Page 64 of 72
Prometer 100 User Manual
BGX501-943-R01
Transformer Compensations
Instrument transformer compensations
Instrument transformer compensations are specified as error in percent for amplitude, and as error in minutes
(one-sixtieth of a degree) for phase angle. These errors can be specified separately for all voltages and
currents.
AmpErr
Amplitude error as percent
PhaseErr
Phase angle error in minutes
meas
u
Measured voltage
u
Compensated voltage
Amplitude compensation
)
1
/(
AmpErr
u
u
meas
+
=
Phase angle compensation
PhaseErr
up
up
meas
−
=
In 3-element meters, phase voltages are compensated and in 2-element meters, phase to phase voltages. The
same calculation is used for all currents and voltages.
Power transformer losses
Power transformer losses consist of copper and iron losses. They are expressed as percentages of nominal
power. One value is specified for active loss and one for reactive.
Iron loss
FeLoss
Active iron loss as percent of nominal power.
meas
P
1
Measured power.
1
P
Compensated power.
Nom
Nominal power per phase
Nom
FeLoss
P
P
meas
⋅
+
=
1
1
Copper loss
CuLoss
Active copper loss as percent of nominal power.
i
Phase current.
nom
i
Nominal current.
Nom
CuLoss
i
i
P
P
nom
meas
⋅
⋅
+
=
2
)
/
(
1
1
Corresponding calculations made for active and reactive power.
Definition of phase order
Correct phase order (123) corresponds to phase position:
p
U
1
Phase position for U1
Summary of Contents for Prometer 100
Page 1: ...Prometer 100 High precision meter User Manual BGX501 943 R01...
Page 2: ...Page 2 of 72 Prometer 100 User Manual BGX501 943 R01 Copyright 2014 SIHPL...
Page 17: ...BGX501 943 R01 Prometer 100 User Manual Page 17 of 72...
Page 23: ...BGX501 943 R01 Prometer 100 User Manual Page 23 of 72...
Page 31: ...BGX501 943 R01 Prometer 100 User Manual Page 31 of 72 Display to be added...