Dry Pendent Design Guidelines

To determine the K-factor, follow these steps:

1.  Determine the K-factor length (NOT The “A” DIMENSION).  The K-factor

is determined as follows:

Flush - “A” dim

7

8

" (22.2 mm) = length for K-factor.

Recessed - “A” dim

3

8

" (9.5 mm) = length for K-factor.

Extended - “A” dim3

1

2

" (88.9 mm) = length for K-factor.

2.  Determine the K-factor for that length by using the K-factor table.

3.  Use the K-Factor at the tee in the branchline for the calculations.

Finished Ceiling

LIne

1" (25 mm)
Thread

“A”

Dimension

(order length)

Main Tube

2 1/2" (63.5 mm)

±

1/8" (3.8 mm)

Ceiling Opening

1 15/16" (49.2 mm)

Inner Cup Dia.

If A is > 3 1/4" (82.6 mm)

Dimension is 4 5/8" (117.5 mm)

(

±

1 1/2" (38.1 mm))

If A is 

 3 1/4" (82.6 mm)

Dimension is 3 5/8" (92.1 mm)

(

±

3/4" (19.1 mm))

Caution:  See step one of installation sequence for appropriate fitting requirements.

Ordering Length for Dry Pendent Heads

Flush 

— The “A” dimension is measured from the face of the tee to the finished ceiling.  This is only approximately flush.  Order

to the nearest 

1

4

" (6.4 mm).   Minimum “A” dimension is 2" (50.8 mm).

Recessed

 — The “A” dimension is measured from the face of the tee to the finished ceiling.  Minimum “A” dimension is 2

1

8

"

(54.6 mm).  Adjustment is 

±

 3

16

" (4.8 mm).

Extended

 — The “A” dimension is measured from the face of the tee to the finished ceiling.  Follow one of these two options:

If the “A” dimension is less than or equal to 3

1

4

" (82.6 mm), total adjustment is 1

1

2

" (38.1 mm) (from the mid point of the

adjustment range 

±

3

4

" (19.1 mm)).  Order to the nearest 

1

4

" (6.4 mm).  Minimum “A” dimension is 0".

If the “A” dimension is greater than 3

1

4

" (82.6 mm), the total adjustment is 3" (76.2 mm) (from the mid point of the adjustment

range 

±

1

1

2

" (38.1 mm)).  Order to the nearest 

1

4

" (6.4 mm).   Minimum “A” dimension is 3

1

4

" (82.6 mm).

Length

K-Factor

(metric)

2

1

2

"

 (63.5 mm) to less than 10

1

8

(76.4 mm)

5.3

(76.4)

10

1

8

(254.1 mm) to less than 17

5

8

(75.0 mm)

5.2

(75.0)

17

5

8

(447.7 mm) to less than 25

1

4

(73.5 mm)

5.1

(73.5)

25

1

4

(641.4 mm) to less than 32

3

4

(72.1 mm)

5.0

(72.1)

32

3

4

(831.9 mm) to less than 40

3

8

(70.7 mm)

4.9

(70.7)

40

3

8

"

 (1025.5 mm) to less than 48" (1219.2 mm)

4.8

(69.2)

K-Factor Table

Finished Ceiling

LIne

1" (25 mm)
Thread

“A”

Dimension

(order length)

Main Tube

2 1/2" (63.5 mm)

±

1/8" (3.8 mm)

Ceiling Opening

1 15/16"

(49.2 mm)

Inner Cup Dia.

OBSOLETE

Summary of Contents for GB

Page 1: ...hline tee using a sprinkler wrench This allows easy installation in hard ceilings such as sheet rock as the barrel of the dry pendent would be inaccessible The Model GB and GB QR Dry Pendents have a maximum adjust ment of 11 2 38 1 mm in the extended version allowing ease of field installation and ordering Also the Model GB dry pendent is avail able recessed or flush for situations that require a ...

Page 2: ...oximately flush Order to the nearest 1 4 6 4 mm Minimum A dimension is 2 50 8 mm Recessed The A dimension is measured from the face of the tee to the finished ceiling Minimum A dimension is 21 8 54 6 mm Adjustment is 3 16 4 8 mm Extended The A dimension is measured from the face of the tee to the finished ceiling Follow one of these two options If the A dimension is less than or equal to 31 4 82 6...

Page 3: ...nstall the escutcheon plate easily from the floor Do not over or under tighten the sprinkler to compensate for inaccurate escutcheon plate adjustment Caution If installing in a CPVC system appropriate adaptation must be made to insure that the dry pen dent is being installed into a threaded cast iron ductile iron or malleable iron tee only Special care must be taken when installing with a CPVC sys...

Page 4: ... service Be certain to secure permission from all Authori ties Having Jurisdiction and notify all personnel who may be affected during system shutdown A fire watch during maintenance periods is a recommended precaution To remove the system from service first refer to the system operating guide and valve instruction Drain water and relieve pressure in the pipes Remove the existing unit and install ...

Reviews: