20
4.2 Operating Mode
Normal range mode: Under Input mode the UPS accepts AC input voltage
range for +/-20%.
Generator mode: Under generator mode, the low frequency transfer point can
go as low as 40Hz and as high as 80Hz before being transferred to battery
mode.
Wide range mode: Under Input settings mode, the UPS accepts AC input
voltage range for -30% ~ +20%.
Battery mode
When the UPS is operating during a power outage, the alarm beeps once every
four seconds and the LCD display string shows
“bATT” to indicate the UPS work
at battery mode.
If battery volume becomes low while in Battery mode, the alarm beeps once
every second and the LCD display string shows
“bATL”.
Standby mode
When the UPS is turned off and remains plugged into a power outlet, the UPS is
on Standby mode. The LCD display string shows
“STbY” to indicate that power is
not available to your equipment. The battery recharges when necessary.
4.3 Configuring Load Segment
Load segment are sets of receptacles that can be controlled through the display.
Each UPS has two configurable load segments. See
“Rear Panels” on page 30
for load segment for each UPS model.
Note: This configuring can be operated when UPS is power on.
1K model has only one load segment, can not configure.
To configure the load segment through the display:
1.
Enter settings mode:
Press and hold the Enter button
more than 3
seconds. Then UPS will transfer to setting mode.
2.
Select settings items:
Press the Select button
to select the setting items
show as Table 5.
3.
Enter settings item:
When the LCD display
“LS1” or “LS2”, press the enter
button
more than one second to enter the setting item and the settings
string will flash.
4.
Select setting value:
Press the Select button
to select the settings value.
Select the value [001] or [000] to set the desired load segment ON or OFF.