CG Drives & Automation 01-7513-11r0
Technical data
27
4.3
System timing information
1) You must determine and evaluate the complete response time of the system,
i.e. also consider e.g. sensor reaction time and response time of safety
switching device.
4.4
Environmental conditions
The environmental specifications differ from product to product. Please consult
the user manual of the Emotron main product for actual environmental
specifications for the actual Emotron product.
As the Emotron OSTO_100 option can be used with any 2.1 model of the
standard Emotron products FDU/VFX/CDU/CDX, as well as in any
customized product based on these standard products, the Emotron
OSTO_100 option has been verified against the most severe environmental
specifications. These are listed in the Table 7 below.
Table 6
Timing information
System event
Time
Response time for one of
STO1
or
STO2
inputs going low until IGBT driver sig-
nals made powerless
1
≤
15 ms
STO_STATUS_ISO response time from
STO active state achieved
≤
10 ms
Filter time constant on input:
Maximum OSSD test pulse length
≤
1 ms
Table 7
Environmental conditions
Parameter
Normal
Operation
Transportation
Storage
Ambient
temperature
0-45
°
C (55
°
C with
reduced drive
load)
-40°C to +70°C
-25°C to +60°C