Page 62 of 72
Prometer 100 User Manual
BGX501-943-R01
Active and reactive power
Active and reactive power is calculated as the sum of harmonic component power up to 31st harmonic. The
calculation is made with plus and minus signs, where negative power represents export direction and positive
represents import direction.
P
Total active power
1
P
Active power in L1
Q
Total reactive power
1
Q
Reactive power in L1
3
2
1
P
P
P
P
+
+
=
3
2
1
Q
Q
Q
Q
+
+
=
For 2-element meters, two elements are added instead of three.
Apparent power
S
Total apparent power
1
S
Apparent power in L1
2
2
Q
P
S
+
=
2
2
1
1
1
Q
P
S
+
=
Energy
Energy is calculated by integrating power (P, Q and S) over time.
Definition of quadrants
The term phase angle is described under its own heading below.
Quadrant I: phase angle 1–90
°
Quadrant II: phase angle 90–180
°
Quadrant III: phase angle -180–(-90)
°
Quadrant IV: phase angle (-90)–0
°
Active energy
Active energy is calculated for import and export. The direction is controlled by the sign for active power
(+ import, – export).
Active energy import: quadrant I and IV
Active energy export: quadrant II and III
Reactive energy
Reactive energy is calculated for four quadrants. The quadrant is controlled by the sign for active and reactive
power (e.g., active power >= 0 and reactive power >= 0 corresponding to quadrant I).
Reactive energy import: quadrant I and II
Active energy export: quadrant III and IV
Reactive energy inductive: quadrant I and III
Summary of Contents for Prometer 100
Page 1: ...Prometer 100 High precision meter User Manual BGX501 943 R01...
Page 2: ...Page 2 of 72 Prometer 100 User Manual BGX501 943 R01 Copyright 2014 SIHPL...
Page 17: ...BGX501 943 R01 Prometer 100 User Manual Page 17 of 72...
Page 23: ...BGX501 943 R01 Prometer 100 User Manual Page 23 of 72...
Page 31: ...BGX501 943 R01 Prometer 100 User Manual Page 31 of 72 Display to be added...