background image

©1998 Central Sprinkler Company
   Printed in U.S.A.

C-1A.1

Ordering
Information

Ordering Information:  When placing
an order, indicate the full product
name.  Please specify the quantity,
model, style, orifice size, temperature
rating, type of finish or coating, and
sprinkler wrench.

Availability and Service:  Central
sprinklers, valves, accessories, and
other products are available through-
out the U.S. and Canada, and interna-
tionally, through a network of Central
Sprinkler distribution centers. You
may write directly to Central Sprinkler
Company, or call (215) 362-0700 for
the distributor nearest you.

Conversion Table:
1 inch = 25.400 mm
1 foot = 0.3048 m
1 pound = 0.4536 kg
1 foot pound = 1.36 Nm
1 psi = 6.895 kpa

= 0.0689 bar
= 0.0703 kg/cm

2

1 U.S. gallon = 3.785 dm

3

= 3.785 liters

Conversions are approximate.

Central Sprinkler Company

451 North Cannon Avenue, Lansdale, PA 19446

Phone (215) 362-0700

FAX    (215) 362-5385

always use new sprinklers of the
same type and temperature rating as
replacements.

Because the discharge pattern is

critical to protection of life and property,
nothing should be hung or attached to
the sprinkler unit that would disrupt the
pattern.  Such obstructions must be
removed. In the event that construction
has altered the original configuration,
additional sprinklers should be installed
to maintain the protection level.

Do not attempt to replace sprinklers

without first removing the fire protec-
tion system from service.  Be certain
to secure permission from all

 Authori-

ties Having Jurisdiction, and notify all
personnel who may be affected during
system shutdown.  A fire watch during
maintenance periods is a recom-
mended precaution.

To remove the system from service

mode, first refer to the system operat-
ing guide and valve instructions.
Drain water and relieve the pressure
in the system piping.  Remove the
existing unit and install the replace-
ment, using only the special sprinkler
wrench.  Be certain to match model,
style, orifice, and temperature rating.

A fire protection system that has

been shut off after an activation should
be returned to service immediately.
Inspect the entire system for damage
and replace or repair as necessary.
Sprinklers that did not operate but were
subjected to corrosive elements of
combustion or excessive temperatures
should be inspected, and replaced if
need be. The 

Authority Having Juris-

diction will detail minimum replacement
requirements and regulations.

Guarantee:  Central Sprinkler Com-
pany will repair and/or replace any pro-
ducts found to be defective in material
or workmanship within a period of one
year from the date of shipment.  Please
refer to the current Price List for further
details of the warranty.

OBSOLETE

Summary of Contents for Omega C-1A

Page 1: ...by the heat collect ing fins and conducted to the alloy pellet At the rated temperature the Manufactured by Central Sprinkler Company 451 North Cannon Avenue Lansdale Pennsylvania 19446 1 98 C 1A Technical Data 3 8 1 2 9 5 mm 12 7 mm Orifice Adjustable Pendent Automatic Sprinkler alloy melts causing the ball plunger to drop freeing balls from the retaining groove This movement allows system water ...

Page 2: ...Drop 1 x 1 2 25 mm x 15 mm NPT Reducing Coupling Dust Cover 2 5 8 66 7 mm Max 1 3 4 44 5 mm Min 2 3 8 60 3 mm Flush take out 1 1 4 31 8 mm Max 3 8 9 5 mm Min 5 8 15 9 mm Flush Finished Ceiling Line 1 9 16 39 7 mm Max 11 16 17 5 mm Min 1 5 16 33 3 mm Flush Installation Diagram Omega C 1A Commercial Quick Response Omega Adjustable Model A Sprinkler Wrench O B S O L E T E ...

Page 3: ...ge Step 5 Leave the protector cap in place until the installation is finished When the system is ready for service remove the cap Step 6 To install the escutcheon plate align it with and press it over the sprinkler body until the outer edge of the escutcheon meets the mounting surface CAUTION Special care must be taken when installing with a CPVC system Sprinklers must be installed after the CPVC ...

Page 4: ...ation additional sprinklers should be installed to maintain the protection level Do not attempt to replace sprinklers without first removing the fire protec tion system from service Be certain to secure permission from all Authori ties Having Jurisdiction and notify all personnel who may be affected during system shutdown A fire watch during maintenance periods is a recom mended precaution To remo...