background image

SAFETY CONSIDERATIONS

Installing, starting up, and servicing air--conditioning equipment
can be hazardous due to system pressures, electrical components,

and equipment location (roofs, elevated structures, etc.).
Only trained, qualified installers and service mechanics should

install, start--up, and service this equipment.
Untrained personnel can perform basic maintenance functions such
as cleaning coils. All other operations should be performed by

trained service personnel.
When working on the equipment, observe precautions in the

literature and on tags, stickers, and labels attached to the
equipment.
Follow all safety codes. Wear safety glasses and work gloves. Keep

quenching cloth and fire extinguisher nearby when brazing. Use
care in handling, rigging, and setting bulky equipment.
Read these instructions thoroughly and follow all warnings or
cautions included in literature and attached to the unit. Consult

local building codes and National Electrical Code (NEC) for

special requirements. Recognize safety information. This is the
safety--alert symbol

!

!

. When you see this symbol on the unit and

in instructions or manuals, be alert to the potential for personal

injury.Understand these signal words: DANGER, WARNING, and
CAUTION. These words are used with the safety--alert symbol.

DANGER identifies the most serious hazards which

will

result in

severe personal injury or death. WARNING signifies hazards

which

could

result in personal injury or death. CAUTION is used

to identify unsafe practices which

may

result in minor personal

injury or product and property damage. NOTE is used to highlight

suggestions which

will

result in enhanced installation, reliability, or

operation.

!

WARNING

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal

injury or death.
Before installing, modifying, or servicing system, main

electrical disconnect switch must be in the OFF

position. There may be more than 1 disconnect switch.

Lock out and tag switch with a suitable warning label.

EXPLOSION HAZARD

Failure to follow this warning could

result in death, serious personal injury,

and/or property damage.
Never use air or gases containing

oxygen for leak testing or operating

refrigerant compressors. Pressurized

mixtures of air or gases containing

oxygen can lead to an explosion.

!

WARNING

CAUTION

!

EQUIPMENT DAMAGE HAZARD

Failure to follow this caution may result in equipment

damage or improper operation.
Do not bury more than 36 in. (914 mm) of refrigerant pipe

in the ground. If any section of pipe is buried, there must be

a 6 in. (152 mm) vertical rise to the valve connections on

the outdoor units. If more than the recommended length is

buried, refrigerant may migrate to the cooler buried section

during extended periods of system shutdown. This causes

refrigerant slugging and could possibly damage the

compressor at start--up.

SYSTEM REQUIREMENTS

Allow sufficient space for airflow and servicing unit. See

minimum required distances between unit and walls or

ceilings.

ence)
Power Wiring:

The main power is supplied to the outdoor unit. The field supplied

connecting cable from the outdoor unit to indoor unit consists of

three (3) wires and provides the power for the indoor unit. Two
wires are high voltage AC power and one is a ground wire.
Consult your local building codes and the NEC (National
Electrical Code) or CEC (Canadian Electrical Code) for special

requirements.
All wires must be sized per NEC or CEC and local codes. Use

Electrical Data table MCA (minimum circuit amps) and MOCP

(maximum over current protection) to correctly size the wires and
the disconnect fuse or breakers respectively.
Per caution note, only copper conductors with a minimum 300 volt
rating and 2/64--inch thick insulation must be used.

Communication Wiring:

A separate shielded copper conductor only, with a minimum 300
volt rating and 2/64--inch thick insulation, must be used as the

communication wire from the outdoor unit to the indoor unit.
To minimize voltage drop of the control wire,

CAUTION

!

EQUIPMENT DAMAGE HAZARD

Failure to follow this caution may result in equipment

damage or improper operation.

S

Wires should be sized based on NEC and local codes.

S

Use copper conductors only with a minimum 300 volt

rating and 2/64 inch thick insulation.

2

To minimize voltage 

drop, the factory recommended wire size is 14/3 stranded with a 

   ground. In special cases where there is high electrical interference, 

   please use a separate shielded 16GA stranded control wire.

Specifications are subject to change without notice.

Summary of Contents for GWHD(30)ND3EO

Page 1: ...Models GWHD 30 ND3EO GWHD 36 ND3EO GWHD 42 ND3EO MULTI DUCTLESS INVERTER HEAT PUMP Installation manual OUTDOOR UNIT...

Page 2: ...TY CONSIDERATIONS 2 INDOOR UNITS COMBINATIONS 3 PREFACE 4 PRODUCT INTRODUCTION 5 PREPARATION BEFORE INSTALLATION 8 INSTALLATION 10 TROUBLESHOOTING 17 THE CONDITIONS LISTED BELOW ARE NOT CLASSIFIED INT...

