Installation
1. Remove all boxes of firebricks and any packaging from inside the appliance.
2. Clean out the masonry fireplace ensuring the ashes are placed in a metal container.
3. Remove or lock open the damper plate in the masonry fireplace.
4.
5. The insert must be installed in compliance with the minimum clearances to combustible
constructions and floor protection stated on appliance certification label (located on back of unit)
and listed below. See page 5 for further instructions about floor protection.
FAILURE TO FOLLOW THESE MINIMUM CLEARANCE REQUIREMENTS MAY RESULT IN AN
UNSAFE INSTALLATION.
6. Install the refractory bricks (see page 10).
7. Install faceplate onto inser
. The trim should fit against the face of the
fireplace. If this is not a good fit, a 2"(50mm) wide strip of fibreglass insulation can be used to
insure a good fit.
Contact local building, fire officials or authorities having jurisdiction about permits, restrictions
and installation inspection requirements in your area.
t (see pages 9 and 11)
CLEARANCE TO COMBUSTIBLE CONSTRUCTIONS
A
UNIT TO SIDE WALL
12” (305mm)
B
UNIT TO TOP TRIM
10” (255mm)
C
UNIT TO SIDE TRIM
10” (255mm)
D
UNIT TO MANTEL
17” (430mm)
E
FLOOR PROTECTOR FRONT
16” (405mm) IN THE US
18” (457mm) IN CANADA
F
FLOOR PROTECTOR SIDE
8” (200mm)
4
FLOOR
MANTLE
S
ID
E
W
A
L
L
FACE PLATE
S
ID
E
T
R
IM
F
C
E
B
D
12”
(305mm)
MAX
A
**See Floor protection requirements, next page
TOP TRIM
FLOOR PROTECTOR