9.1. COMBINING MEASUREMENTS/SENSORS
In DES-300 sensor can be combine measurements/sensors together, as in the table below.
Sensor
T
TE
H
AP
TA/PA
L
SL
PIR
CO2
T
-
-
+
+
+
+
+
+
-
TE
-
-
-
-
-
-
-
-
-
H
+
-
-
+
+
+
+
+
-
AP
+
-
+
-
+
+
+
+
-
TA/PA
+
-
+
+
-
+
+
-
-
L
+
-
+
+
+
-
+
+
-
SL
+
-
+
+
+
+
-
+
-
PIR
+
-
+
+
-
+
+
-
-
CO2
-
-
-
-
-
-
-
-
-
+ - measurements/sensors can be combine
- - measurements/sensors can not be combine
10. SPECIFICATIONS
Parameters
Data
Parameters of Temperature Sensor
Measuring range of temperature
-55°C ... +125°C
1-WIRE Transducer
DS18B20
Measuring accuracy of temperature transducer
+/-0,5°C in the scope -10°C...+85°C
Temperature transducer resolution
12 bits (0,06°C)
Operating temperature
-55°C ... +125°C
Parameters of Humidity Sensor
Measuring range of relative humidity
0% ... 100% RH
Measuring accuracy of relative humidity
+/-3,50% RH
Operating temperature
-40°C ... +85°C
Parameters of Atmospheric Pressure Sensor
Measuring range of atmospheric pressure
150 hPa ... 1150 hPa
Measuring accuracy of atmospheric pressure
+/-15 hPa
Operating temperature
-40°C ... +85°C
Parameters of Temperature Adjuster
Range of temperature adjuster
+5°C ... +40°C
Accuracy of temperature adjuster
+/-1 °C
Operating temperature
-20°C ... +75°C
Parameters of Percent Value Adjuster
Range of values adjuster
0% ... 100%
Accuracy of values adjuster
+/-1 %
Operating temperature
-20°C ... +75°C
Parameters of Lighting Sensor
Measuring range of lighting
0% ... 100% Lux
Measuring accuracy of lighting
+/-0,5% Lux
Operating temperature
-30°C ... +70°C
Parameters of Sunlight Sensor
13