Instruction Handbook PFP-23hpVGD-MR
- 12 -
C.E.T. Fire Pumps Mfg. This handbook is subject to change without notice,
Contact your local C.E.T. dealer or C.E.T. direct to ensure you have the latest version.
6.
Performance
The pump running under *normal conditions will give you these performances:
*
Normal conditions : geostatic height of 4’ 10” (1.5m), temperature de 59°F (15°C), water clear of sand
and debris, atmospheric pressure < 3280’ (1000m) from sea level
None conformance to the instructions given in this handbook can reduce the
performances given by the pump.
0
250
500
750
1000
1250
0
2
4
6
8
10
12
14
16
0
50
100
150
200
250
300
350
0
50
100
150
200
250
F
lo
w
(
L
P
M
)
Head (BAR)
F
lo
w
(
G
P
M
)
Head (PSI)
Flow (GPM / LPM)
Pressure (PSI / Bar)
285 / 1078
10 / 0.6
265 / 1003
50 / 3.4
150 / 567
150 / 10.3
80 / 302
200 / 13.8
35 / 132
225 / 15.5