Manufactured by:  Central Sprinkler Company
451 North Cannon Avenue, Lansdale, Pennsylvania 19446

Product
Description

GB & GB-QR Dry Pendent

No. 5-5.0

Model:  GB & GB-QR Dry Pendent

Style:  Flush, Recessed & Extended

Wrench:
  

Offset 

(flush & extended) Part #1068

  Universal 

(recessed pendent) Part #1069

Orifice Size:  

1

2

(12.7 mm)

K-Factor:  See K-Factor Table on page 2.

Thread Size  1" 

(25 mm)

 N.P.T.

*Temperature Ratings & Bulb Color:

135

°

F/57

°

C

Orange

155

°

F/68

°

C

Red

175

°

F/79

°

C

Yellow

200

°

F/93

°

C

Green

250

°

F/121

°

C

Blue

286

°

F/141

°

C

Blue

360

°

F/182

°

C

Purple

* Refer to chart below for specific temperature

Listings.

Approvals:  U.L., U.L.C.

Technical
Data

The Model GB and GB-QR Dry

Pendent Glass Bulb Sprinklers are
designed for use in special applica-
tions such as freezing environments
or in conditions where sediment or
foreign materials might accumulate in
ordinary drop nipples. They are
available in standard response (5mm
bulb) or quick response (3mm bulb).

A significant installation feature for

the extended version is the built in 3"
(76.2 mm) of adjustment.  This allows
installation of common lengths and
can compensate for field variations.

A larger wrench boss allows the

sprinkler to be installed into the
branchline tee using a sprinkler
wrench.  This allows easy installation
in “hard” ceilings such as sheet rock
as the barrel of the dry pendent
would be inaccessible.

The Model GB and GB-QR Dry

Pendents have a maximum adjust-
ment of 

±

1

1

2

" (38.1 mm) in the

extended version, allowing ease of
field installation and ordering.  Also,
the Model GB dry pendent is avail-
able recessed or flush for situations
that require a more aesthetic appear-
ance.

  Operation:  The glass bulb

capsule operating mechanism
contains a heat-sensitive liquid that
expands upon application of heat.  At
the rated temperature, the frangible
capsule ruptures, thereby releasing
the orifice seal.  The sprinkler then
discharges water in a pre-designed
spray pattern to control or extinguish
the fire.

GB & GB-QR Dry Pendent

1-98

Standard and Quick Response
Flush, Recessed and Extended
Glass Bulb Sprinkler

GB Flush & Extended GB Recessed GB-QR Flush & Extended GB-QR Recessed

135, 155, 175,

135, 155, 175

135, 155, 175,

135, 155, 175

200, 286, 360

200

200, 250

200

U.L. & U.L.C. Temperature Listings

Maximum Working Pressure:
175 psi (12.1 bar)

Factory Hydro Test: 100% at
500 psi (34.5 bar)

Standard Finishes:

Sprinkler: brass, chrome plated,

white

Escutcheon: brass, chrome plated

and white painted

1

2

(12.7 mm)

Orifice
Dry Pendent
Automatic
Sprinklers

Corrosion-Resistant Coatings 

(U.L.

Only): white and black painted

Ceiling Opening:  2 1/4" (57.2 mm)

OBSOLETE

Summary of Contents for GB

Page 1: ...hline tee using a sprinkler wrench This allows easy installation in hard ceilings such as sheet rock as the barrel of the dry pendent would be inaccessible The Model GB and GB QR Dry Pendents have a maximum adjust ment of 11 2 38 1 mm in the extended version allowing ease of field installation and ordering Also the Model GB dry pendent is avail able recessed or flush for situations that require a ...

Page 2: ...oximately flush Order to the nearest 1 4 6 4 mm Minimum A dimension is 2 50 8 mm Recessed The A dimension is measured from the face of the tee to the finished ceiling Minimum A dimension is 21 8 54 6 mm Adjustment is 3 16 4 8 mm Extended The A dimension is measured from the face of the tee to the finished ceiling Follow one of these two options If the A dimension is less than or equal to 31 4 82 6...

Page 3: ...nstall the escutcheon plate easily from the floor Do not over or under tighten the sprinkler to compensate for inaccurate escutcheon plate adjustment Caution If installing in a CPVC system appropriate adaptation must be made to insure that the dry pen dent is being installed into a threaded cast iron ductile iron or malleable iron tee only Special care must be taken when installing with a CPVC sys...

Page 4: ... service Be certain to secure permission from all Authori ties Having Jurisdiction and notify all personnel who may be affected during system shutdown A fire watch during maintenance periods is a recommended precaution To remove the system from service first refer to the system operating guide and valve instruction Drain water and relieve pressure in the pipes Remove the existing unit and install ...

Reviews: