98
GB
MENU
SUB-MENU
P
ARAMETER
DESCRIPTION
RANGE
NOTE
5
2
7
Heating circuit type
0. Quick radiators
1. Medium radiators
2. Slow radiators
3. Quick under-fl oor system
4. Medium under-fl oor system
5. Slow under-fl oor system
6. Room control only
Proportional
5
2
8
Max. integral action on room sensor
HYD
5
3
Zone 2 diagnostics
5
3
0
Room temperature
5
3
1
Set room temperature
5
3
2
Flow temperature
5
3
3
Return temperature
5
3
4
Z2 heat request status
ON - OFF
5
3
5
Pump status
ON - OFF
5
4
Zone 2 devices
5
4
0
Zone pump modulation
0. Fixed speed
1. Modulating on delta T
2. Modulating on pressure
5
4
1
Target delta T for modulation
5
4
2
Fixed pump speed
6
ZONE 3 PARAMETERS
6
0
Temperature setting
6
0
0
Daytime temperature
6
0
1
Night-time temperature
6
0
2
Zone 2 temperature
6
0
3
Zone anti-frost temperature
6
1
General parameters
menu - settings