The fuel to be used is only wood logs under 25% humidity content (wood dried min. 1 year).
The return flow temperature always has to be over 60°C. This can be reached by obligatory
connection of the 3-way mixing valve with actuator and return flow sensor (60°C)
- recommended
or 3-way thermic valve ESBE VTC 512 (60°C), VTC 531 (60°C), LTC 141 (60°C), Laddomat 21
(63°C) which keeps return flow temp. to the boiler min. 60°C.
The connection of CAS water accumulation tanks is obligatory. It is recommended to connect min.
50 liters water accumulation to each 1 kW of boiler power (or see local regulation).
To the closed central heating system an expanding vessel has to be connected (the volume of the
expanding vessel is min. 10% of the installation volume).
To the open central heating system an open expanding vessel has to be conneced (OPC), which
volume has to be min. 7% of the installation volume.