background image

©1998 Central Sprinkler Company
   Printed in U.S.A.

Central Sprinkler Company

451 North Cannon Avenue, Lansdale, PA 19446

Phone:  215-362-0700

FAX:  215-362-5385

GB Dry Pendent.2

Ordering Information:  When
placing an order, indicate the full
product name.  Please specify the
quantity, model, style, orifice size,
temperature rating, sprinkler finish,
and escutcheon finish.

Order dry pendents by the “A”
dimension.

Availability and Service:  Central
sprinklers, valves, accessories and
other products are available through-
out the U.S. and Canada, and interna-
tionally, through a network of Central
Sprinkler distribution centers. You may
write directly to Central Sprinkler
Company, or call  (215) 362-0700 for
the distributor nearest you.

Patents:  Patents are pending.

Conversion Table:
1 inch = 25.400 mm
1 foot = 0.3048 m
1 pound = 0.4536 kg
1 foot pound = 1.36 Nm
1 psi = 6.895 kpa

= 0.0689 bar
= 0.0703 kg/cm

2

1 U.S. gallon = 3.785 dm

3

= 3.785 liters

Conversions are approximate.

Ordering
Information

Do not attempt to replace sprinklers

without first removing the fire protec-
tion system from service.  Be certain
to secure permission from all 

Authori-

ties Having Jurisdiction, and notify all
personnel who may be affected
during system shutdown.  A fire
watch during maintenance periods is
a recommended precaution.

To remove the system from service,

first refer to the system operating
guide and valve instruction. Drain
water and relieve pressure in the
pipes.  Remove the existing unit and
install the replacement, using only the
recommended sprinkler wrench.  Be
certain to match model, style, orifice,
and temperature rating.

A fire protection system that has

been shut off after an activation
should be repaired and returned to
service immediately.  Inspect the

entire system for damage and replace
or repair as necessary.  Sprinklers
that did not operate but were sub-
jected to corrosive elements of
combustion or excessive tempera-
tures should be inspected, and
replaced if need be.  The 

Authority

Having Jurisdiction will detail mini-
mum replacement requirements and
regulations.

Guarantee:  Central Sprinkler

Company  will repair and/or replace
any products found to be defective in
material or workmanship within a
period of one year from the date of
shipment.  Please refer to the current
Price List for further details of the
warranty.

OBSOLETE

Summary of Contents for GB

Page 1: ...hline tee using a sprinkler wrench This allows easy installation in hard ceilings such as sheet rock as the barrel of the dry pendent would be inaccessible The Model GB and GB QR Dry Pendents have a maximum adjust ment of 11 2 38 1 mm in the extended version allowing ease of field installation and ordering Also the Model GB dry pendent is avail able recessed or flush for situations that require a ...

Page 2: ...oximately flush Order to the nearest 1 4 6 4 mm Minimum A dimension is 2 50 8 mm Recessed The A dimension is measured from the face of the tee to the finished ceiling Minimum A dimension is 21 8 54 6 mm Adjustment is 3 16 4 8 mm Extended The A dimension is measured from the face of the tee to the finished ceiling Follow one of these two options If the A dimension is less than or equal to 31 4 82 6...

Page 3: ...nstall the escutcheon plate easily from the floor Do not over or under tighten the sprinkler to compensate for inaccurate escutcheon plate adjustment Caution If installing in a CPVC system appropriate adaptation must be made to insure that the dry pen dent is being installed into a threaded cast iron ductile iron or malleable iron tee only Special care must be taken when installing with a CPVC sys...

Page 4: ... service Be certain to secure permission from all Authori ties Having Jurisdiction and notify all personnel who may be affected during system shutdown A fire watch during maintenance periods is a recommended precaution To remove the system from service first refer to the system operating guide and valve instruction Drain water and relieve pressure in the pipes Remove the existing unit and install ...