Especially with inductive loads, a relay output may cause flickering, flickering, flickering, or malfunction. If this happens, it will be 
necessary to install an anti-spark circuit between the two relay contacts used in the connection, which will ensure the absorption of 
the peak current that causes the aforementioned problem. Note fig. 2. If the load connected to the circuit relay is powered at 230 V. 
apply a 100nF/400 V. capacitor and a 47 ohm ½ W resistor. If you have a 100nF type X2 capacitor (more effective), resistance will 
not be necessary. In applications where the load is powered at 230VAC, the installation will consider only the condenser, without 
the resistor. It should be tested with values between 10 nF and 47 nF until the fluctuation disappears.

4

INFORMATION REGARDING ENVIRONMENTAL PROTECTION

When this product is no longer in use, it cannot be disposed of with normal household waste, it must be taken to a 
selective collection point for the recycling of electrical and electronic equipment. A symbol on the product, the 
instructions for use or the packaging indicates this. Materials are recyclable as marked. If you reuse, recycle or 
otherwise use old appliances you are making an important contribution towards protecting the environment. Please 
ask your local council which is the closest appropriate disposal point or landfill to your home.

 

CONSIDERATIONS / WARRANTY

This kit is intended for use by professionals, or users with a technical level or sufficient knowledge, which allows them to develop 
the desired projects or applications by themselves. If it is used for educational use, its use and assembly under the supervision 
of teaching staff is recommended. Cebek products have a 3-year guarantee from the date of purchase. Incorrect assembly or 
handling is excluded. We reserve the right to introduce technical alterations. We do not take any responsibility for printing errors. 
The technical documentation of this product responds to a transcription of that provided by the manufacturer.

www.cebek.com

    -    [email protected]

Fig 2 filter anti-relay fluctuations
230V AC load from 50W

power load

Normally closed
Normally open

Charging

device

Summary of Contents for TL-602

Page 1: ...me Transmitter command delay relay response 0 2 sec Compatibility Group 3 RF Emitters TL 300 TL 301 Weight 420 grams Measurements 98 75 x 72 x 30 mm Working temperature 10ºC to 45ºC Regulations Electromagnetic compatibility 89 336 CEE and its modifications 23 31 CEE and 93 68 CEE with the ETS 300 200 regulation Insulation IP55 INSTALLATION The power supply must be made on the Power input directly ...

Page 2: ...er when the led of the first relay lights up briefly press Select the new relay will be selected and its corresponding led will light up From that moment on the rest of the process must simply be completed The memory is FIFO so from the pairing with 5 transmitters the next programmed will occupy the memory that was allocated to the first another one would replace the memory initially allocated to ...

Page 3: ...ght bulb common NC NC NO NO Relay 2 Relay 1 Relay connection Load control The relay connection should not be considered as an output it does not provide voltage Electrically isolated from the rest of the circuit its function is to open or close its contacts to allow or interrupt the passage of an electrical signal as a common switch would do on a light bulb The relay has three terminals Common Nor...

Page 4: ...ctrical and electronic equipment A symbol on the product the instructions for use or the packaging indicates this Materials are recyclable as marked If you reuse recycle or otherwise use old appliances you are making an important contribution towards protecting the environment Please ask your local council which is the closest appropriate disposal point or landfill to your home CONSIDERATIONS WARR...

Reviews: