11.
- To set Alarm1 percentage
Example:-
12.
- To set Alarm2 percentage
Example:-
12.
- To set Trip percentage
Example:-
13.
- To Test outputs
14.
- To set Integration
,
15.
- To Manipulating Error
,
Note:-
Again press
key, Display shows
,
.
Again press
key, Display shows
, it is the percentage value of running demand period at which Alarm2 will
be on full normal period.
.
Again press
key, Display shows
, it is the percentage value of running demand period at which Trip will
be on full normal period.
.
Again press
key, Display shows
Use
key, Display show
and AL1 LED glows, and Alarm1 on in 10 seconds.
Again press
key, Display show
and AL2 LED glows, Alarm2 on in 10 seconds.
Again press
key, Display show
and Trip LED glows, Trip on in 5 seconds.
Again press
key, Display shows
it should be equal to energy meter.
Again press
key, Display shows
This feature is for matching controller kW with energy meter kW and
hence RD running demand will match automatically.
= 100 - actual controller calibration
= 110 - 10% addition to the actual controller calibration
= 90
- 10% below actual controller calibration
Measurement should be stimulation from controller and energy meter for matching.
Alarm1 energizes when kW More than Set MD.
If user set target demand at 160 kW and AL1 is at 110
Then over load limit will be 160x110/100 = 176 kW
As the running load exceeds 176 Alarm1 will be ON.
If user set target demand at 160 kW and AL2 is at 95
There limit for Alarm2 will be 160x95/100 = 152 kW
As Rising Demand (RD) reaching 152 Alarm2 will be ON.
If user set target demand at 160 kW and Trip is at 100
There limit for Alarm2 will be 160x100/100 = 160 kW
As Rising Demand (RD) reaching 160 Trip will be working 5 seconds.
Use
and
keys to set Alarm1 value.
Use
and
keys to set Alarm2 value.
Use
and
keys to set Trip value.
Use
and
keys to set integration time 15 and 30 minutes.
Suit the Integration time equal to energy meter Integration time usual it is 30 minutes
Use
and
keys to increase and decrease value.
User Manual
MDI-CONTROLLER
98MDC