MOTORS:

The motor to open first is the “master “ motor 1, the other one is
the “second” motor 2. If only one motor is used, the connection
for motor 2 is held in reserve.

The cable for the capacitors supplied with the motors must be
inserted in terminals OP and CL together with the cables for the
direction of rotation (brown/black). For space reasons the
capacitors may also be installed in the distribution boxes.  Make
sure that they are connected correctly and powered sufficiently.
The capacitors are responsible for the force that the motors will
have later on.

First connect the motors as follows:

Motor 1 

4

Brown & capacitor 1

5

Blue

6

Black & capacitor 1

—————————————————————

Motor 2 

7

Black & capacitor 2

Blue

9

Brown & capacitor 2

To start up see the section Initial operation / basic setting.

Note: During initial operation, the gate wings must OPEN for
the first run. If one or both wings close(s) instead of opening,
the brown and black cables must be swapped on this motor.
Disconnect from the power supply before doing so!

Typical configuration of a unit:

1. Motor
2. Control board
3. photocell (active for closing), max. height 200 mm
First photocell. 
4. photocell (active for opening), max. height 200 mm
Second photocell. 
5. Flashing light (optional)
Important visual information on the movement of the gate.
6. Key-operated switch
Is mounted on the outside. The gate is opened by key or by
entering a number.
7. Contact strip (optional)
Safeguards the gate on being touched. Contact strips can be
mounted on the gate or on the pillars. If required, contact strips
must be mounted at a height of up to 2.5m. 
8. photocell (active for opening/closing), max. height 200 mm
(optional)
9. Contact loop entrance (optional)
10. Safety contact loop in the swinging range of the gate (optional)
11. Contact loop exit (optional)

The control board complies with the latest EU

guidelines. One of these guidelines specifies that the closing
forces at the gate edge must not exceed 400 N (40 kg) for the last
500 mm before the door is CLOSED. Above 500 mm, the
maximum force at the gate edge must not exceed 1400 N (140
kg). If this cannot be ensured, a contact strip must be mounted on
the gate at a height up to 2.5 m or on the pillar on the opposite
side (EN12453). 

GB-2

709438

Summary of Contents for CB10

Page 1: ...električne instalacije CB10 Istruzioni e installazione elettrica CB10 Instruktie en electrische installatie CB10 Manuais e instalação eléctrica CB10 Instrukcja i instalacja elektryczna CB10 Инструкции и электромонтаж CB10 GB F D E HR GR CZ H I NL P PL www liftmaster com Email info chamberlain com 0678 AT BA BE BG CH CY CZ DE DK ES FR GB GR HR HU IE IS IT LU MT NL NO PL PT RO RU SE SI SK TR YU RUS ...

Page 2: ...709438 Chamberlain GmbH 2010 all rights reserved ...

Page 3: ... modes Standard standard no self hold hold to run in closing Automatic with stop residential channel separation car park no self hold hold to run Max running time 80 sec Rest time 0 150 sec Dimensions 124x152 mm without box GB 1 PLEASE START BY READING THESE IMPORTANT SAFETY RULES SAVE THESE INSTRUCTIONS This safety alert symbol means Caution failure to comply with such an instruction involves ris...

Page 4: ...ypical configuration of a unit 1 Motor 2 Control board 3 photocell active for closing max height 200 mm First photocell 4 photocell active for opening max height 200 mm Second photocell 5 Flashing light optional Important visual information on the movement of the gate 6 Key operated switch Is mounted on the outside The gate is opened by key or by entering a number 7 Contact strip optional Safeguar...

Page 5: ...ton Learn Delete radio channel 1 8 CH2 pushbutton Learn Delete radio channel 2 9 L1 pushbutton Learning the distance covered 10 JMP1 jumper Programming the photocell 11 DIP1 Dip switch block 12 PT4 potentiometer Force setting drive 2 13 PT3 potentiometer Force setting drive 1 14 PT2 potentiometer Automatic closing 15 PT1 potentiometer Bipart delay GB 3 DESCRIPTION OF THE LEDs RED LEDs should be sw...

Page 6: ...or 1 master is opened first and closed last It is necessary that the bipart delay is always set so that nobody is caught between the wings when they close Left stop Bipart delay OFF PT2 TRIMMING POTENTIOMETER 2 AUTOMATIC CLOSING TIMER TO CLOSE The waiting time for the gate for GATE OPEN can be defined The gate is closed 0 150 sec after the set time expires Only working with failsafe photocell s 77...

Page 7: ...ile pedestrian stops the next one closes Residential Gate closed 1 impulse opens the next one closes the next one opens the next one closes etc Gate closed 1 impulse opens pedestrian door the next one closes immediately Impulse while pedestrian closes the gate immediately Impulse during the rest closes the gate immediately Impulse during automatic closing opens the gate immediately Impulse during ...

Page 8: ...rd LED off OK LED on constantly control board disables LED flashes OK no photocell connected Cable cross section 0 5 mm2 or more Voltage 12 24 volts AC DC Do not use any fixed copper lines Do not lay any 230 volt cables in parallel and do not lay any 2 cables in the same cable trunking open öffnen ouvrir open close schliessen fermer sluiten close schliessen fermer sluiten open öffnen ouvrir open J...

Page 9: ...g range of the gate Connection to terminals 19 20 stop Relay output of the evaluation unit when using failsafe photocells NO closer If relay photocells are used as NC opener Automatic closing function not recommended Attention The only safeguard that is not permitted according to EU standard 24 VDC OUTPUT For relay infrared senors or other devices e g receivers max 500 mA Do not use any fixed copp...

Page 10: ...E transmitterS Press button CH1 The LED Learn1 lights up red Now press one of the transmitter s button for approx 5 seconds The LED Learn 1 flashes now Finished Proceed in exactly the same way for CH2 However now press one of the transmitter s buttons that has not yet been assigned Up to 128 transmitters can be programmed in this way To delete the programmed transmitter setting simply press button...

Page 11: ...gins at this position 4 Press L1 again limit stop reached 2 seconds Wing 2 now starts automatically 5 Press L1 again soft stop OPEN for wing 2 begins at this position 6 Press L1 again limit stop reached 2 seconds Wing 2 now restarts automatically and closes 7 Press L1 again soft stop CLOSED for wing 2 begins at this position 8 Press L1 again limit stop CLOSED reached 2 seconds Wing 1 now starts au...

Page 12: ...bserve LEDs find and rectify fault The gate opener doesn t respond at all although the controller has been connected LEDs are on 1 Remote control has not been programmed 2 LEDs indicate a fault 3 Photocell connected incorrectly 4 Jumper between STOP and COM missing 5 Motor terminal possibly not connected properly 1 Programming remote control 2 Find and rectify fault s see description of LEDs 3 Che...

Page 13: ...ends the gate and or post 1 A B dimensions correct 2 Force set too high 3 Reinforce gate 1 Check A B dimensions 2 Turn force potentiometer in an anticlockwise direction 3 Possibly screw gate opener to a reinforcement plate post Possibly fit reinforcement plate at point of pull push pressure gate wing Use suitable screws and plugs Can different A B dimensions be used on the two sides Generally spea...

Reviews: