![CG TAO-659 Maintenance Handbook Download Page 38](http://html1.mh-extra.com/html/cg/tao-659/tao-659_maintenance-handbook_2585395038.webp)
CAMTECH/97/E/TM/3.0
TM Maintenance Handbook January’97
35
3.2.3.1
Testing of Neutral Axis
Connect a voltmeter in between `N’ and `S’ pole of the TM (at brush holder),
apply 50 to 60 V DC to the TM field. The voltmeter reading should stand at
zero.
3.2.4
Voltage Drop Test for Commutator Segments
Direct current is applied to the
armature winding (about 20 to
30% )of rated current of the TM
at suitable intervals between the
commutator segments. Voltage
drop is measured with a mil-
livoltmeter (Multimeter- 50mV) as
shown in figure 3.3. The varia-
tions in the voltage between
commutator segments must be
less than
±
5 % of the mean
value. If there are extremely large
variations in the voltage drop, this
means either that the joint on the
commutator riser has come loose
or that there is a short circuit in
the winding.
Therefore, in such cases a thorough investigation must be made for the
cause, and the trouble must be repaired. In making these tests, please note
that if an excessively large current is applied, the winding will be over heated.
Precautions:
In case of carrying out voltage drop tests of the commutator
segments, particular care must be given to the fact that the current must not be
switched ON and OFF by means of the electrodes in contact with the commuta-
tor. This is because the commutator segment will be damaged by arcing if the
electrodes are switched ON and OFF. For this reason, it is absolutely neces-
sary to use the knife switch for the current to ON and OFF.
3.2.5 Ovality Test
Ovality on the commutator surface must be tested by means of an ovality
testing gauge which should not be more than 0.06
mm .
3.2.6 Heat Run Test
After reassembling the TM, to conduct the heat run test ,apply 50v DC to
the TM and allow to run for four hours. During this testing, experience the tem-
perature rise and bearing noise at both PE & CE , as designated.
APPENDIX A
Figure 3.3