Installing and start up the control panel
7.1
Using the control panel as a room thermostat
The control panel can be used as a room thermostat.
Before installation make sure that the electrical power supply is disconnected.
Picture 5
Install the room thermostat in the living space according to following:
•
A suitable installation is about 1.5 meters above floor and on an inner wall.
•
The room thermostat must not be combined with other thermostats in the same control zone.
Use a suitable 2-conductor cable between the connection box and the operator control panel. With a conductor
area of 0.6 mm
2
, the maximum cable length is 50 m
etres. Maximum 5Ω/conductor. Install the cable ends in the
terminal, marked A and B, located in the operator control panel. Connect the plug to the connection box again.
The unit can now be connected to the electrical power.
After starting up, choose configuration and operating mode, see