or detector Replace loop sensor or loop detector 2 Bad connection between the loop Check connections to make sure they are secur...

Reviews: