Site Preparation

Check the national and local building codes

BEFORE

installation. Refer also to the

Site Planning Safety Checklist

in the Appendix.

Conduit and Concrete Pad

Trench and install conduit. Before trenching, contact underground
utility locating companies. Conduit must be UL approved for low
and high voltage. Consider the operator placement BEFORE
installing the pad or post.

Concrete Pads

Safety

Entrapment protection devices are required to protect against any entrapment or
safety conditions encountered in your gate application. Install a warning sign
(two provided) on the inside and outside of the property, where easily visible.

Warning Sign

Gate

Gate must be constructed and installed according to ASTM F2200
standards (refer to page 4). Gate must fit specifications of operator
(refer to specifications).

SAFETY CATCH ROLLERS
Install catch rollers with safety covers 
on the side of a post or wall with a 
minimal distance of half an inch 
between the rollers and gate

DO NOT use a gate catch post. 
Because the coasting distance may 
vary due to changes in temperature, it 
is NOT recommended to install a 
catch post in front of the gate's path. 
To do so will cause the gate to hit the 
post in certain instances.

Additional Accessories

The vehicle loops allow the gate to stay open when vehicles are obstructing the
gate path. Suggested for vehicles 14 feet (4.27 m) or longer. Vehicle loops are
not required but are recommended. Before installing your Access Control
Device(s) be sure to complete a site survey and determine the best device for
your site needs.

Outside Property

Vehicle Loops

Access Control
Device

INTRODUCTION

Summary of Contents for HDFSL24UL

Page 1: ...V vehicular slide gate applications HDFSL24UL is intended for use in Class III and IV vehicular slide gate applications ONLY Visit LiftMaster com to locate a professional installing dealer in your area This gate operator is compatible with MyQ and Security 2 0 accessories LiftMaster 300 Windsor Drive Oak Brook IL 60523 Access installation and technical support guides or register this product Send ...

Page 2: ... 37 MAINTENANCE 38 Important Safety Instructions 38 Maintenance Chart 39 Batteries 39 Drive Train 39 TROUBLESHOOTING 40 Diagnostic Codes 40 Control Board LEDs 41 Troubleshooting Chart 42 SOLAR PANELS 45 Step 6 Solar Panel s 45 REPAIR PARTS 49 ACCESSORIES 50 WARRANTY 52 APPENDIX 53 SAMS Wiring With Relays Not Energized 53 Dual Gate Settings 53 Limit Setup With a Remote Control 54 Wiring Diagram 55 ...

Page 3: ...er devices in the same entrapment zone Use the Site Planning Safety Checklist in the appendix to identify entrapment zones found in your installation Requirements l A minimum of two independent monitored entrapment protection devices are required to be installed at each entrapment zone l It is the responsibility of the installer to install external monitored entrapment protection devices for each ...

Page 4: ...g a Stop and or Reset button it must be located in the line of sight of the gate Activation of the reset control shall not cause the operator to start 10 A minimum of two 2 WARNING SIGNS shall be installed in the area of the gate Each warning sign is to be visible by persons located on the side of the gate on which the sign is installed 11 For a gate operator utilizing a non contact sensor a Refer...

Page 5: ...t the existing gate shall be upgraded to conform to the provisions of ASTM F2200 2 4 When the gate of an automated gate system requires replacement the new gate shall conform to the provisions of ASTM F2200 3 Vehicular Horizontal Slide Gates 3 1 The following provisions shall apply to Class I Class II and Class III vehicular horizontal slide gates 3 1 1 All weight bearing exposed rollers 8 feet 2 ...

Page 6: ...er link Eye Bolt Kit LiftMaster Monitored Retro Reflective Photoelectric Sensor Model LMRRUL HDSL24UL only 5 ft Edge sensor kit HDSL24UL 1 HDFSL24UL 2 Key 2 Battery 12 Vdc 7AH 2 Warning Signs 2 Installation Manual Cover Operator MONITORED ENTRAPMENT PROTECTION DEVICES INTRODUCTION ...

Page 7: ...Maximum Gate Travel Distance 75 feet 22 86 m Maximum Gate Travel Speed HDSL24UL 1 ft sec HDFSL24UL 2 ft sec Maximum Daily Cycle Rate Continuous for line voltage not continuous for solar Maximum Duty Cycle Continuous Operating Temperature Without Heater 20 C to 60 C 4 F to 140 F With Optional Heater 40 C to 60 C 40 F to 140 F 120VAC accessory power outlets 6 amps When the 3PHCONV kit is used the ou...

Page 8: ...ASTM F2200 standards refer to page 4 Gate must fit specifications of operator refer to specifications SAFETY CATCH ROLLERS Install catch rollers with safety covers on the side of a post or wall with a minimal distance of half an inch between the rollers and gate DO NOT use a gate catch post Because the coasting distance may vary due to changes in temperature it is NOT recommended to install a catc...

Page 9: ...re than 18 inches 46 cm deep l ALWAYS wear protective gloves and eye protection when changing the battery or working around the battery compartment Types of Installations Standard Installation Gate Rail Stop Operator Inside Property Gate Rail Stop Rear Installation Inside Property Gate Rail Stop Operator Gate Rail Stop INSTALLATION ...

Page 10: ...er conduit Below the frost line Check all national and local codes 6 15 2 cm Above Ground 1 2 1 8 cm 1 2 2 5 5 1 cm Pad conduit location Rear Installation 1 The gate operator should be installed near the back of the gate in the OPEN position Lay out the concrete pad 2 Install the electrical conduit 3 Pour a concrete pad reinforced concrete is required conduit Back of gate Gate in open position Bel...

Reviews: