background image

Instruction Handbook                       PFP-11hpHND-EM-HP  

- 11 -

 

 C.E.T. Fire Pumps Mfg. This handbook is subject to change without notice, 

Contact your local C.E.T. dealer or C.E.T. direct to ensure you have the latest version.

 

5.

 

Transport and storage 

 

Transport :  

 

WARNING: Never transport the pump while it is running.  

 

The pump and its frame have been designed to be easily transported by two adults 

or more. 

 

The pump shouldn’t be inclined by more than 35° during transport, especially if 

the engine has oil in it.  

 

Storage: 

 

Warning: It is important to take into account the dangerous materials and 

components,  such  as  diesel,  oil  and  the  battery.  Store  away  from  heat 

source, flames and sparks (e.g. heater using a pilot).  

 

The pump should be stored in a cool, dry place away from salty air. If the pump is 

to be stored for over 30 days, you should completely drain the fuel and carefully 

follow  the  steps  written  in  your  engine  owner’s  manual.  It  is  important  to 

disconnect the battery and charge it at least once every 3 months if you don’t use 

the pump for that period of time. 

 

Summary of Contents for PFP-11HPHND-EM-HP

Page 1: ...C E T direct to ensure you have the latest version Instruction Handbook Version 1 0 Model PFP 11hpHND EM HP Your version of the pump the engine and their accessories may vary from the one seen on the...

Page 2: ...r C E T direct to ensure you have the latest version Table of contents 1 FOREWORD 3 2 SAFETY INSTRUCTIONS 4 3 DESCRIPTION 7 4 GENERAL INSTRUCTIONS 10 5 TRANSPORT AND STORAGE 11 6 PERFORMANCE 12 7 STAR...

Page 3: ...ry of experience in building fire fighting equipment If you follow the directives given in this handbook your pump will be a useful ally for many years to come For your own safety and those around you...

Page 4: ...fler o NEVER run the engine without a muffler or proper exhaust system o NEVER operate the engine if the fuel tank cap is removed do not fill the tank while the engine is running If fuel is spilled mo...

Page 5: ...hot water scald and burn hazards NEVER let the pump run for more than one minute with discharge valve s completely closed When the pump is running make sure to always leave the discharge valve slight...

Page 6: ...e attached note will put at risk the security of the personnel operating near the pump The words danger warning and caution are used for levels of risk This symbol means that it is mandatory to read a...

Page 7: ...e the latest version 3 Description This portable pump is directly driven by the very high quality Honda gasoline 11 hp engine It is equipped with an electric starter and also has a backup recoil start...

Page 8: ...esistance aluminum alloy body It also has an axial mechanical seal The pump can operate to a maximum pressure of 200 PSI 13 8bar It has been designed to work at a temperature between 5 F 15 C and 104...

Page 9: ...starter Install in a properly ventilated area Recommended individual protective equipments not included Firefighting grade protective gloves conforms to EN659 or equivalent Protective glasses Hearing...

Page 10: ...at the end of the suction hose If you are not sure of the quality of the pumped water use a floating strainer to prevent drawing the sand or stone from bottom source The Honda GX340 engine is certifi...

Page 11: ...than 35 during transport especially if the engine has oil in it Storage Warning It is important to take into account the dangerous materials and components such as diesel oil and the battery Store awa...

Page 12: ...rmances Normal conditions geostatic height of 4 10 1 5m temperature de 59 F 15 C water clear of sand and debris atmospheric pressure 3280 1000m from sea level None conformance to the instructions give...

Page 13: ...have the latest version 7 Starting procedure 7 1 Place the pump on a flat and stable surface with an angle less than 15 Place your pump as close as possible to the water source WARNING NEVER run the e...

Page 14: ...se the safety of your installation Warn the surrounding people before you start the pump It is important that you evaluate the trajectory of the hose to prevent incidents NOTE If you are pumping from...

Page 15: ...ttle control to its maximum speed CAUTION NEVER run the pump dry for more than one 1 minute it could damage the mechanical seal Always prime the pump as fast as possible 7 11 When water comes out of t...

Page 16: ...o ensure you have the latest version 7 14 2 Control the opening of a valve or a nozzle at the end of the discharge hose By reducing the opening pressure will increase and flow will decrease WARNING NE...

Page 17: ...ve water inside the casing of the pump and valves The water could freeze and damage them CAUTION After each use it is important to flush the inside of your pump with fresh water This will help prevent...

Page 18: ...test Functional test Connect suction hose of 2 5 diameter and a length of 10 Make sure to completely submerge the end of the suction hose at least 12 Connect a discharge hose of 1 5 diameter and not...

Page 19: ...t Dispose properly of the used oil and filters according to the local environmental regulations WARNING Never run the pump if the inlet strainer is not on or is damaged Maintenance Interval Daily Firs...

Page 20: ...r tight Make sure to have well understood and applied the priming protocol of the pump Check for any possible air leakage in the suction hose Check the mechanical seal for leakage Faulty engine Refer...

Page 21: ...eposits or dust is obstructing the priming system Carefully dismantle the priming system clean it up or replace the components if necessary The engine runs fine but the pump output is low The restrict...

Page 22: ...RE PUMPS MFG incurs no liability under this warranty or otherwise for equipment which has been abused altered or improperly maintained or for equipment which has been returned for inspection or repair...

Page 23: ...E T direct to ensure you have the latest version 13 Contact Us For repair or questions about warranties please contact your local C E T fire pumps dealer E mail service fire pump com Tel 1 450 568 271...