C400 User Manual
Page 11
INSTALLATION
•
DO NOT
connect the UPS to a mains supply until installation is completed
•
Ventilation of the UPS is important for proper operation. Ensure the air vents on the front, side and rear of the
UPS are clear. Allow adequate space around the UPS. The airflow diagram is shown as below:
Installation considerations:
•
The final location of the UPS unit must be on a flat stable surface in a well-ventilated environment
•
DO
keep at least 150mm of free space behind the rear panel
•
If installing an additional unit, place it next to the first unit in its final location
•
DO
allow the UPS to reach ambient temperature before turning on
•
The UPS needs to be fully charged to achieve full autonomy
C400 TOWER MODEL INSTALLATION
STEP ONE
Ensure utility power is switched off.
STEP TWO
Carefully place the UPS in its final location
STEP THREE
If not installing additional EBMs skip to step six.
Position the EBM adjacent to the UPS, ensure adequate space for UPS ventilation.
STEP FOUR
Connect the EBM to the UPS
STEP FIVE
To connect to multiple EBMs the EBM cable is connected directly into the previously installed EBM
STEP SIX
After setting up the UPS, the load can then be connected. Please make sure the load equipment is turned off before connecting
all loads into the output ports
STEP SEVEN
Plug the UPS into a mains power socket and turn Utility power on. The UPS will power on in bypass mode and begin charging
STEP EIGHT
To switch the UPS from bypass mode to online press and hold the
‘ON/Silence’ button
for 1 second the unit will beep and the LCD
display will show
“LINE”
signalling that the UPS is powered and protecting the equipment
DO NOT MAKE ANY UNLICENSED MODIFICATIONS TO THE UPS. THIS MAY INCUR DAMAGE AND AFFECT THE UPS
WARRANTY.
A QUICK START VIDEO GUIDE FOR THE C400 TOWER MODEL IS AVAILABLE AT
C400 battery model tower variant.