C400R User Manual
Page 11
ELECTRICAL SPECIFICATION
INPUT
Model No.
C400R-010-B
C400R-010-C
C400R-020-B
C400R-020-C
C400R-030-B
C400R-030-C
Phase
Single
Frequency
50/60Hz +/- 10%
AC Voltage (V)
220/230/ 240/250V
220/230/ 240/250V
220/230/ 240/250V
220/230/ 240/250V
220/230/ 240/250V 220/230/ 240/250V
Current(A)
230V / 7.5A
230V / 13.5A
230V / 16A
OUTPUT
Model No.
C400R-010-B/C
C400R-020-B/C
C400R-030-B/C
Power rating*
1000VA/900W
2000VA/1800W
3000VA/2700W
Voltage
220VAC/230VAC/240VAC
Frequency
50/60Hz
Waveform
Sinusoidal
BATTERIES
Model No.
C400R-010-B
C400R-010-C (EBM)
C400R-020-B
C400R-020-C
(EBM)
C400RR-030-B
C400RR-030-C
(EBM)
Voltage
36V
36V
48V
48V
72V
72V
Capacity
7Ah x 3
7Ah x 6 (EBM)
9Ah x 4
9Ah x 8 (EBM)
9Ah x 6
9Ah x 12 (EBM)
OPERATING ENVIRONMENT
Ambient Temperature
0
°Cto 40
° C (Full load no de-rating)
40
°C to50
°C output power derated to 50% load, Charger current derated 50%
Operating humidity
< 95% no condensing
Altitude
< 3000m
3000m (Above 3000m altitude10% derating per 1000m)
Storage temperature
-25°C~55°C (-13 to 130°F)
Audible noise
< 50 dBA at 1 meter typical for 6kVA models
< 55 dBA at 1 meter typical for 10kVA models
*Above 3000m altitude10% derating per 1000m.