CellarPro AH12S Series Manual Download Page 18

                                                                                             

 

 

V12.21 

 

 

 

 

18 

 

 

 

Humidity Management:  The humidity level in the cellar can be maximized by allowing 
the cooling fans to run at the end of every cooling cycle.  The unit is equipped with an 
Off-Delay relay in the electrical enclosure and can be adjusted from 12 -390 seconds.  
The  recommended  setting  is  180  seconds  (3  minutes).   With  this  setting,  at  the  end 
of each cooling cycle the cooling unit fans will continue to run for 3 minutes.  

 

Integrated  Humidifier  Option:    The  humidifier  cannot  be  controlled  from  the 
Networkable  Thermostat.    A  separate  humidistat  is  provided  with  this  option  that  is 
not networkable.  It must be located inside the cellar along with the NT.  Refer to the 
Integrated  Humidifier  Owner’s  Manual  for  detailed  instructions  on  setting  up  the 
humidistat.    Note:    The  Ecobee4  NT  will  display  the  humidity  level,  and  high/low 
alarms  can  be  set,  but  the  humidity  set  point  can  o nly  be  accessed  on  the  separate 
humidistat. 

 

Temperature Display on Cooling Unit 

The temperature display provided on the cooling unit enhances the functionality of the NT for 
wine cellar applications.  Alarms trigger an audible alarm only at the cooling un it, the alarms 
are not communicated through the NT.  Note that the temperature shown on the unit mounted 
controller  display  may  differ  from  the  NT  display  due  to  the  different  locations  of  the 
temperature  measurements  and  slower  temperature  response  of  NT  devices.    If  there  is  a 
large  difference  between  the  two,  it  may  indicate  that  the  NT  is  not  in  a  good  location.  
Relocate closer to the return air stream in an area that has good airflow.    

 

The  “Set”  button  has  no  effect  since  the  set  point  is  managed  by  the  NT.    The 
controller is programmed to fixed value of SET=4 5 to provide freeze protection.  If the 
unit  mounted  temperature  probe  records  an  inlet  air  temperature  below  4 5°F,  the 
Dixell controller will shut off the compressor overriding a call for coolin g from the NT 
thermostat. 

 

The  following  parameters  and  functions  are  not  available  with  the  NT  configuration:  
HY, FON, SET, HES, Quick Chill and Energy Saver.  

 

A factory preset start up delay of 3 minutes is enabled when power is first supplied to 
the unit.  

 

The defrost cycle will be managed automatically.  When the cooling unit is in defrost, 
“DEF”  is  shown  on  the  display.    Defrosts  are  time  initiated,  temperature  terminated, 
with a factory default of 1 hour (idF=1).  With this setting, every hour the evaporator 
will  go  into  air  defrost  mode,  with  fan  on/compressor  off.    When  the  coil  is  clear  of 
frost the defrost will terminate, followed by a 3 minute off cycle delay.  For installations 
where  there  is  minimal  frost  loading,  the  defrost  frequency  can  be  changed  by 
adjusting the Dixell parameter “idF”.  The values are in hours, for example to change 
the defrost frequency to every 4 hours,  set idF=4. 

 

The power button can be used to turn 

the controller to the “OFF” position. When the 

display  reads  “OFF”, the  compressor  cannot  be  energized,  however  the  NT still  has 
24VAC  power  and  may  continue  to  operate  the  fan,  heater,  and  humidifier .   

To 

completely shut down the system, turn off both the cooling unit and the NT, or 
disconnect power to the cooling unit. 

 

 

Summary of Contents for AH12S Series

Page 1: ...V1 20 CellarPro Large Air Handler Split Systems AH12Sx AH18Sx AH24Sx Residential Commercial 1445 N McDowell Blvd Petaluma CA 94954 877 726 8496 www cellarpro com Outdoor Condensing Unit Evaporator...

Page 2: ...V12 21 2 This page intentionally left blank...

Page 3: ...Sx Model AH Air Handler Nominal Cooling Capacity BTUH at 55 F Cellar Temp 12 12 400 1 25 Ton 18 15 500 1 50 Ton 24 18 200 2 00 Ton Configuration Sx S Split System with Remote Condensing Unit x Designe...

Page 4: ...uminum fin evaporator coils are mounted in a stainless steel condensate pan with a condensate safety switch to guard against condensate overflow Commercial grade Electrofin coating protects the evapor...

Page 5: ...he system will terminate the defrost and return to refrigeration automatically after a 3 minute delay Compressor All systems incorporate scroll compressors for high reliability high efficiency and low...

Page 6: ...to 50 RH The Humidistat must be installed inside the cellar near the return airflow in an area with good air circulation The Humidistat controls the humidity from 5 to 70 RH in 5 increments The humidi...

Page 7: ...lerts and service reminders including air filter monitor over or under temperature high humidity or customer selected contact closure Displays the cellar humidity from 5 to 95 Voice recognition throug...

Page 8: ...V12 21 8 System Airflows Hot Air Exhaust Cold Air Intake From Cellar Cold Air Exhaust To Cellar Fresh Air Intake Rear and Left Side Condensing Unit Evaporator Front System Specifications...

Page 9: ...V12 21 9 Evaporator Cut Sheet Evaporator Piping Connections...

Page 10: ...V12 21 10 Evaporator Wiring Diagram AH12 24Sx...

Page 11: ...V12 21 11 Condensing Unit Cut Sheet DIMENSIONS IN INCHES...

Page 12: ...V12 21 12 Condensing Unit Wiring Diagram AH12 24Sx...

Page 13: ...17 63 20 25 03 30 AH24Sx 208 230V 1Ph 60Hz 4 1 422 7 4 1700 12 5 3000 5 13 15 12 53 20 17 63 20 25 03 30 Evaporator Circuit Rating Evaporator Fan Humidifier Heater Evaporator Circuit Rating Evaporator...

Page 14: ...r Mfg Emerson Copeland Nominal HP RLA LRA Watts MCA Max Fuse AH12Sx 208 230V 1Ph 60Hz XFAM 020Z CFV 081 2 12 0 56 0 1385 16 10 25 AH18Sx 208 230V 1Ph 60Hz XFAM 025Z CFV 081 2 5 18 0 75 0 1755 23 60 40...

Page 15: ...sure the external condensate drain line pitches downward at a slope of one inch every ten feet and terminates to an open drain When installing make sure to properly level the unit to maintain proper...

Page 16: ...to the cooling unit It is now safe to connect the 18 5 thermostat wire to the NT If the NT does not have a remote sensor the NT must be installed inside the cellar It is very important to locate the...

Page 17: ...specified In that case set the mode to Auto Disable all scheduling learning and occupancy tracking functions These routines are intended for comfort cooling and are not suitable for long term wine st...

Page 18: ...at the NT is not in a good location Relocate closer to the return air stream in an area that has good airflow The Set button has no effect since the set point is managed by the NT The controller is pr...

Page 19: ...5 30 30 35 37 42 44 49 50 60 20 23 28 29 34 35 40 42 47 50 60 50 60 60 70 25 30 35 37 42 44 49 50 60 50 60 60 70 60 70 30 38 43 44 49 50 60 50 60 60 70 60 70 65 70 35 44 49 50 60 50 60 60 70 60 70 65...

Page 20: ...g no power is connected to the cooling unit It is now safe to connect the thermostat wire to the Humidistat Ensure that the external control humidistat is located in the cellar near the return air str...

Page 21: ...e no effect on the air handler temperature settings for the cellar The humidistat has a factory set point of 55 RH adjustable in 5 increments using the Up or Down arrows The maximum humidity set point...

Page 22: ...To set the humidifier to Auto press the System button until the following screen is shown Pressing the Up or Down arrows will cause the display to change and the current set point value to blink Use...

Page 23: ...ow the humidistat set point When the cooling unit turns off there will be a spike in humidity that will balance out during the cooling unit off cycle This is caused by water left on the fins of the co...

Page 24: ...the water level reaches a depth of 3 16 The pump is provided with 25 feet of PVC drain tubing This tubing should be routed to a suitable open drain according to the following design limits Over time t...

Page 25: ...kness in Up to 25 feet Over 25 feet up to 50 feet Over 50 feet up to 100 feet Over 100 feet up to 150 feet AH12Sx 3 8 5 8 3 4 3 4 7 8 1 1 8 AH18Sx 1 2 5 8 3 4 7 8 1 1 8 1 1 8 AH24Sx 1 2 5 8 7 8 1 1 8...

Page 26: ...nsing units 1 When the evaporator and condensing unit are located on the same level pipe suction line with inverted trap as shown to prevent liquid migration to the compressor during the off cycle Pit...

Page 27: ...ction line with inverted trap as shown to prevent liquid migration to the compressor during the off cycle The vertical lift of the liquid line is limited to 30 feet The lift may be increased to 60 fee...

Page 28: ...access valves on the condensing unit to make sure the system is fully evacuated If the vacuum is achieved proceed to the next step otherwise locate and repair the leak and repeat from step 4 5 Disconn...

Page 29: ...tional details on the operation of the condensing unit 8 Measure pressures and temperatures to verify the system is within normal operating limits as indicated on the Split System Data Sheet A loose c...

Page 30: ...ce the unit to cycle off Once the solenoid valve closes the system pumps down and the condensing shuts off based on the value of the Low Pressure Cut Out parameter Cou If the condensing unit does not...

Page 31: ...stem Charge lbs by Split System Model ft AH12 AH18 AH24 5 5 98 6 17 6 35 10 6 19 6 56 6 75 15 6 40 6 96 7 15 20 6 61 7 35 7 55 25 6 81 7 74 7 95 30 7 02 8 18 8 44 35 7 23 8 58 8 86 40 7 44 8 98 9 27 4...

Page 32: ...warranty applies only to cooling units purchased from the factory or an authorized dealer Damage caused by others or by any cause beyond the control of CellarPro shall not be considered defects in ma...

Page 33: ...ed with water and tested for drainage Y N Operation Start Date Initial Refrigerant Charge Through Check One ____ Suction Access Valve ___ Liquid Access Valve Operational Data Take the following measur...

Reviews: