8
CONTROL WIRING
Standard C2 or B2 Wiring
Standard operators are shipped from the factory with
jumper set for C2 wiring, which requires constant
pressure on button to close the door. If momentary
contact on close direction is desired (B2 wiring) you
must include an entrapment protection device. See
close control settings to the right.
WIRING
This Operator has
Control Wiring.
SUPPLEMENTAL WIRING DIAGRAM(S)
REPLACEMENT WIRING DIAGRAM
Note: Supplemental Wiring Diagrams are
to be used in addition to 1753 or 1754.
Replacement Wiring Diagram is to be used
in place of 1753 or 1754.
SPECIAL CONTROL
WIRING DATA
LOCATING THE CONTROL STATION
All operators are supplied with some type of control station. Generally a three button station
(OPEN/CLOSE/STOP) is provided. A two-position key switch or control station (OPEN/CLOSE) may be added or
substituted when requested at the time of order. Mount the control station near the door.
WARNING
CAUTION
WARNING
WARNING
INSTALL THE CONTROL STATION WHERE THE
DOOR IS VISIBLE, BUT AWAY FROM THE DOOR AND
ITS HARDWARE. IF CONTROL STATION CANNOT BE
INSTALLED WHERE DOOR IS VISIBLE, OR IF ANY
DEVICE OTHER THAN THE CONTROL STATION IS
USED TO ACTIVATE THE DOOR,
A REVERSING
EDGE MUST BE INSTALLED ON THE BOTTOM OF
THE DOOR. FAILURE TO INSTALL A REVERSING
EDGE UNDER THESE CIRCUMSTANCES MAY
RESULT IN SERIOUS INJURY OR DEATH TO
PERSONS TRAPPED BENEATH THE DOOR.
W A R N I N G
TO PREVENT ENTRAPMENT
DO NOT START DOOR DOWNWARD
UNLESS DOORWAY IS CLEAR
OPEN
OPEN
CLOSE
CLOSE
STOP
Control Station
WARNING Notice
Push
Buttons
IMPORTANT: Mount WARNING NOTICE beside or
below the push button station.
MOUNT WARNING NOTICE
DETERMINE WIRING TYPE
Refer to the wiring diagram located on the inside cover the electrical box to determine the type of control wiring.
Wiring Diagram label on inside cover
of electrical box
Wiring
Type
SPECIAL CONTROL WIRING
If your operator was shipped from the factory with
non-standard control wiring or with optional
accessories that require addition instructions, refer to
the wiring diagram(s) indicated in the special control
wiring data box. When a replacement wiring diagram
is present, wiring diagrams in this manual will not
apply. Refer only to the replacement wiring diagram
for all connections.
Constant pressure on close (C2 wiring)
In the electrical enclosure, a RED wire was placed on
terminal block #12. With this setting, the operator
will require constant pressure on close control in
order to keep door moving in the close direction.
Momentary contact on close (B2 wiring)
Move RED wire from terminal block #12 to terminal
#2. The operator will require only momentary contact
to close the door.