Page 3: ...leak testing or operating refrigerant compressors Pressurized mixtures of air or gases containing oxygen can lead to an explosion WARNING CAUTION EQUIPMENT DAMAGE HAZARD Failure to follow this cautio...

Page 4: ...3 INDOOR UNITS COMBINATIONS Specifications are subject to change without notice...

Page 5: ...indoor unit receives the signal to make full use of the after heat function for the next operation 5 When the running modes of the indoor and outdoor units conflict the conflict appears on the wired c...

Page 6: ...20 can be realized V arious product lineup is provided with capacity range from 30KBtu to 42KBtu which can be widely used in a boarding house a working area and especially applicable in a location wit...

Page 7: ...Level and Capacity Code of the Indoor 6 Specifications are subject to change without notice Indoor Unit Nominal Unit Btuh Indoor Model Number Outdoor Model Number 9 000 GWH09QC D3DNA1D I 12 000 GWH12Q...

Page 8: ...parameters below are tested under a rated working condition If there is any change to them please refer to the nameplate 3 The heating capacity parameters of the heat pump indoor unit excludes the au...

Page 9: ...lace free of dust typhoons and earthquakes 3 Try to keep the unit away from combustible inflammable and corrosive or exhaust gases 4 Leave some space for heat exchanging and servising to guarantee the...

Page 10: ...is the more the cooling and heating capacity will decrease 9 Specifications are subject to change without notice Outdoor Unit System size 30 36 42 Piping Min Piping Length ft 9 84 9 84 9 84 Standard...

Page 11: ...tline dimension and mounting holes Unit inch 38 3 7 36 2 9 17 1 3 14 4 7 31 24 15 5 7 Fig 4 3 3 38GJQG36 3 42K Outline dimension and mounting holes Fig 5 36K 10 40 42 1 2 24 5 6 17 1 3 14 1 4 15 3 4 4...

Page 12: ...forcefully otherwise the capillary or other pipes may crack whichwould result in leakage 2 The refrigerant pipe should be supported by brackets Do not allow the unit to support the weight of the refri...

Page 13: ...ft H3 Height difference between indoor units m 24 6ft 24 6ft H2 b a e d c L4 L3 L2 L5 L1 Outdoor uni t Height difference between indoor unit and outdoor unit H1 Height difference between indoor units...

Page 14: ...erant pipe and electric wire together with tape and separate them from the drain pipe to prevent the condensate water from overflowing b Wrap the pipe from the bottom of the outdoor unit to the top of...

Page 15: ...ge in the Outdoor Unit before Shipment NOTICE 1 The outdoor unit has been charged with refrigerant prior to delivery The refrigerant charge is not included and is an additional charge for the indoor u...

Page 16: ...nd overload Table 8 Models Power Supply Capacity of the breaker A 208 230V 60Hz 30 208 230V 60Hz 30 208 230V 60Hz 30 30K 36K 42K 15 Specifications are subject to change without notice GWHD 30 ND3EO IN...

Page 17: ...ng and connection line of each indoor unit should connectwell according to the instruction 3 The electric installation should be carried out by a technician instructed in the local laws regulations an...

Page 18: ...acity Does the unit have proper thermal insulation It may causecondensation and dripping Does the unit drain well It may causecondensation and dripping Is the voltage in accordance with the rated volt...

Page 19: ...absorbed in are blown out again NOTICE If problem can not be solved after checking the above items please contact C H service center and show phenomena and models Following circumstance are not malfu...

Page 20: ...conflicts with that of outdoor unit indoor fault indicator will flash and conflict will be shown on the wired controller after 5 minutes Indoor unit stops to run and meanwhile change outdoor operatin...

Page 21: ...Over burden Flash 3 times Outdoor ambient sensor malfunction Flash 6 times Outdoor tube sensor malfunction Flash 5 times Exhaust sensor malfunction Flash 7 times Attain the temperature of switch on F...

Page 22: ...ced 4 Check if the filter screen has been set correctly 5 After a long period of nonuse open the main power switch 8 hours before re operating the unit to preheat the compressor crankcase 6 Check if t...

Page 23: ...Add West Jinji Rd Qianshan Zhuhai Guangdong China 519070 MANUFACTURER GREE ELECTRIC APPLIANCES INC OF ZHUHAI www cooperandhunter us...

Reviews: