background image

 

28 

7. Specification

   

 

7.1 Specification 

 

Table7. Electrical Specification 

Model 

1000 

1500 

      1500S 

2000 

2000S 

3000 

3000S 

Capacity 

Watt 

900W 

1350W 

1800W 

2700W 

Input 

Input voltage range 

161-276VAC 

Frequency range 

50/60Hz ±5Hz for Normal Mode 

40-70Hz for Generator Mode 

Output 

Voltage 

220/230/240VAC 

Voltage Regulation 
(Batt. Mode) 

±5%   

Frequency 

50Hz or 60Hz 

Waveform 

Pure sinewave 

Overload rating 

Line Mode 

110% -0%, +8%: shutdown after 3 minutes.   

150% -0%, +10%: shutdown after about 200ms 

Battery Mode 

110% ± 6%; shutdown after 30 seconds.   

120 % ± 6 %; shutdown after about 100ms 

Internal battery 
(Standard model) 

Battery Type 

2*12V/9AH  3*12V/9AH  6*12V/7AH  6*12V/9AH 

Backup Time 
(at full load) 

3

′ 

3

′   

4

′30″ 

3

′   

Recharge Time 

8 hours to 

90% after 

discharged 

4 hours to 

90% after 

discharged 

3 hours to 

90% after 

discharged 

4 hours to 

90% after 

discharged 

External battery 

module(EBM) 

Battery Type 

12V/7AH 

Interface 
 

RS-232 

Yes 

USB 

Yes 

Dry-Contact 

Optional 

SNMP 

Optional 

EPO 

Optional 

 
 
 
 

Summary of Contents for 1500VA

Page 1: ...USER MANUAL Line Interactive UPS 1000VA 1500VA 2000VA 3000VA Uninterruptible Power Supply System ...

Page 2: ...for 1000VA 1500VA 2000VA 3000VA series that should be followed during installation and maintenance of the UPS and batteries Please read all safety and operating instructions before operating the UPS Adhere to all warnings on the unit and in this manual And follow all operating and user instructions ...

Page 3: ... Configuring Green Function 21 5 Communication Port 22 5 1 RS 232 and USB Communication Ports 22 5 2 Emergency Power Off EPO 22 5 3 Network Management Card Optional 23 6 UPS Maintenance 24 6 1 UPS and Battery Care 24 6 2 Storing the UPS and Batteries 24 6 3 Time to Replace Batteries 24 6 4 Replacing UPS Internal Batteries 25 6 5 Testing New Batteries 27 6 6 Recycling the Used Battery 27 7 Specific...

Page 4: ...rm indications A control button from the front panel allows users to silence off the AC fail alarm and initiate the UPS self test sequence as well The UPS case for 1000VA 3000VA is made of metal This series is powered from the AC mains and supply AC outputs via receptacles on the rear panel Communication and control of UPS is available through serial or USB ports located on the rear panel The seri...

Page 5: ...eed 3 5mA The socket outlet that supplies the UPS shall be installed near the UPS and shall be easily accessible Protective earthling connections shall be such that disconnection of a protective earth should be made at one point that is the furthest away from the UPS maintaining the dedicated line in order to secure equipotential connection The UPS and EBMs connected in series should be installed ...

Page 6: ... in this manual and may appear in your application process Therefore all users should be familiar with them and understand their explanations Table1 Description of Commonly Used Symbols Symbol Description Alert you to pay special attention Caution of high voltage Alternating current source AC Direct current source DC Protective ground Recycle Keep UPS in a clear area ...

Page 7: ... out of the outer carton and set it on a flat stable surface 3 Discard or recycle the packaging in a responsible manner or store it for future use 3 3 UPS Setup All model series are designed for tower and rack purpose They can be installed into a 19 inches equipment rack Please follow the instruction for Tower Setup and Rack Mount Setup Tower setup This series of UPS can be placed horizontally and...

Page 8: ...5 Use the following procedure to install UPS in UPS stands 1 Slide down the UPS vertically and put two UPS stands at the end of the tower 2 Place down the UPS into two stands carefully ...

Page 9: ...6 3 Pull out the LCD box and rotate it in a clockwise direction to 90 degree and then push it back in the front panel ...

Page 10: ...s Both the UPS and external battery enclosure need 2U of valuable rack space Use the following procedure to install UPS in a rack 1 Align the mounting ears with screw holes on the side of the UPS and tighten the screw 2 Assemble the rack rails with the rack mounting ...

Page 11: ...8 3 Slide in the UPS into the rack rail and lock it in the rack enclosure 4 Tighten the screw and the load can then be connected ...

Page 12: ...he EBM in Tower form 1 Slide down the UPS and EBM vertically and place two UPS stands with the extend part at the end of the tower 2 Tighten the screw on the metal sheet for stabilization 3 Connect the Earth line from UPS port A to EBM port B B A ...

Page 13: ...eed to remove the small gate C on side of the front panel to allow the outlet wire of the EBM to pass through the gate and then reassemble front panel Connecting the EBM in a rack form 1 Using the same method as assembling UPS in a rack form assemble EBM into the rack mounting on the top or bottom of the UPS B A C ...

Page 14: ...11 2 Connect the earth line from UPS port A to EBM port B 3 Take off the LCD box and unscrew the internal screws A B Unscrew ...

Page 15: ...n reassemble front panel 5 After installing the UPS into rack the load can then be connected to UPS Please make sure the load equipment is turned off before plugging all loads into the output receptacle Connecting the Multiple EBMs 1000VA 1500VA 2000VA and 3000VA UPS include external battery port that allows users to connect multiple EBM in order to provide additional backup time Follow the proced...

Page 16: ... off the front panel and connect the battery terminal A from UPS to EBM terminal B shown as below And then connect the battery terminal D from the first EBM to the battery terminal E from the second EBM Users need to remove the small gate C on side of the front panel to allow the outlet wire of the EBM to pass through the gate and then reassemble front panel B C A D E ...

Page 17: ...e battery terminal A from UPS to EBM terminal B shown as below And then connect the battery terminal D from the first EBM to the battery terminal E from the second EBM Users need to remove the small gate C on side of the front panel to allow the outlet wire of the EBM to pass through the gate and then reassemble front panel Note Three or more EBMs can be connected to the UPS in the same way as sho...

Page 18: ...el display illuminates and UPS status display shows STbY 4 Press and hold the button more than 3 seconds The UPS status display changes to NORM 6 Check the UPS display for active alarms or notices Resolve any active alarms before continuing See Troubleshooting 8 If optional EBMs are installed see Configuring UPS for EBM numbers on page 21 to set the number of installed EBMs 9 To change any other f...

Page 19: ...t Standard back light is used to light up the display with black text and a blue background When the UPS has a critical alarm the backlight changes the background to red See Figure below Control Buttons functions There are four buttons on the control panel ON OFF UPS Test Alarm Silence Select Enter ...

Page 20: ... the Select button to select the settings value one by one Enter Enter settings mode Press and hold the button more than 3 seconds Enter settings item Press and hold the Enter button more than one second the UPS allows users to configure the settings and the settings string will flash Confirm settings Press and hold the Enter button for one second Exit Settings mode Press and hold the Enter button...

Page 21: ... plug indicator will light on if there is output power respectively UPS status user setting display String Strings Indicate the UPS status see Table 4 Strings Indicate user setting options see Table 5 Warning indication Light on when the UPS is failure or alarm Settings Light on when the UPS under settings mode Battery volume level display Indicate the amount of battery volume remaining Each batte...

Page 22: ...verload bATH Battery voltage is too high bATL Battery voltage is too low OVTP Internal temperature is too high FNLK Fan is locked bTWK Batteries are weak User Setting String Description The following table shows the options that can be changed by user Table5 User Setting String OPV Output voltage mode select 220 220V 230 230V 240 240V AVR Input type select 000 Normal range mode 001 Wide range mode...

Page 23: ...STbY to indicate that power is not available to your equipment The battery recharges when necessary 4 3 Configuring Load Segment Load segment are sets of receptacles that can be controlled through the display Each UPS has two configurable load segments See Rear Panels on page 30 for load segment for each UPS model Note This configuring can be operated when UPS is power on 1K model has only one loa...

Page 24: ...ss and hold the Enter button one second ups will return to current setting item 6 Exit Settings mode Press and hold the Enter button for 3 seconds or button for 0 5 second to exit setting mode 4 5 Configuring Green Function Green Function is that when an insignificant amount of load is detected the UPS will shut down output automatically on battery mode The green function is disabled on default mo...

Page 25: ...ll data and an orderly shutdown of the equipment The cable pins for the RS 232 communication port are identified as below and the pin functions are described in Table 6 Table6 DB9 Female RS232 dry contact PIN Description I O Function Explanation 1 BATLOW Output Battery low 2 RXD input RXD 3 TXD Output TXD 4 DTR Input N A 5 Common Common tied to chassis 6 DTR Input N A 7 RING Output Ring 8 LNFAIL1 ...

Page 26: ... Wire Size Rating Suggested Wire Size EPO 4 0 32mm2 12 22AWG 0 82mm2 18AWG Note Leave the EPO connector installed in the EPO port on the UPS even if the EPO function is not need EPO Connector 5 3 Network Management Card Optional Network Management Card allows the UPS to communicate in a variety of networking environments and with different types of devices The series UPS has one available communic...

Page 27: ... sounding the battery may need to be replaced Please check the battery connection or contact your local dealer to order new battery WARNING Turn off the UPS and disconnect the utility power cord from the wall outlet Servicing should be performed by qualified service personnel knowledgeable of batteries and required precautions Keep unauthorized personnel away from batteries Batteries can present a...

Page 28: ...harmful to skin and eyes Note If you are not qualified service personnel to replace the battery do not attempt to open the battery cabin Please call local dealer or distributor immediately 6 4 Replacing UPS Internal Batteries Follow the steps and Charts as below to replace batteries 1 Take off the LCD box and remove the screws 2 Slide and Pull the front panel leftward and then take it off 3 Discon...

Page 29: ...right inner battery bracket 5 Pull the battery pack out onto flat area 6 Install new battery pack into UPS 7 Screw up the battery bracket and reconnect the battery cable A and B 8 Re install the front panel back to UPS ...

Page 30: ... Recycling the Used Battery Warning Never dispose the batteries in a fire It may explode Do not open or mutilate the batteries Released electrolyte is harmful to the skins and eyes It may be toxic A battery can present a risk of electrical shock and high short circuit current To recycle properly the used battery please do not discard the UPS battery pack and batteries into the trash bin Please fol...

Page 31: ...wave Overload rating Line Mode 110 0 8 shutdown after 3 minutes 150 0 10 shutdown after about 200ms Battery Mode 110 6 shutdown after 30 seconds 120 6 shutdown after about 100ms Internal battery Standard model Battery Type 2 12V 9AH 3 12V 9AH 6 12V 7AH 6 12V 9AH Backup Time at full load 3 3 4 30 3 Recharge Time 8 hours to 90 after discharged 4 hours to 90 after discharged 3 hours to 90 after disch...

Page 32: ...unding every second UPS Fault Continuously Sounding Overload Sounding every second Battery Replacement Sounding every second Table9 Operating Environment Temperature 0 to 40 C Humidity 20 80 relative humidity non condensing Altitude 1500m Storage Temperature 15 to 45 C Table10 Dimensions and weights Model 1000 1500 1500S 2000 2000S 3000 3000S UPS Case Net weight kg 15 0 17 8 10 27 8 16 27 8 16 Dim...

Page 33: ...ar panel 1500VA Standard Super charger model rear panel No Function 1000VA 1500VA 1 AC Output 2 Modem Network Surge Protection 3 SNMP Port 4 AC Input 5 RS232 Dry Contact Communication Port 6 USB Port 7 EPO 8 Earth Line Port No Function 2K 3KVA Standard Supper charger model 1 AC Output 2 Modem Network Surge Protection 3 SNMP Port 4 Fan 5 AC Input 6 RS232 Dry Contact Communication Port 7 USB Port 8 ...

Page 34: ...31 2000VA Standard model rear panel 2000VA Super charger model rear panel 3000VA Standard Supper charger model rear panel ...

Page 35: ...32 The EBM rear panel description table and picture are shown as below 1 1 36V 72V EBM rear panel No Function 36V 72V EBM 1 Earth Line Port ...

Page 36: ...ouble Shooting Problem Cause Solution The UPS can t be turned on when power switch is pressed Internal fuse may be broken Please contact your local dealer UPS is on and no power to load Output Jumpers is not connected correctly Check output Jumpers No power on output receptacle Check if the LS1 and LS2 are set up from 001 to 000 Backup time is short Battery is empty Re charge the battery at least ...

Page 37: ...LAN at the same time such as shutting down system in security saving application data and shutting down the UPS when power fails Installation procedure 1 Go to the website http www ups software download com index htm 2 Choose the operation system you need and follow the instruction described on the website to download the software 3 When downloading all required files from the internet enter the s...

Reviews: