3.0    Installation and Safety

 

3.1   General

 

There  are  no  health  hazards  associated  with  this  product  whilst  in  normal  use.    However,  care  should  be 
exercised during the following operations.  
In the UK the requirements of the 

'Health and Safety at Work Act'

 must be met. 

Handling  and  electrical  work  associated  with  this  product  to  be  in  accordance  with  the 

'Manual Handling 

Operations Regulations' and 'Electricity at Work Regulations, 1989'

.  Your attention is drawn to the paragraphs 

(i) 'Electrical Supplies', (ii) 'Electrical Fault Finding and Replacement' and (iii) 'Inspection and Maintenance'.  The 
luminaires are Class 1 and should be effectively earthed. 
The  information  in  this  leaflet  is  correct  at  the  time  of  publication.    The  company  reserves  the  right  to  make 
specification changes as required. 
The polycarbonate diffuser presents a potential source of ignition by 

electrostatic electricity

. The diffuser 

should only be cleaned using a damp cloth. The luminaire should not be mounted very near to any probable 
location of fast-moving stream of dry air, steam etc. which could generate a propagating brush static discharge. 

 

3.1.1  Use in Combustible Dust Atmospheres – Zone 22 

Where the equipment is used in ignitable dust atmospheres reference must be made to the selection and 
installation standards in order that the equipment is used correctly. This applies to the de-rating of surface 
temperature for use where dust clouds may be present. Dust layers should not be allowed to accumulate on the 
fitting surface and good housekeeping is required for safe operation. Dust in layers has the potential to form 
ignitable clouds and to burn at lower temperatures.  
Refer to EN (IEC) 60079-10-2 & EN (IEC) 60079-14 for additional details of selection and installation.  

 

3.1.2   Hybrid Mixtures – Gas plus Dust. 

Where Hybrid mixtures exist as defined in EN1127 as a potentially explosive atmosphere, consideration should 
be given to verifying that the maximum surface temperature of the luminaire is below the ignition temperature of 
the hybrid mixture. 

 

3.1.3  Cleaning

 

The body of the luminaire may be cleaned with a mild solution of household detergent and water, after cleaning 
the body should be washed and wiped with clean water.  The diffuser should not be polished or wiped with a dry 
cloth, as a risk of explosion due to electrostatic discharge may result. Cleaning of the diffuser with any chemical 
or hydrocarbon solvent-based cleaner may result in severe damage. 

 

3.1.4  Aggressive substances 

If the equipment is likely to meet aggressive substances, then it is the responsibility of the user to take suitable 
precautions that prevent it from being adversely affected, thus ensuring that the type of protection provided by 
the equipment is not compromised. 
Aggressive substances: e.g. acidic liquids or gases that may attack metals or solvents that may affect polymeric 
materials. 
Suitable precautions: e.g. regular checks as part of routine inspections or establishing from the material’s data 
sheets that it is resistant to specific chemicals. 

 

3.2   Tools

 

12mm, 5mm and 3mm flat blade screwdriver. Pozi number 2 screwdriver 
Suitable spanners for installing cable glands. Pliers, knife, wire strippers/cutters. 

 

3.3    Electrical Supplies and Control Gear

 

Luminaires fitted with electronic control gear are suitable for a rated supply of 230Vac 50-60Hz, 
The safety limits are +10% of this, however, luminaires should  not be operated continuously at more than +/-
10% of the rated supply voltage of the control gear

The supply would normally be expected to lie /-6% of 

rated. The LED supply is regulated, therefore the light output over the range is substantially unchanged. 
The driver can also utilise DC voltage 176-264Vdc.   

 

Electronic gear has integrated power factor correction to >0.90. 

 

Warning:  

Luminaires are assessed and/or tested for EMC requirements. This is based on the disposition 

                 of entry cables and, where appropriate, through wiring arrangements as supplied or specified. 

Summary of Contents for Protecta III 02L

Page 1: ...minaires for use with Inotec Central Battery System CBS ATEX IECEx and UKEX Important Please read these instructions carefully before installing or maintaining this equipment Good electrical practices...

Page 2: ...U by reason of the Type Examination EU Type Examination and meets the UK statutory requirements Sl 2016 No 1107 and compliance with the Essential Health and Safety Requirements M Poutney Technical Man...

Page 3: ...tially explosive atmosphere consideration should be given to verifying that the maximum surface temperature of the luminaire is below the ignition temperature of the hybrid mixture 3 1 3 Cleaning The...

Page 4: ...uct is certified for ATEX IECEx and UKEX and to comply with the certification for installation cable glands and sealing plugs must be ATEX IECEx or UKEX certified depending on site requirements Cable...

Page 5: ...ring between body and tray Replace in reverse order 3 8 4 Retro Fitting Lamps to LED s Before opening the front cover ensure that the luminaire is isolated from the mains supply Access for retro fitti...

Page 6: ...nts and the body parts may give off noxious fumes if incinerated Take care to render these fumes harmless or avoid inhalation Any local regulations concerning disposal must be complied with Any dispos...

Page 7: ...Watts Line Current Inrush Current Duration 02L JSVS 2 x 560mm 2296 400mA 18 0 08A 31A 41 s 04L JSVS 2 x 1120mm 3526 300mA 25 0 11A 27A 41 s 07L JSVS 2 x 1120mm 6596 600mA 54 0 24A 22A 42 s 02L JSVT 2...

Page 8: ...I PR3C 03 doc Issue 03 17 01 2022 8 IOM PROTECTA LED Ex ec...

Page 9: ...gegeben da keine nderungen erfolgt sind die einen Einfluss auf den technischen Stand des Produkts haben Terms of the directive Standard Date Certified to Standards Date Declared to Prescription de la...

Page 10: ...Produkts der Produkte zusammen mit dieser Erkl rung das Ger t die Ger te alle technischen und regulativen Anforderungen der oben aufgef hrten Direktiven erf llt Name and Date Mark Poutney 17 01 2022...

Reviews: