Universal Power Supply Plus (UPS Plus)
English
© CEDES | V 1.0
7
6.5 Wiring cegard/Mini in combination with IMS 100
Follow the wiring diagram (Figure 4) to connect e.g a cegard/Mini in combination with a IMS100 to the elevator
controller. For the functional description of the cegard/Mini light curtain and the IMS 100 please refer to the manuals
on www.cedes.com.
Figure 4:
Wiring of the UPS Plus with the cegard/Mini light curtain in combination with the IMS 100 3D sensor
6.6 Power-up and test for proper function
Turn on power after the sensor has been correctly installed
in conjunction with the UPS Plus. The start-up time for the
UPS Plus takes max. 4 s.
The green LED in the UPS Plus indicates that there is supply
voltage available.
An orange LED indicates the status of the sensor input 1
and the output relay 1.
A red LED indicates the status of the sensor input 2 and
the output relay 2.
NO
COM
Buzzer
Test
ON
OFF
LED
Power
Green
Power OK
No power
ON
OFF
Orange
Red
Input 1
Input 2
Outputs
-
Test
Test+
Test-
V V
Sensor connection
24 V
0 V
Input 1
Input 2
Test_out
Logic_sel
V V
V
V
V V
Output
relay 1
Power
N
CO
M
NC
NO
Output
relay 2
CO
M
NC
NO
L
V V
V
V V
V
V V
V
IMS 100
L
N
Emitter
Receiver
UPS Plus LED definition:
- Power LED (green) is ON, if supply voltage is connected correctly.
- Input LED (orange) is ON, if the protected area is obstructed.
- Input LED (red) is ON, if the protected area is obstructed.
Relay definition:
In the configuration shown, the relay is energized if there is
voltage applied and there is no obstruction. Contact between
COM and NO (safest connection).
*
Time-out selector connection (white wire) has to be connected (depending on the requested time-out setting)
Time-out setting
Connect the white wire from IMS 100 to 24 VDC for 18 s **
Connect the white wire from IMS100 to GND (0 V) for Infinity
For more details refer to the IMS 100 manual on www.cedes.com
** The timer begins to count after the first sensor triggering. After this time the sensor will be disabled until the
next door opening.
Buzzer definition:
- Buzzer is OFF, if the protected area (light curtain) is not obstructed.
- The buzzer can be turned on/off by using a switch.
Protective
ground
Supply voltage:
20 ... 265 VAC
20 ... 375 VDC
Output relay 1
To the
elevator controller
Output relay 2
blue
black
white
brown
blue
brown
black
white
*
Orange LED
Sensor input 1 Output relay 1
ON
LOW
COM = NC
OFF
HIGH
COM = NO
Red LED
Sensor input 2 Output relay 2
ON
LOW
COM = NC
OFF
HIGH
COM = NO